Danfoss CDS 801 Operating guide

MAKING MODERN LIVING POSSIBLE
OOperating Instructions
VLTp Inverter Scroll CDS 801
Contents
Contents
VLT® Inverter Scroll CDS 801 Operating Instructions
1 General
1.1 Coverage
1.1.1 Disclaimer 4
1.1.2 Coverage 4
1.2 Safety Instructions
1.3 Approvals
1.4 General Warning
1.5 Disposal Instruction
1.6 Before Commencing Repair Work
1.7 ESD Precautions
1.8 Product Identification
1.9 Unpacking the Drive
1.10 Table of Abbreviations
2 Mechanical Installation
2.1 Dimensions and Weight
2.2 Installation Orientation and Clearances
2.2.1 Surface Mounting 9
4 4
4 4 5 5 5 5 5 5 6
7 7 9
2.2.2 Structural Mounting 11
2.3 Air Circulation/Cooling
2.4 Condensation and Dripping Water
2.5 Vibration and Mechanical Resonances
3 Electrical Installation
3.1 Electrical Connection in General
3.2 Tightening Torque
3.3 Cable Quality and Dimensioning
3.4 Fuses/Circuit Breakers
3.5 EMC Correct Installation
3.6 Electrical Connections
3.6.1 Routing of Motor and Supply Cable 15
3.6.2 Power Supply Connection (Mains) 16
3.6.3 Motor (Compressor) Connection 16
3.6.4 Sensor Connections 18
3.6.5 4-way Reversing Valve Connection 18
3.6.6 Condenser Fan Motor Control Connection (EXT_FAN) 18
12 12 12
13 13 13 13 13 14 15
3.6.7 EEV Controller (HP Mode) Connection (EEV_2) 18
3.6.8 Serial Communication Cable Connection 19
3.6.9 Connector Specification 20
3.6.10 Allocation of Connector Pins 21
MG10V402 - VLT® is a registered Danfoss trademark 1
Contents
VLT® Inverter Scroll CDS 801 Operating Instructions
3.6.11 Overview Wiring Diagram 22
4 Serial Communication (Modbus RTU)
5 Commissioning
5.1 Initial Configuration of the Performer VSD sub-system
5.2 Drive Setup
5.2.1 Drive Parameters (Modbus Registers, node 162) 27
5.2.2 Drive Parameters (Modbus Registers, node 163) 28
5.3 Condenser Fan Speed Reference Output
5.4 Crankcase Heating
5.5 Ambient Temperature Source
5.6 Pressure sensor scaling
5.7 Normal Operation
6 Embedded Application Controller “Thermo Control”
6.1 Introduction
6.2 Applications
6.2.1 Generic AC 31
25
27 27 27
29 29 29 30 30
31 31 31
6.2.2 Generic AC/HP (Reversible) 32
6.2.3 Ground Source Heat Pump (Reversible) 33
6.3 Application Controller
6.3.1 Introduction 33
6.3.2 System Modes 33
6.3.2.1 Off 33
6.3.2.2 AC 33
6.3.2.3 HP 34
6.3.2.4 Defrost 34
6.3.3 Compressor Capacity Control 34
6.3.3.1 Single Loop Room Temperature Control 35
6.3.3.2 Open Loop/ External Speed Control 35
6.3.4 Condensing Pressure Control 36
6.3.4.1 AC Mode 36
6.3.4.2 HP Mode 38
6.3.4.3 Defrost Mode 39
6.3.5 Auxiliary Functions 39
33
6.3.5.1 Start-Up Sequence 39
6.3.5.2 Restart Timer 40
6.3.5.3 Compressor Safety Envelope 40
6.3.5.4 Oil Return 40
2 MG10V402 - VLT® is a registered Danfoss trademark
Contents
VLT® Inverter Scroll CDS 801 Operating Instructions
6.3.5.5 Derating 40
6.3.5.6 Discharge temperature cut out 41
6.3.5.7 Max Suction Pressure (MOP) 41
6.3.5.8 Frequency Cancelation 41
6.3.5.9 System Status 41
6.4 Thermo Controller Register Overview (Node 162)
7 Fault Conditions, Messages and Causes
8 Troubleshooting
9 Specifications
10 Special Operating Conditions
11 Maintenance
11.1 Replacement of Internal Cooling Fan
11.2 Cleaning
12 Service and Spare Parts
Index
42
44
47
48
50
51 51 51
52
53
MG10V402 - VLT® is a registered Danfoss trademark 3
General
VLT® Inverter Scroll CDS 801 Operating Instructions
11
1 General
1.1 Coverage
The earth leakage current exceeds 3.5 mA
A stop command does not disconnect power
from the drive
1.1.1 Disclaimer
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Coverage
1.1.2
This instruction covers 3 different drive sizes with single phase 208-240 V power supply matching compressor sizes for
- 13 kW/3 t cooling capacity
- 16 kW/4 t cooling capacity
- 20 kW/5 t cooling capacity
from software version 1.09.
