Danfoss CRCT230HC1, CRCT230 HC1A Installation guide

CRCT230HC1 &
CRCT230 HC1A
Electronic Heat / Cool thermostat
with auto-changeover
GB
Installation Instructions User Instructions
GB
Index
Installation Instructions 3-8 User Instructions 9
Installation Instructions
Installation Instructions
Please note
This product should only be installed be a suitably qualifi ed electrician or heating installer. The installation must comply with local Building Regulations and wiring Regulations, including any
competent person requirements that may exist
Product Specifi cation
GB
Thermostat features
Temperature range, heating 5-30°C
Temperature range, cooling 7-32°C at dead-band of 2K
9-34°C at dead-band of 4K
Selectable dead-band 2 or 4K
Thermostat off /auto & fan on
selector
Power supply 230 Vac ± 15%, 50/60Hz
Installation Instructions
Relay outputs, heat, cool & fan 3 x SPST, 3(1)A, 10-230 Vac, Type
1B
Dimensions (mm) 110 wide x 90 high x 40 high
Design standard EN60730-2-9
Rated impulse voltage 2.5Kv
Ball hardness test 75°C
Control pollution situation Degree 2
Temperature accuracy ±1°C
GB
Product overview
The thermostat is primarily designed for use in systems equipped with 4-pipe fan-coil units. It may also be used in other heat / cool systems, including split systems and air to air heat-pumps.
The thermostat controls room temperature by sequencing the operation of heating and cooling. A selectable dead-band prevents overlap of heating and cooling processes. For systems equipped with compressor derived cooling, including heat-pumps, a selectable compressor delay timer is also included. If used to control a heat­pump, the reversing valve can be energisation on either a heat or cool
demand.
Installation Instructions
Installation
First, remove the wallplate from the back of the unit.
Ensure that there is a minimum of 50mm above the unit and 100mm below the unit in order to mount the plug-in module.
Fix at a height of approximately 1.5m from the fl oor, away from draughts or heat sources such a fan-coil outlets, sunlight or offi ce equipment.
Wiring
X SEN
X SEN
N
L
FAN
1
COM
HEAT/
RV
COOL/ COMP.
1
SPEED
FAN
ELECTRONICS
N
COOLING OUTPUT
HEATING OUTPUT
COMMON IN
(LIVE IN)
REMOTE SENSOR
('A' MODELS ONLY)
230 VAC
FIXED 3A
N
L
N
L
FAN
1
COM
HEAT/
RV
COOL/ COMP.
ELECTRONICS
N
COMPRESSOR
REVERSING VALVE
COMMON
(LIVE IN)
REMOTE SENSOR
('A' MODELS ONLY)
230 VAC
FIXED 3A
X SEN
X SEN
1
SPEED
FAN
4-pipe fan coil application
GB
Note:
If HEAT/COOL/FAN outputs are 230V, link terminals L - COM
Installation Instructions
Heat-pump application
Note:
If HEAT/COOL/FAN outputs are 230V, link terminals L - COM
GB
ON
On/Off
Chrono
Chrono 3Chrono 6
°C
°F
No Comp Del
Comp Del
3 Minutes
4 Minutes
DB 2°C/4°F
DB 4°C/8°F
Fan Coil Heat Pump
RV-
RV+
Sw On
1
2
3
4
5
6
7
8
Commissioning
Prior to re-fi tting the thermostat to the wallplate, the DIL switches on the rear of the unit must be set to the desired setting.
Installation Instructions
DIL Switch options, shown in factory set position.
DIL Switch descriptions
Switch 8: If set to On/Off , both heating and cooling stages operate
in on/off mode. If set to Chrono, heating stage operates in chrono-proportional modes, cooling continues in On/off mode.
Switch 7: Active only if switch 8 is set to Chrono. This switch
determines the number of cycles per hour that the thermostat will impose on the system, the options are three 20 minute cycles or six 10 minute cycles.
GB
Switch 6: Allows Celsius or Fahrenheit temperature scaling to be
selected.
Switch 5: Enables or disables a compressor delay timer which is
activated at the end of each cooling call. This feature need only be used where cooling is provided by a compressor as opposed to chilled water. Set to Cmp del if a compressor delay is required, otherwise leave set to No Cmp del.
Switch 4: Active only if switch 5 is set to Cmp del. The options are 3
or 4 minutes.
Installation Instructions
Switch 3: Allows dead-band between heating and cooling to be set,
options are 2°C or 4°C.
Switch 2: Allows application to set as fan coil or as heat pump. If
heat-pump is selected, the output normally used to operate the heating valve is re-assigned to the heat-pump reversing valve, the compressor stop/start signal for both heat and cool calls is re-assigned to the relay normally used to operate the cooling valve.
Switch 1: The function of this switch is dependent upon the setting
of switch 2:
Switch 2 set to Heat-pump: allows the reversing valve to be set up to be energised in heating mode (R+), or energised in cooling mode (R-)
GB
Mounting thermostat to the wallplate
To mount the thermostat to the wallplate, align the tabs on the top of the thermostat with the apertures in the wallplate and hinge the thermostat down, pressing fi rmly to engage the securing clip in the wallplate.
Installation Instructions
Locking & limiting
To lock or limit the setting range turn the setting dial to 3 and remove knob.
Position the locking springs on the rear of the dial to the desired position and re-mount the knob ensuring that number 3 on the dial aligns with the reference mark on the case.
LED lit red during heating
demand
LED lit green when cooling
demand.
LED fl ashes green during
GB
compressor delay period
User Instructions
RESET
button
Temperature setting dial, read
setting off LCD display
LCD display, shows actual room temperature unless knob is moved at which time a
fl ashing set temperature is momentarily displayed. During heating demand a fl ame
symbol is lit, during cooling demand a snowfl ake symbol is lit
Fan runs continuously
Fan runs with heat or
cool demand
Thermostat off
LED lit green when
thermostat is powered
LED lit orange when fan
running
Note: Should it be necessary to reset the microprocessor for any reason, a reset button is located beneath the setting dial. Use a non-metallic
point, for example a match- stick to depress the recessed button.
101112
www.danfoss.com/BusinessAreas/Heating
This product complies with the following EC Directives:
Electro-Magnetic Compatibility Directive.
(EMC) (2004/108/EC)
Low Voltage Directive.
(LVD) (2006/95/EC)
Part No 3501v01 08/08