Danfoss CDS 803 Operating guide

Operating Guide
VLT® Compressor Drive CDS 803
6–30 kW
vlt-drives.danfoss.com
LanguagesOperating Guide | VLT® Compressor Drive CDS 803

Languages

1
American English 5
2
Chinese simplified 49
3
French 91
4
5
Italian 179
6
Brazilian Portuguese 223
7
Russian 267
8
Spanish 317
AQ32174876762701-000301/130R0627 | 3Danfoss A/S © 2021.06
Operating Guide | VLT® Compressor Drive CDS 803 Languages
AQ32174876762701-000301/130R06274 | Danfoss A/S © 2021.06
VLT® Compressor Drive CDS 803

American English

Operating Guide
Contents
1
Introduction 8
1.1
Purpose of this Operating Guide 8
Additional Resources 8
1.2
Supplementary Documentation 8
1.2.1
1.2.2
VLT® Motion Control Tool MCT 10 Software Support 8
1.3
Manual and Software Version 8
1.4
Approvals and Certifications 8
1.5
Disposal 9
1.6
CE Declaration 10
Safety 12
2
Safety Symbols 12
2.1
Qualified Personnel 12
2.2
Contents
Safety Precautions 12
2.3
Installation 14
3
3.1
Mechanical Installation 14
3.1.1
Side-by-side Installation 14
3.1.2
Operating Environment 14
3.1.2.1
3.1.2.2
3.2
Electrical Installation 14
3.2.1
Electrical Installation in General 14
3.2.1.1
3.2.2
Fuses and Circuit Breakers 15
3.2.2.1
3.2.3
Electrical Wiring 15
3.2.3.1
3.2.3.2
3.2.3.3
Derating for Ambient Temperature and Switching Frequency 14
Derating for Low Air Pressure and High Altitudes 14
Fastener Torque Ratings 14
Recommendation of Fuses and Circuit Breakers 15
Wiring Schematic 15
Terminal Overview of Enclosure Sizes H3–H5 17
Terminal Overview of Enclosure Size H6 18
3.2.4
3.2.5
4
Commissioning 26
4.1
Programming Interfaces 26
3.2.3.4
3.2.3.5
3.2.3.6
Setting Up RS485 Serial Communication 21
EMC-compliant Electrical Installation 22
Connecting to Mains and Compressor Terminals 18
Relay Terminals 19
Control Terminals 20
AQ32174876762701-000301/130R0627 | 5Danfoss A/S © 2021.06
VLT® Compressor Drive CDS 803
American English
Operating Guide
4.2
Local Control Panel (LCP) 26
4.2.1
Programming via the Quick Menu 27
4.2.2
Programming via the Main Menu 27
4.2.3
Data Transfer from Drive to LCP 28
4.2.4
Data Transfer from LCP to Drive 28
4.2.5
Restoring Factory Default Settings 28
4.2.5.1
4.2.5.2
4.3
Starting Up the Drive for the First Time 29
5
Troubleshooting 30
5.1
Acoustic Noise or Vibration 30
5.2
Warnings and Alarms 30
6
Specifications 34
Recommended Initialization (via Parameter 14-22 Operation Mode) 28
Two-finger Initialization 29
Contents
6.1
Electrical Data 34
6.1.1
Electrical Data 3x200–240 V AC 34
6.1.2
Electrical Data 3x380–480 V AC 34
6.2
Mains Supply (L1, L2, L3) 35
6.3
Compressor Output (U, V, W) 35
6.4
Control Input/Output 36
6.4.1
10 V DC Output 36
6.4.2
24 V DC Output 36
6.4.3
Analog Inputs 36
6.4.4
Analog Outputs 36
6.4.5
Digital Inputs 36
6.4.6
Digital Outputs 37
6.4.7
Relay Outputs, Enclosure Sizes H3–H5 37
6.4.8
Relay Outputs, Enclosure Size H6 37
6.4.9
RS485 Serial Communication 38
6.5
Ambient Conditions 38
6.6
Conforming Standards 39
6.7
Cable Lengths and Cross-sections 39
6.8
Acoustic Noise 39
6.9
Shipping Dimensions 40
6.10
Accessories and Spare Parts 40
7
Appendix 41
7.1
Abbreviations 41
AQ32174876762701-000301/130R06276 | Danfoss A/S © 2021.06
VLT® Compressor Drive CDS 803
American English
Operating Guide
7.2 Conventions 42
Contents
AQ32174876762701-000301/130R0627 | 7Danfoss A/S © 2021.06
Edition
Remarks
Software version
AQ321748767627, version 0301
Various editorial updates.
6.0–10 kW (8–15 hp): Version 2.0 18–30 kW (25–40 hp): Version 61.20
Description
Conformity mark
EU/EC Declaration of Conformity (EC/CE - European Conformity/Conformité Européenne)
Low Voltage Directive/Electromagnetic compatibility (EMC)/Restriction of Hazardous Substances (RoHS)
Countries of use: Europe
ACMA Declaration of Conformity (RCM - Regulatory Compliance Mark)
Australian Communications Media Authority (ACMA) Low Voltage Directive/Electromagnetic compatibility (EMC)
Countries of use: Australia and New Zealand
VLT® Compressor Drive CDS 803
American English
Operating Guide
Introduction

