Danfoss CSV 2, CSV 22, CSV 3, CSV 6, CSV 10 Data sheet

...
Data Sheet
Solenoid valve and coil Type CSV 2 - CSV 22
Normally Closed (NC)
CSV is a direct or servo-operated solenoid valve for liquid, suction, and hot gas lines with common uorinated refrigerants.
CSV valves are for refrigeration, freezing, and air conditioning plants.
CSV valves and coils are sold separately.
Features
• Designed for media temperatures up to 105 °C / 221 °F
• Supplied as normally closed (NC) with de­energized coil
• Wide choice of coils for AC and DC
• Suitable for listed refrigerants, including ammable refrigerants
• Available in are and solder connection
3
8 in
1
2 in
versions Flare connections up to
• Solder connections up to 1
• Small encapsulated coils with long life time under extreme conditions.
• Compact construction with small dimensions, low weight for both valve and coil
• Simple and fast mounting of coil - clip-ON / OFF
AI153586441354en-000801
Features
Description
Refrigerant
R22, R134a, R404A, R507, R407C, R513A, R452A, R1234ze, R600, R600a and R290.
Temperature of medium
-40 – 105 °C / -40 – 221°F (Maximum 130 °C / 265 °F during defrosting)
Maximum working pressure
35 bar / 508 psig
Solenoid valve and coil, Type CSV 2 - CSV 22
Media
Table 1: Media features
For a complete list of approved refrigerants, visit store.danfoss.com and search for individual code numbers, where refrigerants are listed as part of technical data.
NOTE:
Special note for R1234ze(E), R290, R600 and R600a: Ignition risk is evaluated in accordance to ISO 5149 and IEC
60335. EX range Zone 2(category 3 IIA).
For countries where safety standards are not an indispensable part of the safety system Danfoss recommends the installer gets a third party approval of any system containing ammable refrigerant.
NOTE:
• Please follow specic selection criteria stated in the data sheet for these particular refrigerants.
• CSV is not suitable for oil free application. For detailed informations please contact Danfoss
• Flare connections are only approved for A1 and A2L refrigerants.
© Danfoss | Climate Solutions | 2021.02 AI153586441354en-000801 | 2
Type
Kv (m3/h)
R22/R407C
R134a
R404A/R507
R290
R513A
R452A
R600
R600a
R1234ze(E)
CSV 2
0.1
2.01
1.86
1.36
2.24
1.66
1.38
2.53
2.25
1.66
CSV 3
0.3
6.03
5.58
4.09
6.72
4.97
4.15
7.6
6.76
4.99
CSV 6
0.54
10.86
10.05
7.35
12.09
8.95
7.48
13.69
12.18
8.98
CSV 10
1.5
30.17
27.91
20.43
33.59
24.85
20.76
38.02
33.82
24.93
CSV 15
2.6
52.3
48.38
35.41
58.22
43.07
35.99
65.89
58.62
43.22
CSV 20
5
100.57
93.04
68.1
111.96
82.83
69.22
126.72
112.74
83.12
CSV 22
6
120.68
111.65
81.72NA99.39
83.06NANA
NA
Type
Kv (m3/h)
R22/R407C
R134a
R404A/R507
R290
R513A
R452A
R600
R600a
R1234ze(E)
CSV 2
0.1
0.22
0.16
0.19
0.27
0.16
0.19
0.13
0.15
0.13
CSV 3
0.3
0.67
0.48
0.58
0.82
0.47
0.56
0.38
0.45
0.39
CSV 6
0.54
1.2
0.87
1.05
1.47
0.8410.68
0.82
0.7
CSV 10
1.5
3.33
2.42
2.91
4.08
2.35
2.78
1.89
2.27
1.95
CSV 15
2.6
5.77
4.2
5.04
7.07
4.07
4.81
3.27
3.93
3.38
CSV 20511.1
8.08
9.69
13.6
7.82
9.26
6.3
7.56
6.49
CSV 22613.32
9.69
11.61NA9.38
11.11NANA
NA
Type
K
v
(m3/h)
R22/R407C
R134a
R404A/R507
R290
R513A
R452A
R600
R600a
R1234ze(E)
CSV 2
0.1
0.9
0.69
0.74
1.02
0.64
0.76
0.56
0.63
0.56
CSV 3
0.3
2.69
2.08
2.22
3.07
1.93
2.29
1.68
1.89
1.67
CSV 6
0.54
4.85
3.75
3.99
5.53
3.48
4.12
3.03
3.4
3.01
CSV 10
1.5
13.46
10.38
11.05
15.35
9.66
11.44
8.42
9.45
8.37
CSV 15
2.6
23.34
17.99
19.15
26.61
16.75
19.83
14.6
16.38
14.51
CSV 20544.88
34.59
36.83
51.18
32.21
38.13
28.07
31.5
27.91
CSV 22653.86
41.51
44.2NA38.65
45.76NANA
NA
Solenoid valve and coil, Type CSV 2 - CSV 22
Product specication
Rated capacity [KW]
Table 2: Rated capacity [KW] for Liquid
Table 3: Rated capacity [KW] for Suction
Rated liquid and suction vapour capacity is based on:
• evaporating temperature te = -10 °C
• liquid temperature ahead of valve tl = 25 °C
• pressure drop in valve ∆p = 0.15 bar
Table 4: Rated capacity [KW] for Hot-gas
Rated hot gas capacity is based on:
• condensing temperature tc = 40 °C
• pressure drop across valve ∆p = 0.8 bar
• hot gas temperature th = 65 °C
• subcooling of refrigerant ∆t
sub
= 4 K
Valve selection based on capacity calculation
As for extended capacity calculations and valve selection based on capacities and refrigerants, please refer to Coolselector®2. Rated and extended capacities are calculated with the Coolselector®2 calculation engine to ARI standards with the ASEREP equations based on laboratory measurements of selected valves.