1.2
Safety Instructions
1.3 Approvals
The drive has been designed/approved in accordance with the following standards:
Safety UL/EN 60335-1, 60335-2-34 (UL 984) Household UL/EN 60730 Industrial EN 61800-3 (frequency converter standard) Software UL 1998 cl. B Polymerics UL 746 C EMC With ferrite: EN 55011 cl. A, EN 55014 Harmonics EN 61000-3-12, IEEE 519-1992 Surge EN 61642-12 Immunity EN 61000-6 Transient EN 61000-4 Corrosion UL 50E, ISO 9223, EN 61000-5-1, ASTM B117 Environment IEC 60721-3-3 cl. 3K4 Enclosure NEMA 250-2003
Table 1.1 Standards Complied to
The equipment complies with the flicker requirement according to IEC/EN61000-3-11 at 230 V nominal voltage under the condition that the service current capacity is permissible system impedance Z
100 A per phase or a maximum
= 0.1892
MAX
Ω
1.2.1 High Voltage Warning
WARNING
The voltage of the variable speed drive is dangerous whenever it is connected to mains. Incorrect installation of the variable speed drive may cause damage to the equipment, serious injury or death. Consequently, it is essential to comply with the instructions in this manual as well as local and national rules and safety regulations.
1.2.2 Safety Instructions
Make sure the drive is properly connected to
earth Do not remove the mains connector or motor
(compressor) connector while the drive is connected to power
Protect personnel against supply voltage
Protect the variable speed drive against over-
current according to national and local regulations
4 MG10V402 - VLT® is a registered Danfoss trademark
130ZB121.10
IP00/CHASSIS -25
C/ -13 F to 52 C/125 F
PERFORMER
MADE IN DENMARK
R
CDS801 Variable Speed Drive
P/N: 176L7002 S/N: 010199D082
20 kW/5 TR cooling capacity
IN: 1x208-230V 50-60Hz 33A 6,7 kW
OUT: 3x270V 45-210Hz 33A
VSD
o o o o
CAUTION:
See manual before use.
Lire le manual avant utilisation
WARNING:
Stored charge, wait 5 min. before service.
Energia aimacenada, asperar 5 min. para descaega antes de lisar.
E337256
* 1 7 6 L 7 0 0 2 0 1 0 1 9 9 D 0 6 2 *
Charge stockée, attendre 5 min. avant l’emploi.
Leer manual antec deusar.
General
VLT® Inverter Scroll CDS 801 Operating Instructions
1.4 General Warning
WARNING
Touching the electrical parts may be fatal - even after the equipment has been disconnected from mains. Also make sure that other voltage inputs have been disconnected. Be aware that there may be high voltage on the DC link even when the LED is turned off. Before touching any potentially live parts of the drive, wait at least 1 minute.
CAUTION
Leakage Current The earth leakage current from the variable speed drive exceeds 3.5 mA. Grounding and bounding shall comply with UL 1995/NEC. Residual Current Device This product can cause a D.C. current in the protective earth, only an RCD of Type B (time delayed) shall be used in the supply side of this product. See also Application Note on RCD, MN90G. Protective earthing of the drive and the use of RCDs must always follow national and local regulations.