1 Introduction

1.1 Purpose of this Operating Guide
This Operating Guide provides information for safe installation and commissioning of the AC drive. It is intended for use by qualified personnel.
Read and follow the instructions to use the drive safely and professionally. Pay particular attention to the safety instructions and general warnings. Always keep this Operating Guide with the drive. VLT® is a registered trademark for Danfoss A/S.
1.2 Additional Resources
1.2.1 Supplementary Documentation
Other resources are available to understand advanced drive functions and programming.
The Programming Guide provides information on how to program and includes complete parameter descriptions.
The Design Guide provides detailed information about capabilities and functionality to design motor control systems.
The Modbus RTU Operating Instructions explains how to physically establish and configure communication between the Danfoss FC Series and a controller using the Modbus RTU protocol. Download the Operating Instructions from www.danfoss.com in the section Service and Support/Documentation.
See
www.danfoss.com for supplementary documentation.
1.2.2 VLT® Motion Control Tool MCT 10 Software Support
Download the software from the Service and Support download page on www.danfoss.com. During the installation process of the software, enter CD-key 34544400 to activate the CDS 803 functionality. An activation key is not
required for using the CDS 803 functionality. The latest software does not always contain the latest updates for the drive. Contact the local sales office for the latest drive updates
(in the form of *.upd files), or download the drive updates from the Service and Support download page on www.danfoss.com.
1.3 Manual and Software Version
This manual is regularly reviewed and updated. All suggestions for improvement are welcome.
Table 1: Manual and Software Version
1.4 Approvals and Certifications
AQ32174876762701-000301 / 130R06278 | Danfoss A/S © 2021.06
Description
Conformity mark
VIT-SEPRO Declaration of Conformity (VIT - All-Union Institute of Transformer Engineering)
Low Voltage Directive/Electromagnetic compatibility (EMC) Country of use: Ukraine
089
Moroccan Declaration of Conformity (CMIM - Moroccan Conformity Mark) Low Voltage Directive/Electromagnetic compatibility (EMC)
Country of use: Morocco
Eurasian Economic Union Declaration of Conformity (EAC - Eurasian Conformity Mark)
Customs Union Technical Regulations (CU TR) Low voltage Directive/Electromagnetic compatibility (EMC)/Restriction of Hazardous Substances Direc-
tive (RoHS)
Countries of use: Eurasian Economic Union (Russia, Belarus, Kazakhstan, Armenia, and Kirghizstan)
Certification of Compliance UL listed (UL - Underwriters Laboratories)
Safety organization
Countries of use: USA and Canada
Certification of Compliance UL recognized (UL - Underwriters Laboratories)
Safety organization Countries of use: USA and Canada
Do not dispose of equipment containing electrical components together with domestic waste. Collect it separately in accordance with local and currently valid legislation.
VLT® Compressor Drive CDS 803
American English
Operating Guide
Introduction
N O T I C E
The VLT® Compressor Drive CDS 803 with SXXX in the type code is certified against UL 508C. Example: CDS803P7K5T4E20H4XXCXXXSXXXXAXBXCXXXXDX The VLT® Compressor Drive CDS 803 with S096 in the type code is certified against UL/EN/IEC 60730-1. Example: CDS803P30KT4E20H2XXXXXXS096XAXBXCXXXXDX
1.5 Disposal
AQ32174876762701-000301 / 130R0627 | 9Danfoss A/S © 2021.06
VLT® Compressor Drive CDS 803
American English
Operating Guide
1.6 CE Declaration
Introduction
AQ32174876762701-000301 / 130R062710 | Danfoss A/S © 2021.06
VLT® Compressor Drive CDS 803
American English
Operating Guide
Introduction
AQ32174876762701-000301 / 130R0627 | 11Danfoss A/S © 2021.06
VLT® Compressor Drive CDS 803
American English
Operating Guide

