Danfoss CF-DS Data sheet

Data Sheet
CF-DS Dew Point Sensor
Application
Ordering
Technical Data
The CF-DS dew point sensor is used in oor heating/cooling systems to protect against building of condensation. The CF-DS is strapped onto the supply pipe and connected to the Global Standby input on the CF-MC Master Controller. CF-DS measures the relative air humidity compared to the pipe temperature. At 90% RH the dew point sensor sends a signal to the CF-MC Master Controller, which closes the cooling supply pipes.
Product Code no.
CF-DS dew point sensor 088U0251
Humidity sensor HC 105 Working range 10 - 100% RH Switching point at 20°C / 68°F 90±3% RH Switching hysteresis 5% RH Response time, change of surface temperature t90 < 3 min. Response time, change of relative humidity t90 < 25 sec. Electrical output potential free relay with changeover contact Switching capacity max. 24 V AC/DC, 1 A Supply voltage 24 V AC/DC ± 20% Current consumption at 24 V DC < 3 mA Relay status indication LED (red) Electrical connection 5-pole push-in terminal, max. 1.5 mm² Dust protection by special coating (permeable for water vapour) Housing protection class IP40 Housing material PC, re resistant (according to UL94-V0) Electromagnetic compatibility EN 61326-1, EN 61326-2-3 Working temperature 0 - 50° C (32 - 122° F) Storage temperature -20 - 70° C (-4 - 158° F) Size (L x H x W) 63 x 54 x 23 mm Weight approx. 60 g
VDSPI302
© Danfoss | FHH | 2015.09 | 1
Mounting
max. Ø 50 mm (2“)
24
D
Wiring Connections
+
V+
~
V AC/DC ± 20%
-
GND
~
NC COM NO
Status indication:
• LED continuous light: Operating < 90% RH
• LED blinking: Condensation danger
Heat-conductive lm
LE
Danfoss A/S
Floor Heating Hydronics • Ulvehavevej 61 • DK-7100 Vejle • Denmark • Phone: +45 7488 8500 • Fax: +45 7488 8501 heating@danfoss.com • www.oorheating.danfoss.com
Danfoss ca n accept no respons ibility for pos sible errors in ca talogues, bro chures and other pr inted material. Da nfoss reserves t he right to alter its p roducts with out notice. This als o applies to produ cts already o n order provided t hat such alteratio ns can be made with out subsequenti al changes being n ecessary in spe cications alr eady agreed. All trade marks in this mate rial are proper ty of the respec tive companies . Danfoss and the Dan foss logotyp e are trademark s of Danfoss A/S. Al l rights reserv ed.