WARNING
Installation in high altitudes: At altitudes above 6000 ft (2000 m), contact Danfoss regarding SELV.
1 1
1.6 Before Commencing Repair Work
1. Disconnect the variable speed drive from mains (flip the circuit breaker or pull fuses).
2. Wait for at least 5 minutes for discharge of the DC-link capacitors.
3. Remove motor (compressor) cable.
1.7 ESD Precautions
A variable speed drive is a sensible electronic device. Electrostatic discharge (ESD) can cause a malfunction or destroy the frequency converter. Do not touch components on the printed circuit board (PCB). When handling the drive make sure that necessary ESD precautions are taken, i.e. wearing wrist straps, using anti­static mats etc.
1.8 Product Identification
A product identification label is placed on the drive chassis. It carries the ordering code i.e. 76L7002. The last 3 digits of the numeric string indicate the production date, i.e. 062 means week 6 in 2012. Do not remove the identifi­cation label from the drive (loss of warranty).
Avoid unintended start While the variable speed drive is connected to mains, the motor (compressor) can be started/stopped using serial communication commands.
- Disconnect the frequency converter from mains whenever personal safety considerations make it necessary to avoid unintended start.
1.5
Disposal Instruction
Equipment containing electrical components may not be disposed together with domestic waste. It must be separately collected with electrical and electronic waste according to local and valid legislation.
Illustration 1.1 Product Identification Label
1.9 Unpacking the Drive
NOTE
To avoid damage to the drive caused by electrostatic discharge, people handling the drive should wear wrist traps for proper grounding at all time!
MG10V402 - VLT® is a registered Danfoss trademark 5
General
VLT® Inverter Scroll CDS 801 Operating Instructions
11
1.10 Table of Abbreviations
VSD Variable speed drive VFD Variable frequency drive, also used instead of VSD EMC Electromagnetic compatibility RCD Residual current device SELV Safety extra low voltage ESD Electrostatic discharge PCB Printed circuit board AWG American wire gauge EEV Electronic expansion valve RTU Remote terminal unit OEM Original equipment manufacturer AC Air-conditioning HP Heat pump RLA Rated load amperage AOC Application oriented controller MOC Motor oriented controller
Table 1.2 Abbreviations
6 MG10V402 - VLT® is a registered Danfoss trademark
196 mm/7.7 in
374 mm/
14.7 in
175ZB032.13
394 mm/15.5 in
216 mm/8.5 in
255 mm/10 in
98 mm/
3.8 in
Mechanical Installation
2 Mechanical Installation
2.1 Dimensions and Weight
VLT® Inverter Scroll CDS 801 Operating Instructions
2 2
Illustration 2.1 Dimensions
MG10V402 - VLT® is a registered Danfoss trademark 7
236 mm/9.3 in
216 mm/8.5 in 394 mm/15.5 in
180 mm/
7.1 in
98 mm/
3.8 in
175ZB031.13
255 mm/10 in
180 mm/
7.1 in
Mechanical Installation
VLT® Inverter Scroll CDS 801 Operating Instructions
22
Illustration 2.2 Dimensions
Mounting holes: ¼ inch, Ø 6 mm Weight: 10.3 lbs/5.5 kg
8 MG10V402 - VLT® is a registered Danfoss trademark
175ZB036.10
175ZB037.10
Mechanical Installation
VLT® Inverter Scroll CDS 801 Operating Instructions
2.2 Installation Orientation and Clearances
2.2.1 Surface Mounting
The drive can be installed horizontally (see Illustration 2.4) or vertically (see Illustration 2.3) on any plain surface with the PCB pointing towards the surface. Typically, the 6 mounting holes in the side flaps of the chassis are used for installation.
For vertical installation, the upper two mounting holes can be used as suspension holes.