2 Safety

2.1 Safety Symbols
The following symbols are used in this manual:
D A N G E R
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
W A R N I N G
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
C A U T I O N
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
N O T I C E
Indicates information considered important, but not hazard-related (for example, messages relating to property damage).
Safety
2.2 Qualified Personnel
To allow trouble-free and safe operation of the unit, only qualified personnel with proven skills are allowed to transport, store, as­semble, install, program, commission, maintain, and decommission this equipment.
Persons with proven skills:
Are qualified electrical engineers, or persons who have received training from qualified electrical engineers and are suitably experienced to operate devices, systems, plant, and machinery in accordance with pertinent laws and regulations.
Are familiar with the basic regulations concerning health and safety/accident prevention.
Have read and understood the safety guidelines given in all manuals provided with the unit, especially the instructions given in the Operating Guide.
Have good knowledge of the generic and specialist standards applicable to the specific application.
2.3 Safety Precautions
W A R N I N G
HAZARDOUS VOLTAGE
AC drives contain hazardous voltage when connected to the AC mains or connected on the DC terminals. Failure to perform installation, start-up, and maintenance by skilled personnel can result in death or serious injury.
Only skilled personnel must perform installation, start-up, and maintenance.
-
W A R N I N G
UNINTENDED START
When the drive is connected to AC mains, DC supply, or load sharing, the motor may start at any time. Unintended start during programming, service, or repair work can result in death, serious injury, or property damage. Start the motor with an external switch, a fieldbus command, an input reference signal from the local control panel (LCP), via remote operation using MCT 10 software, or after a cleared fault condition.
Disconnect the drive from the mains.
-
Press [Off/Reset] on the LCP before programming parameters.
-
Ensure that the drive is fully wired and assembled when it is connected to AC mains, DC supply, or load sharing.
-
AQ32174876762701-000301 / 130R062712 | Danfoss A/S © 2021.06
Voltage [V]
Power range [kW (hp)]
Minimum waiting time (minutes)
3x200
6.0–10 (8.0–15)
15
3x400
6.0–7.5 (8.0–10)
4
3x400
10–30 (15–40)
15
VLT® Compressor Drive CDS 803
American English
Operating Guide
Safety
W A R N I N G
DISCHARGE TIME
The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be present even when the warning indicator lights are off. Failure to wait the specified time after power has been removed before performing service or repair work could result in death or serious injury.
Stop the motor.
-
Disconnect AC mains, permanent magnet type motors, and remote DC-link supplies, including battery back-ups, UPS, and
-
DC-link connections to other drives.
Wait for the capacitors to discharge fully. The minimum waiting time is specified in the table Discharge time and is also visible
-
on the nameplate on the top of the drive.
Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors
-
are fully discharged.
Table 2: Discharge Time
W A R N I N G
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the drive properly can result in death or serious injury.
Ensure that the minimum size of the ground conductor complies with the local safety regulations for high touch current
-
equipment.
W A R N I N G
EQUIPMENT HAZARD
Contact with rotating shafts and electrical equipment can result in death or serious injury.
Ensure that only trained and qualified personnel perform installation, start-up, and maintenance.
-
Ensure that electrical work conforms to national and local electrical codes.
-
Follow the procedures in this manual.
-
C A U T I O N
INTERNAL FAILURE HAZARD
An internal failure in the drive can result in serious injury when the drive is not properly closed.
Ensure that all safety covers are in place and securely fastened before applying power.
-
AQ32174876762701-000301 / 130R0627 | 13Danfoss A/S © 2021.06
Power [kW (hp)]
Clearance above/below [mm (in)]
Size
IP protection rating
3x200–240 V
3x380–480 V
H3
IP20–6.0–7.5 (8.0–10)
100 (4)
H4
IP20
6.0–7.5 (8.0–10)
10 (15)
100 (4)
H5
IP20
10 (15)
18.5–22 (25–30)
100 (4)
H6
IP20–30(40)
200 (7.9)
Power [kW (hp)]
Torque [Nm (in-lb)]
Enclo­sure size
IP protec­tion rat­ing
3x200–240 V
3x380–480 V
Mains
Motor
DC connec­tion
Control ter­minals
Ground
Relay
H3
IP20–6.0–7.5 (8.0–10)
0.8 (7)
0.8 (7)
0.8 (7)
0.5 (4)
0.8 (7)
0.5 (4)
VLT® Compressor Drive CDS 803
American English
Operating Guide

