Danfoss CRCP24 Data sheet

Datasheet
CRCP24 Range 0-10v Proportional Heat/Cool Thermostats
Features
The CRCP range off ers 0-10v output proportional control designed for use controlling fan coil or chilled ceiling units or any other system that requires 0-10v proportional control. Available with various options for manual or auto fan speed control as well as options for using motorised or thermoelectric wax actuators, these thermostats provide an economic standalone solution for most manual fan coil or chilled ceiling requirements.
The thermostats use P+I (Proportional + Integral) control, with the output being proportional to the deviation from the set temperature within a 2k band (see diagram below).
OUTPUT
100% (10V)
0% (0V)
The range consists of four models:
CRCP24
The CRCP24 is ideal for chilled ceiling applications. Having no fan outputs, a simple selection of motorised or wax actuator and whether the thermostat is to act as a heat or cool thermostat is all that is needed to set up this thermostat at time of installation.
CRCP24 CO
Like the CRCP24, the CRCP24 CO is a temperature
Part No. 744v01 07/08
Xp=2K
Heating
SET POINT
Xp=2K
Cooling
only proportional thermostat but with a manual heating or cooling changeover switch present on the front of the unit.
CRCP24 CO1
The CRCP24 CO1 has a front mounted heat/cool changeover switch, as well as a single speed fan output. The fan works in either constant (constant on) or automatic (on/off dependant of output state). Fan operation mode is selected at time of installation via DIL switches within the case. * Fan output can also be used for damper operation instead of a fan.
CRCP24 CO3
The CRCP24 CO3 off ers all the features of the CRCP24 CO with the addition of a manually selectable 3 speed fan with front mounted switch. Fan operation mode is selected at time of installation via DIL switches within the case.
Visual feedback of the thermostat status is available at all times via a combination of two bi-colour LEDs showing both the heat or cool output status as well as the fan ready state (continuous or auto).
Fan operation and actuator type selection is made on the rear of the thermostat prior to installation via the use of DIL switch. Two fan operation modes are available – Fan Auto or Fan Continuous. Setting the unit to Fan Continuous will enable the running of the fan whenever the unit is in either heating or cooling mode. Fan Auto setting enables the running of the fan only when the temperature is 0.2ºC above or below the Setpoint (depending on heat/cool mode).
Due to the diff erent operating characteristics of motorised and thermal wax actuators a DIL switch selection of either MOT (motorised actuator) or WAX (thermoelectric wax actuator) is possible. Changing this switch from MOT to WAX increases the integration time in the heat/cool algorithm compensating for the slower response time of the thermoelectric type actuators, likewise, selection of MOT reduces the integration time to allow for faster responding motorised actuators.
All models off er a range of standard features including active frost protection (fi xed 8ºC etpoint), standby mode (available in cooling only) and a range locking/limiting function.
0-10v Proportional Control
Frost Protection
Standby Mode
MOT or WAX actuator selection
LED status indicators
1
Datasheet CRCP24 Proportional Heat/Cool Thermostats
Wiring
CRCP24
A
0V
24 Vac
24V
ELECTRONICS
B
1
3
2
4
V out
0V
output
0-10V
CRCP24 CO
Electronics
Cool
Heat
0-10V outputs
CRCP24 CO1 CRCP24 CO3
Cool
Heat
0-10V outputs
Electronics
A B
0V
24 Vac
Heating
or
Cooling
24V
0V/
return
COM
Fan 1
1 Speed
Fan
Common In
N
Cool
Heat
0-10V outputs
Electronics
A B
0V
24 Vac
Heating
or
Cooling
A B
0V
24 Vac
Heating
or
Cooling
24V
24V
0V/
return
0V/
return
COM
COM
Fan 2
Fan 3
Fan 1
3 Speed
Fan
Common In
N
Application Example
+
-
Fan-coil Control
DIL Switch Selection Switch 1: Fan Con - Fan will run whenever
1
Fan Con
2
MOT
Sw On
Fan Auto
WAX
thermostat is in heating or cooling mode.
Fan Auto - Fan will run whenever
temperature is 0.2°C or more above/ below (depending on heat/cool mode) setpoint. When temperature reaches setpoint, the fan will switch off .
Switch 2: MOT - Motorised valve actuator
selection.
WAX - Wax valve actuator selection.
2
Part No. 744v01 07/08