NOTE
If the drive is installed on a sheet metal surface, the clearance between the drive PCB and the mounting surface must be observed. As a minimum, sheet metal gauge 22, 33/1000 inch or 1 mm should be used. If electrical contact with the mounting surface can not be avoided an additional isolation foil should be used.
2 2
NOTE
For outdoor units, do not install the drive horizontally with the PCB in the top or bottom. Water condensing on the PCB cannot be properly drained.
Illustration 2.3 Horizontal Orientation
Illustration 2.4 Vertical Orientation
MG10V402 - VLT® is a registered Danfoss trademark 9
175ZB038.12
Mechanical Installation
To avoid insufficient cooling, do not install the drive with the cooling fan in the top, see Illustration 2.5.
VLT® Inverter Scroll CDS 801 Operating Instructions
22
Illustration 2.5 Wrong Drive Orientation
10 MG10V402 - VLT® is a registered Danfoss trademark
175ZB041.10
175ZB042.10
Mechanical Installation
2.2.2 Structural Mounting
VLT® Inverter Scroll CDS 801 Operating Instructions
The drive can be integrated in any kind of mechanical structure of air conditioning equipment Illustration 2.6 and Illustration 2.7.
2 2
Illustration 2.7 Horizontal Installation in Mechanical Structure
CAUTION
During mechanical installation of the drive make sure that no screws can touch electrical parts on the PCB. Screws touching the electrical parts on the PCB can cause personal injury and product damage.
Illustration 2.6 Vertical Installation in Mechanical Structure
MG10V402 - VLT® is a registered Danfoss trademark 11
175ZB043.10
Mechanical Installation
VLT® Inverter Scroll CDS 801 Operating Instructions
2.3 Air Circulation/Cooling
2.5
The drive must be installed in a way that allows for free
22
airflow. However short circuiting the airflow (warm air re­entering the drive’s cooling fan) must be avoided (see Illustration 2.8). A clearance of 5 inches (12.7 cm) must be observed in both ends of the drive chassis. Install the drive in a location where coldest possible air can be drawn into the drive, i.e. from the bottom part of an outdoor unit. Counter flow (static pressure) must not restrict the operation of the internal cooling fan of the drive.
Vibration and Mechanical Resonances
The mechanical structure (sheet metal) carrying the drive must be designed to withstand vibration and consequently resonances induced by the compressor or condenser fan. See vibration specification for the drive further down this document.
Also refer to 6.3.5.8 Frequency Cancelation explaining the possibility to program bypass frequencies in the drive to avoid mechanical resonances of the structure.
Illustration 2.8 Wrong Drive Airflow
2.4
Condensation and Dripping Water
The printed circuit board assembly of the drive is conformally coated and thus sufficiently protected against condensation during off time. Nevertheless, the drive should not be exposed to dripping water (rain) or condensing water slung around by the condenser fan. In outdoor units, it is recommendable to install the drive in a rain proof compartment.
12 MG10V402 - VLT® is a registered Danfoss trademark
Electrical Installation
VLT® Inverter Scroll CDS 801 Operating Instructions
3 Electrical Installation
3.1 Electrical Connection in General
NOTE
All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper conductors required.
3.2 Tightening Torque
Power supply plug terminals 1.5 Nm/1.1 lbf ft Ground screw 3.0 Nm/2.2 lbf ft Motor plug (compressor) 1.5 Nm/1.1 lbf ft EMC clamp for motor cable 1.5 Nm/1.1 lbf ft
Proper temperature rating of the cable must be observed. In installations with ambient temperatures above 30 °C maximum current derating applies, therefore high­temperature cable with 90 °C conductor temperature, e.g. Nexans Rheyflex is recommended. Copper type cable only. Maximum cable length 2 m.
Cable specification for installations in North America: 3-wire cable, minimum cross section AWG 10, voltage rating 600 V, temperature rating 221 °F/105 °C, 2/64 moisture resistant UL style 1230 standard bare copper type. In North America, standards for radiated emission are currently not enforced. Furthermore, FCC parts 15 regulations explicitly exempt air-condition devices. Maximum cable length 7 ft. Local compressor grounding.