3 Installation

3.1 Mechanical Installation
3.1.1 Side-by-side Installation
The drive can be mounted side by side but requires the clearance specified in Table 3 above and below for cooling.
Table 3: Clearance Required for Cooling
N O T I C E
With IP21/NEMA Type1 option kit mounted, a distance of 50 mm (2 in) between the units is required.
Installation
3.1.2 Operating Environment
3.1.2.1 Derating for Ambient Temperature and Switching Frequency
Ensure that the ambient temperature measured over 24 hours is at least 5 °C (9 °F) lower than the maximum ambient temperature that is specified for the drive. If the drive is operated at a high ambient temperature, decrease the constant output current. For derating specifications, see the VLT® Compressor Drive CDS 803 Design Guide listed in
1.1.2 Additional Resources.
3.1.2.2 Derating for Low Air Pressure and High Altitudes
The cooling capability of air is decreased at low air pressure. For altitudes above 2000 m (6562 ft), contact Danfoss regarding PELV. Below 1000 m (3281 ft) altitude, derating is not necessary. For altitudes above 1000 m (3281 ft), decrease the ambient temperature or the maximum output current. Decrease the output by 1% per 100 m (328 ft) altitude above 1000 m (3281 ft) or reduce the maxi­mum ambient cooling air temperature by 1 °C (1.8 °F) per 200 m (656 ft).
3.2 Electrical Installation
3.2.1 Electrical Installation in General
All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper conductors are required. 75 °C (167 °F) is recommended.
3.2.1.1 Fastener Torque Ratings
Table 4: Tightening Torques for Enclosure Sizes H3–H6, 3x200–240 V & 3x380–480 V
AQ32174876762701-000301 / 130R062714 | Danfoss A/S © 2021.06
Power [kW (hp)]
Torque [Nm (in-lb)]
H4
IP20
6.0–7.5 (8.0–
10)
10–15 (15–20)
1.2 (11)
1.2 (11)
1.2 (11)
0.5 (4)
0.8 (7)
0.5 (4) H5
IP20
10 (15)
18.5–22 (25–30)
1.2 (11)
1.2 (11)
1.2 (11)
0.5 (4)
0.8 (7)
0.5 (4)
H6
IP20–30 (40)
4.5 (40)
4.5 (40)
0.5 (4)
3 (27)
0.5 (4)
Circuit breakers
(1)
Fuse
UL
Non-ULULNon-UL
Bussmann
Bussmann
Bussmann
Bussmann
Maximum fuse
Power [kW (hp)]
Type RK5
Type RK1
Type J
Type T
Type gG
3x200–240 V
6.0 (8.0)
FRS-R-50
KTN-R50
JKS-50
JJN-50
gG-50
7.5 (10)
FRS-R-50
KTN-R50
JKS-50
JJN-50
gG-50
10 (15)
FRS-R-80
KTN-R80
JKS-80
JJN-80
gG-63
3x380–480 V
6.0 (8.0)
FRS-R-25
KTS-R25
JKS-25
JJS-25
gG-25
7.5 (10)
FRS-R-25
KTS-R25
JKS-25
JJS-25
gG-25
10 (15)
FRS-R-50
KTS-R50
JKS-50
JJS-50
gG-50
18.5 (25)
–––
JJS-80
gG-63
22 (30)
JJS-80
gG-63
30 (40)
JJS-125
gG-80
VLT® Compressor Drive CDS 803
American English
Operating Guide
Installation
3.2.2 Fuses and Circuit Breakers
Fuses and circuit breakers ensure that possible damage to the drive is limited to damage inside the unit. Danfoss recommends fuses on the supply side as protection. For further information, see the application note Fuses and Circuit Breakers found on www.dan-
foss.com under Service and support/Documentation/Manuals & guides.
N O T I C E
Use of fuses on the supply side is mandatory for IEC 60364 (CE) and NEC 2009 (UL) compliant installations.
3.2.2.1 Recommendation of Fuses and Circuit Breakers
Table 5: Fuses and Circuit Breakers
1
Circuit breakers have not been evaluated by Danfoss as part of the certification process.
3.2.3 Electrical Wiring
3.2.3.1 Wiring Schematic
AQ32174876762701-000301 / 130R0627 | 15Danfoss A/S © 2021.06
L1 L2 L3
3-phase power input
PE
PE
+10 V DC
0-10 V DC-
0-10 V DC-
50 (+10 V OUT)
54 (A IN)
53 (A IN)
55 (COM A IN/OUT)
0/4-20 mA
0/4-20 mA
42 0/4-20 mA A OUT / D OUT
45 0/4-20 mA A OUT / D OUT
18 (D IN)
19 (D IN)
27 (D IN)
29 (
D IN)
12 (+24 V OUT)
24 V (NPN)
20 (COM D IN)
O V (PNP)
24 V (NPN) O V (PNP)
24 V (NPN) O V (PNP)
24 V (NPN) O V (PNP)
Bus ter.
Bus ter.
RS485 Interface
RS485
(N RS485) 69
(P RS485) 68
(Com RS485 ) 61
(PNP)-Source (NPN)-Sink
ON=Terminated
OFF=Unterminated
ON
1 2
240 V AC 3 A
Not present on all power sizes
Do not connect shield to 61
01
02
03
relay 1
relay 2
UDC+
UDC-
Motor
U V
W
e30bj246.10
06
05
04
240 V AC 3 A
VLT® Compressor Drive CDS 803
American English
Operating Guide
Installation
Illustration 1: Basic Wiring Schematic Drawing
There is no access to UDC- and UDC+ on the following units:
IP20, 380–480 V, 30 kW (40 hp).
-
N O T I C E
AQ32174876762701-000301 / 130R062716 | Danfoss A/S © 2021.06
1
2
2
3
4
U
