CRA122 Package Contents
SERIES CRA122
Setpoint Temperature Controller
Power source
24 VAC
Ambient temp: 23°F to 131°F (-5°C to 55°C)
Flow temp. range: 4°F to 200°F (5°C to 95°C)
Power supply: 24 ± 10%, 60 Hz
Power consumption: 3VA
Max run time at max speed: 120 seconds
Weight: 2 lbs (0,9 kg)
Assembly Orientation
2
3MG, 4MG
3G, 4G 3F, 4F up to 6"
VRG valves + Mounting Kit
(ordered separately
code NO: 193B1616)
Temperature Sensor Installation
Wrap the sensor
ADAPTER K IT 900
SERIES CRA120

NOpen Close
T2
N
24V∼
24V∼
Open
Close
ActuatorSupply
Temperature sensor
24 VAC Power Source
min 3VA rating
min. Standard
18 AWG-Solid wire
for low voltage wiring
Temp.sensor
Secondary
Temperature
Setpoint
+++
24V
+
OK
24V
HoldReset
Wiring
3 4
Setting Rotation Time
Selection Buttons
Factory Reset
1
2
0
s
s
0
2
1
24VAC
4 seconds
OK
Press and
hold
OK
Scroll Press Adjust
4 seconds
Press and
hold
*Rotation time shown only at 50Hz
*at 50Hz
at 60Hz
15 sec 12 sec
30 sec 25 sec
60 sec 50 sec
120 sec 100 sec
240 sec 200 sec
480 sec 398 sec

~140 - 176 °F
~104 - 122 °F
120 °F
~140 - 176 °F
~104 - 122 °F
120 °F
Adjust
Adjust
OK
Max 100 Ω
Press
Wait
OK
Press
Wait
Open
OK
Max 100 Ω
Press
Wait
OK
Press
Wait
Closed
Open
Maximum Temperature Limitation
= MAX °
Max°F
Default: 120F (49C)
Maximum temperature
Setting: 200F (95C)
4 seconds
Press and hold Press and holdPress Press
Minimum Temperature Limitation
= MIN °
OK
Press and hold Scroll
Changing of Setpoint
MAX
MAX
+
Adjust
MIN
OK
Press Adjust
T °F
OK OKOKOK
Wait
4 seconds
Min °F
OK OK
Press
Default: 41F (5C)
Minimum temperature
Setting: 41F (5C)
Wait
Press and hold
Adjust
OK
Press
Wait

Select
OK
Adjust
Externally Wired Relay
Closed
Max 100 Ω
°F / °C Temperature Unit Display
Press
Wait
OK
Press
Wait
Open
10 seconds
OK
Press and
hold
Scroll Press Adjust
OK
T2, Secondary Temperature Setpoint
Max 100 Ω
: Secondary Temperature Setting : Primary Temperature Setting
Externally Wired Relay
OK
Wait
Adjust
Press
Actuator Rotation Adjustment
if actuator rotation requires more than or less than 90° actuator rotation
OK
Press Wait
Open
Adjust
OK
Wait
Press
Remove power to the actuator
!
A B
CCWCW
>90˚ 90˚ <90˚
Default Setting