3
3
Table 3.1 Tightening Torque
3.3 Cable Quality and Dimensioning
Power supply cable There is no need for using shielded cable for the supply of the variable speed drive.
Motor cable The cable from the drive to the compressor (motor) must be shielded to comply with EMC regulations for conducted and radiated emissions in accordance with EN 55011 class A and EN 55014 (with ferrite). A proper ground connection of the shield in both ends is essential to obtain the best suppression of emissions. See also 3.6 Electrical Connections.
Power Supply Cable Specification Power connections must be made in accordance with local and national codes. 2-wire cable plus ground conductor, minimum AWG 10, voltage rating minimum 300 V, minimum temp. rating 105 °C/221°F
Min. circuit ampacity 4 t unit 35 A 5 t unit 40 A
Table 3.2 Power-supply Cable Specificatoin
Motor Cable Specification Depending on the desired level of EMC compliance according to European or North American standards for radiated emissions such as EN 55014/55011 or FCC part 15, a suitable cable connection drive and compressor must be selected. It is recommended to use shielded cable under all circumstances.
Cable specification for installations in the EU: 4-wire cable with protective earth (PE) and shield (min 80% coverage), minimum cross section 4 mm2 for 13 kW units and 6 mm2 for 16 and 20 kW units, voltage rating 600 V.
3 t unit 30 A
Min. circuit ampacity 13 kW/3 t unit 30 A 16 kW/4 t unit 35 A 20 kW/5 t unit 40 A
Table 3.3 Motor Cable Specification
Sensor and Transmitter Cables Refer to the documentation provided with the Danfoss sensors and transmitters. For serial communication connections, see 4 Serial Communication (Modbus RTU).
3.4
Fuses/Circuit Breakers
Branch circuit protection To protect the installation against electrical and fire hazard, all branch circuits in an installation must be short-circuited and over-current protected according to national and local regulations.
Short circuit protection Danfoss requires using the fuses mentioned in Table 3.4 to protect service personnel or other equipment in case of an internal failure in the unit or short-circuit on DC-link of the drive. The variable speed drive provides full short circuit protection in case of a short-circuit on the motor output in accordance with UL regulations.
Over-current protection Overload protection must be provided to avoid overheating of the cables in the installation. Over-current protection must always be carried out according to national regulations (NEC Article 430 “Motors, Motor Circuits and Controllers” and NEC Article 440 “Air­conditioning and refrigeration equipment”).
MG10V402 - VLT® is a registered Danfoss trademark 13
Electrical Installation
Fuses
13 kW/3 t unit 176L0767 RLA 22A max. fuse amperage 30 A 16 kW/4 t unit 176L0766 RLA 28A max. fuse amperage 35 A 20 kW/5 t unit 176L0765 RLA 33A max. fuse amperage 40 A
VLT® Inverter Scroll CDS 801 Operating Instructions
3
Table 3.4 Fuses
NOTE
Fuses of type class RK5 must be used in US installations.
Recommended circuit breakers HVCR type fusible circuit breaker may be used, see rating above.
3.5 EMC Correct Installation
Follow these guidelines when compliance with EN 55011 cl. A or EN 55014 is required.
Good engineering practice to ensure EMC-correct electrical installation:
Use only shielded/braided screened/armored
motor cables and control cables. The shield should provide a minimum coverage of 80%. The shield material must be metal, not limited to but typically copper, aluminum, steel or lead. There are no special requirements for the mains cable.
Connect the shield to ground at both ends for
motor cables and control cables. Avoid terminating the shield with twisted ends
(pigtails). Such a termination increases the high frequency impedance of the screen, which reduces its effectiveness at high frequencies. Use low impedance cable clamps (delivered with the drive) and EMC glands instead.
Ensure good electrical contact between the de-
coupling plate and the metal chassis of the variable speed drive.
Where possible, avoid using unshielded/
unarmored motor or control cables inside cabinets housing the drive.
14 MG10V402 - VLT® is a registered Danfoss trademark
Loading...
+ 40 hidden pages