V
W
-DC +DC
e30bb634.11
5
MAINS
MOTOR
1
Mains
2
Ground
3
Compressor
4
Relays
5
Control terminals
VLT® Compressor Drive CDS 803
American English
Operating Guide
3.2.3.2 Terminal Overview of Enclosure Sizes H3–H5
Installation
Illustration 2: Enclosure Sizes H3–H5
AQ32174876762701-000301 / 130R0627 | 17Danfoss A/S © 2021.06
1
95
99
L1 91 / L2 92 / L3 93
U 96 /
V 97 /
W 98
03 02 01
06 05 04
2
3
4
e30bb762.12
1
Mains
2
Ground
3
Compressor
4
Relays
e30bi968.10
VLT® Compressor Drive CDS 803
American English
Operating Guide
3.2.3.3 Terminal Overview of Enclosure Size H6
Installation
Illustration 3: Enclosure Size H6
3.2.3.4 Connecting to Mains and Compressor Terminals
Tighten all terminals in accordance with the information provided in 1.3.2.1.1 Fastener Torque Ratings.
Keep the compressor cable as short as possible to reduce the noise level and leakage currents.
Use a shielded/armored compressor cable to comply with the EMC emission specifications and connect this cable to both the decoupling plate and the compressor. Also see 1.3.2.5 EMC-compliant Electrical Installation.
1.
Connect the ground cable to the ground terminal, then connect the mains supply to terminals L1, L2, and L3.
AQ32174876762701-000301 / 130R062718 | Danfoss A/S © 2021.06
e30bi967.10
Drive terminals
Compressor
UT1VT2W
T3
VLT® Compressor Drive CDS 803
American English
Operating Guide
2.
Connect the ground cable to the ground terminal, then connect the compressor to terminals U, V, and W.
Table 6: Connection of Compressor to Terminals
Installation
3.2.3.5 Relay Terminals
Relay 1
Terminal 01: Common.
Terminal 02: Normally open.
Terminal 03: Normally closed.
Relay 2
Terminal 04: Common.
Terminal 05: Normally open.
Terminal 06: Normally closed.
AQ32174876762701-000301 / 130R0627 | 19Danfoss A/S © 2021.06
Relay1
Relay2
03
02
01
06
05
04
e30bi798.10
e30bd331.11
VLT® Compressor Drive CDS 803
American English
Operating Guide
Installation
Illustration 4: Relay Outputs 1 and 2
3.2.3.6 Control Terminals
Remove the terminal cover to access the control terminals. Use a flat-edged screwdriver to push down the lock lever of the terminal cover under the LCP, then remove the terminal cover as
shown in the following illustration.
Illustration 5: Removing the Terminal Cover
The following illustration shows all the drive control terminals. Applying start (terminal 18), connection between terminals 12-27, and an analog reference (terminal 53 or 54, and 55) make the drive run.
The digital input mode of terminal 18, 19, 27, and 29 is set in parameter 5-00 Digital Input Mode (PNP is default value).
AQ32174876762701-000301 / 130R062720 | Danfoss A/S © 2021.06
e30bf892.10
12 20 55
181927 29 42 54
45 50 53
DIGI IN
61 68 69
N
P
COMM. GND
+24 V
GND
GND
10 V OUT
10 V/20 mA IN
0/4-20 mA A OUT/DIG OUT
BUS TER.
OFF ON
DIGI IN
DIGI IN
DIGI IN
0/4-20 mA A OUT/DIG OUT
10 V/20 mA IN
VLT® Compressor Drive CDS 803
American English
Operating Guide
Illustration 6: Control Terminals
Installation
3.2.4 Setting Up RS485 Serial Communication
3.2.4.1 RS485 Features
RS485 is a 2-wire bus interface compatible with multi-drop network topology. This interface contains the following features:
Ability to select from the following communication protocols:
-
FC (default protocol)
-
Modbus RTU
Functions can be programmed remotely using the RS485 connection or in parameter group 8-** Communications and Options.
A switch (BUS TER) is provided on the control card for bus termination resistance.
N O T I C E
Altering between the supported communication protocols can be accessed and changed via the LCP as parameter 8-30 Protocol is not available in VLT® Motion Control Tool MCT 10.
3.2.4.2 Configuring RS485 Serial Communication
Procedure
1.
Connect RS485 serial communication wiring to terminals (P RS485) 68 and (N RS485) 69.
-
Use shielded serial communication cable.
-
Properly ground the wiring. Refer to 1.3.2.5 EMC-compliant Electrical Installation.
AQ32174876762701-000301 / 130R0627 | 21Danfoss A/S © 2021.06
+
e30bi768.10
RS485
69
GND
68
VLT® Compressor Drive CDS 803
American English
Operating Guide
2.
Configure all required settings such as address, baud rate, and so on in parameter group 8-** Communications and Options. For more details on parameters, refer to VLT® Compressor Drive CDS 803 Programming Guide listed in 1.1.2 Additional Re-
sources.
Example
Illustration 7: RS485 Wiring Connection
Installation
3.2.5 EMC-compliant Electrical Installation
To obtain an EMC-compliant installation, be sure to follow all electrical installation instructions. Also, remember to practice the fol­lowing:
When using relays, control cables, a signal interface, fieldbus, or brake, connect the shield to the enclosure at both ends. If the ground path has high impedance, is noisy, or is carrying current, break the shield connection on 1 end to avoid ground current loops.
Convey the currents back to the unit using a metal mounting plate. Ensure good electrical contact from the mounting plate by securely fastening the mounting screws to the drive chassis.
Use shielded cables for motor output cables. An alternative is unshielded motor cables within metal conduit.
Ensure that motor and brake cables are as short as possible to reduce the interference level from the entire system.
Avoid placing cables with a sensitive signal level alongside motor and brake cables.
For communication and command/control lines, follow the particular communication protocol standards. For example, USB must use shielded cables, but RS485/ethernet can use shielded UTP or unshielded UTP cables.
Ensure that all control terminal connections are rated protective extra low voltage (PELV).
N O T I C E
TWISTED SHIELD ENDS (PIGTAILS)
Twisted shield ends increase shield impedance at higher frequencies, which increases the leakage current.
Use integrated shield clamps instead of twisted shield ends.
-
N O T I C E
SHIELDED CABLES
If shielded cables or metal conduits are not used, the unit and the installation do not meet regulatory limits on radio frequency (RF) emission levels.
N O T I C E
EMC INTERFERENCE
Failure to isolate power, motor, and control cables can result in unintended behavior or reduced performance.
Use shielded cables for motor and control wiring.
-
Provide a minimum 200 mm (7.9 in) separation between mains input, motor cables, and control cables.
-
AQ32174876762701-000301 / 130R062722 | Danfoss A/S © 2021.06
VLT® Compressor Drive CDS 803
American English
Operating Guide
Installation
N O T I C E
EMI/EMC NON-COMPLIANCE
Panel components not installed by Danfoss will invalidate the EMI/EMC compliance and other certifications.
N O T I C E
INSTALLATION AT HIGH ALTITUDE
There is a risk for overvoltage. Isolation between components and critical parts could be insufficient and may not comply with PELV requirements.
Use external protective devices or galvanic isolation. For installations above 2000 m (6500 ft) altitude, contact Danfoss re-
-
garding protective extra low voltage (PELV) compliance.
N O T I C E
PROTECTIVE EXTRA LOW VOLTAGE (PELV) COMPLIANCE
Prevent electric shock by using PELV electrical supply and complying with local and national PELV regulations.
AQ32174876762701-000301 / 130R0627 | 23Danfoss A/S © 2021.06
L1
L2L3PEL1L2L3PEPEu
v
w
2
1
3
5
IEC 60309
16
17
18
14
12
8
7
10
9
4
11
13
446
15
90
+DC
BR- B
M
AINS
L1 L2 L3
91 92 93
RELA
Y 1 RELA
Y 2
99
- L
C -
UV
W
MO T
OR
VLT® Compressor Drive CDS 803
American English
Operating Guide
Installation
Illustration 8: Example of Proper EMC Installation
AQ32174876762701-000301 / 130R062724 | Danfoss A/S © 2021.06
1
Programmable logic controller (PLC)
2
Minimum 16 mm2 (6 AWG) equalizing cable
3
Control cables
4
Minimum 200 mm (7.9 in) between control cables, motor cables, and mains cables
5
Mains supply
6
Bare (unpainted) surface
7
Star washers
8
Brake cable (shielded)
9
Motor cable (shielded)
10
Mains cable (unshielded)
11
Output contactor
12
Cable insulation stripped
13
Common ground busbar. Follow local and national requirements for cabinet grounding.
14
Brake resistor
15
Metal box
16
Connection to motor
17
Motor
18
EMC cable gland
VLT® Compressor Drive CDS 803
American English
Operating Guide
Installation
AQ32174876762701-000301 / 130R0627 | 25Danfoss A/S © 2021.06
e30bb765.11
B
a
c
k
Com.
1-20 Motor Power [5] 0.37kW - 0.5HP Setup 1
A
B
1
12
13
14
15
11
11
10
9
8
7
6
5
4
3
2
C
D
Status
Main Menu
Quick Menu
Hand
On
OK
M
enu
Off
Reset
Auto
On
Alarm
Warn.
On
11
1
Parameter number and name.
2
Parameter value.
VLT® Compressor Drive CDS 803
American English
Operating Guide
Commissioning

4 Commissioning

4.1 Programming Interfaces
The drive can be programmed in 3 different ways:
Locally via the LCP.
Externally via the RS485 interface by either
-
using Modbus RTU
-
or by installing VLT® Motion Control Tool MCT 10.
For the full menu and parameter specifications, refer to the VLT® Compressor Drive CDS 803 Programming Guide listed in 1.1.2 Ad-
ditional Resources.
4.2 Local Control Panel (LCP)
The LCP is divided into 4 functional sections.
A. Display
B. Menu key
C. Navigation keys and indicator lights
D. Operation keys and indicator lights
Illustration 9: Local Control Panel (LCP)
A. Display
The LCD display is illuminated with 2 alphanumeric lines. Table 7 describes the information that can be read from the display.
Table 7: Legend to Section A
AQ32174876762701-000301 / 130R062726 | Danfoss A/S © 2021.06
3
Setup number shows the active setup and the edit setup. If the same setup acts as both active and edit setup, only that setup number is shown (factory setting). When active and edit setup differ, both numbers are shown in the display (setup 12). The number flashing indicates the edit setup.
4
Motor direction is shown to the bottom left of the display – indicated by a small arrow pointing either clockwise or counter­clockwise.
5
The triangle indicates if the LCP is in Status, Quick Menu, or Main Menu.
6
Com. (yellow indicator): Flashes during bus communication.
7
On (green indicator): Control section is working correctly.
8
Warn. (yellow indicator): Indicates a warning.
9
Alarm (red indicator): Indicates an alarm.
10
[Back]: For moving to the previous step or layer in the navigation structure.
11
[] [] []: For navigating among parameter groups and parameters, and within parameters. They can also be used for set­ting local reference.
12
[OK]: For selecting a parameter and for accepting changes to parameter settings.
13
[Hand On]: Starts the motor and enables control of the drive via the LCP.
N O T I C E
[2] Coast inverse is the default option for parameter 5-12 Terminal 27 Digital Input. If there is no 24 V supply to terminal 27, [Hand On] does not start the compressor. Connect terminal 12 to terminal 27.
14
[Off/Reset]: Stops the compressor (Off). If in alarm mode, the alarm is reset.
15
[Auto On]: The drive is controlled either via control terminals or serial communication.
VLT® Compressor Drive CDS 803
American English
Operating Guide
B. Menu key
Press [Menu] to select among Status, Quick Menu, or Main Menu.
C. Navigation keys and indicator lights
Table 8: Legend to Section C
Commissioning
D. Operation keys and indicator lights
Table 9: Legend to Section D
4.2.1 Programming via the Quick Menu
Procedure
1.
To enter the Quick Menu, press [Menu] until indicator in display is placed above Quick Menu.
2.
Press [] [] to select quick guide, closed-loop setup, compressor setup, or changes made, then press [OK].
3.
Press [] [] to browse through the parameters in the Quick Menu. Press [OK] to select a parameter.
4.
Press [] [] to change the value of a parameter setting.
5.
Press [OK] to accept the change.
6.
7.
Press either [Back] twice to enter Status, or press [Menu] once to enter Main Menu.
4.2.2 Programming via the Main Menu
Procedure
1.
Press [Menu] until indicator in display is placed above Main Menu. Press [] [] to browse through the parameter groups.
2.
AQ32174876762701-000301 / 130R0627 | 27Danfoss A/S © 2021.06
VLT® Compressor Drive CDS 803
American English
Operating Guide
3.
Press [OK] to select a parameter group.
4.
Press [] [] to browse through the parameters in the specific group.
5.
Press [OK] to select the parameter.
6.
Press [] [] to set/change the parameter value.
7.
Press [OK] to accept the change or press [Back] to go back to the previous level.
Commissioning
4.2.3 Data Transfer from Drive to LCP
Once the setup of a drive is complete, Danfoss recommends storing the data in the LCP or on a PC via VLT® Motion Control Tool MCT 10.
W A R N I N G
Stop the compressor before performing this operation.
Procedure
1.
Go to parameter 0-50 LCP Copy.
2.
Press [OK].
3.
Select [1] All to LCP. Press [OK].
4.
4.2.4 Data Transfer from LCP to Drive
Connect the LCP to another drive to copy the parameter settings to this drive as well.
W A R N I N G
Stop the compressor before performing this operation.
Procedure
1.
Go to parameter 0-50 LCP Copy.
2.
Press [OK].
3.
Select [2] All from LCP.
4.
Press [OK].
4.2.5 Restoring Factory Default Settings
There are 2 different ways of initializing the drive to factory default settings:
Via parameter 14-22 Operation Mode (this is the recommended way).
Two-finger initialization
Some parameters will not be reset, see more details in and 1.4.2.5.2 Two-finger Initialization.
4.2.5.1 Recommended Initialization (via Parameter 14-22 Operation Mode)
Initialization of the drive to default settings (via parameter 14-22 Operation Mode).
Procedure
1.
Select parameter 14-22 Operation Mode.
2.
Press [OK].
3.
Select [2] Initialisation and press [OK]. Cut off the mains supply and wait until the display turns off.
4.
Reconnect the mains supply.
5.
1.4.2.5.1 Recommended Initialization (via Parameter 14-22 Operation Mode)
The drive is now reset, except the following parameters:
Parameter 1-06 Clockwise Direction
Parameter 1-13 Compressor Selection
Parameter 4-18 Current Limit
Parameter 8-30 Protocol
AQ32174876762701-000301 / 130R062728 | Danfoss A/S © 2021.06
VLT® Compressor Drive CDS 803
American English
Operating Guide
Parameter 8-31 Address
Parameter 8-32 Baud Rate
Parameter 8-33 Parity / Stop Bits
Parameter 8-35 Minimum Response Delay
Parameter 8-36 Maximum Response Delay
Parameter 8-37 Maximum Inter-char delay
Parameter 15-00 Operating hours to parameter 15-05 Over Volt's
Parameter 15-03 Power Up's
Parameter 15-04 Over Temp's
Parameter 15-05 Over Volt's
Parameter 15-30 Alarm Log: Error Code
Parameter group 15-4* Drive identification parameters
4.2.5.2 Two-finger Initialization
Procedure
1.
Power off the drive.
2.
Press [OK] and [Menu].
3.
Power up the drive while still pressing the keys above for 10 s.
Commissioning
The drive is now reset, except the following parameters:
Parameter 1-06 Clockwise Direction
Parameter 15-00 Operating hours
Parameter 15-03 Power Up's
Parameter 15-04 Over Temp's
Parameter 15-05 Over Volt's
Parameter 15-30 Alarm Log: Error Code
Parameter group 15-4* Drive identification parameters
Initialization of parameters is confirmed by AL80 in the display after the power cycle.
4.3 Starting Up the Drive for the First Time
The procedure in this section requires user-wiring and application programming to be completed. The following procedure is rec­ommended after application setup is completed.
1.
Press [Auto On].
If warnings or alarms occur, see the Warnings and Alarms section.
Apply an external run command. Examples of external run commands are a switch, button, or programmable logic control-
2.
ler (PLC). Adjust the speed reference throughout the speed range.
3.
Ensure that the system is working as intended by checking the sound and vibration levels of the compressor.
4.
Remove the external run command.
5.
AQ32174876762701-000301 / 130R0627 | 29Danfoss A/S © 2021.06
Status
Color
Warning
Constant yellow light
Alarm
Flashing red light
VLT® Compressor Drive CDS 803
American English
Operating Guide
Troubleshooting

5 Troubleshooting

5.1 Acoustic Noise or Vibration
If the compressor application makes noise or vibrations at certain frequencies, adjust the following parameters to avoid resonance problems within the system.
Upper and lower frequency limits, Parameter group 4-6* Speed Bypass.
Switching pattern and switching frequency, parameter group 14-0* Inverter Switching.
5.2 Warnings and Alarms
A warning or an alarm is signaled by the relevant indicator on the front of the drive and indicated by a code on the display. A warning remains active until its cause is no longer present. Under certain circumstances, operation of the compressor may still be
continued. Warning messages may be critical. In the event of an alarm, the drive has tripped. To restart operation, reset alarms once their cause has been rectified.
This may be done in 4 ways:
By pressing [Reset].
Via a digital input with the Reset function.
Via serial communication.
By resetting automatically using the [Auto Reset] function, see parameter 14-20 Reset Mode.
A trip is the action following an alarm. The trip coasts the compressor and is reset by pressing [Reset] or by a digital input (parameter group 5-1* Digital Inputs). The original event that caused an alarm cannot damage the drive or cause dangerous conditions. A trip lock is an action when an alarm occurs, which could damage the drive or connected parts. A trip lock situation can only be reset by cycling power.
Refer to the VLT® Compressor Drive CDS 803 Programming Guide listed in gramming.
1.1.2 Additional Resources for parameter details and pro-
Table 10: Indicator Lights
The alarm words, warning words and extended status words can be read out via serial bus or optional fieldbus for diagnosis. See also parameter 16-90 Alarm Word, parameter 16-92 Warning Word, and parameter 16-94 Ext. Status Word.
N O T I C E
MOTOR RESTART
After a manual reset pressing [Reset], press [Auto On] or [Hand On] to restart the motor.
If an alarm cannot be reset, the reason may be that its cause has not been rectified, or the alarm is trip-locked, see Table 11.
C A U T I O N
ALARM RESET
Alarms that are trip-locked offer extra protection, meaning that the mains supply must be switched off before the alarm can be reset. After being switched back on, the drive is no longer blocked and may be reset as described above once the cause has been rectified. Alarms that are not trip-locked can also be reset using the automatic reset function in parameter 14-20 Reset Mode (Warning: auto­matic wake-up is possible!) alarm for a given fault.
Table 11 specifies whether a warning occurs before an alarm, or whether to show a warning or an
AQ32174876762701-000301 / 130R062730 | Danfoss A/S © 2021.06
Loading...
+ 330 hidden pages