Danfoss CDS 302, CDS 303 Troubleshooting Manual

Compressor Drives Troubleshooting Check List
CDS 302/CDS 303
http://cc.danfoss.com
Check List
Introduction ......................................................................................................................................... 4
For Your Safety ..................................................................................................................................... 5
Diagnostics...........................................................................................................................................6
Initial Trouble Shooting (visual inspection of the installation) ....................................................... 7
Input power wiring ................................................................................................................................................................................... 7
Output to motor ........................................................................................................................................................................................ 7
Grounding .................................................................................................................................................................................................... 7
Control wiring ............................................................................................................................................................................................. 7
Programming .............................................................................................................................................................................................. 7
Compressor Motor .................................................................................................................................................................................... 7
Cable routing .............................................................................................................................................................................................. 7
Peripheral equipment (sensors, contactors, etc) ............................................................................................................................7
Trip on over Temperature ....................................................................................................................................................................... 7
Drive interior ............................................................................................................................................................................................... 7
EMC Precautions ........................................................................................................................................................................................ 7
Vibration ....................................................................................................................................................................................................... 7
Environmental conditions ...................................................................................................................................................................... 7
Proper clearance ........................................................................................................................................................................................ 7
Trouble shooting ................................................................................................................................8
Fault Symptoms - Display of the drive .............................................................................................................................................. 8
No display (blank display) ...................................................................................................................................................................... 8
Intermittent display .................................................................................................................................................................................. 8
Fault Symptoms in the compressor (motor) ....................................................................................................................................9
Common drives and motor problems ..............................................................................................11
Control logic problems ..........................................................................................................................................................................11
Programming problems ........................................................................................................................................................................11
IGBT, Motor or load problems ............................................................................................................................................................12
Procedure to conduct the dynamic test to check the IGBT .....................................................................................................12
Faults in the drive ....................................................................................................................................................................................12
EMC - Electro Magnetic Compatibility .............................................................................................................................................13
Static test procedures .......................................................................................................................14
Rectier test (static) ................................................................................................................................................................................14
IGBT static test ..........................................................................................................................................................................................15
3FRCC.PC.036.A2.02
Check List
Introduction
Many frequency converters that are sent back to Danfoss every year for factory analysis are diagnosed with No Fault Found (NFF). Establishing whether a frequency converter is faulty or not prior returning it to the factory can increase the uptime of the compressor solution, reduce the unnecessary use of resources and limit the number of NFF.
The purpose of this check list is to facilitate users, eld technicians, engineers and service
personnel working with Danfoss frequency converters to identify faults and perform a rst diagnosis on the drive before sending it to inspection and analysis.
PERFORM THE FOLLOWING FAULT DIAGNOSIS
BEFORE RETURNING A FREQUENCY CONVERTER FOR
FACTORY INSPECTION.
CHECK ALL POSSIBILITIES.
IN CASE OF DOUBT, PLEASE SEEK DANFOSS SUPPORT.
4 FRCC.PC.036.A2.02
Check List
For Your Safety
Figure 1: Drive must be turned OFF for 20min before repair can start
Frequency Converters (FC) contain dangerous voltages when connected to the line voltage. Only a competent technician should carry out the service.
Some instructions should be compulsorily followed to ensure safety while working with the FC.
• Do not touch electrical parts of the FC when the AC line is connected.
• Frequency converters contain DC-link capacitors that can remain charged even when the frequency converter is not powered. To avoid electrical hazards, disconnect AC mains, any permanent magnet type motors, and any
remote DC-link power supplies, including battery backups, UPS and DC-link connections to other frequency converters.
• Wait for at least 20 minutes before touching any of the components.
• When repair or inspection is done, the AC line must be disconnected.
• The STOP key on the control panel does not disconnect the AC line.
• During operation and programming of the parameters, the motor may start without warning. So you have to activate the STOP key when changing data.
5FRCC.PC.036.A2.02
Check List
Diagnostics
WARNINGS and ALARM
Fault detection via LCP: messages are displayed when the frequency converter fault circuit detects a faulty condition or an unresolved fault.
A warning light ashing display indicates potential problems.
There are two levels of alarms; Reset Alarms and Trip-lock Alarms.
Alarm Log Check the content of the alarm log.
5 latest alarms are available through the “Alarm Log” button key on the LCP.
Check the alarm code and refer to the troubleshooting session of the Operating Instructions VLT® CDS 302 and CDS 303 on page
135. It contains guidance for the complete list of alarms and warnings.
Figure 2: WARNINGS and ALARM messages are displayed when the frequency converter fault detects a faulty condition
a) In case of reset alarm: you can stop and then
start the unit.
b) In case of trip-lock alarm, you have to
disconnect the mains, wait for dark display, then stop and start.
If the troubleshooting suggested does not resolve the problem, please contact Danfoss for support.
Do not exchange the drive before contacting Danfoss support.
6 FRCC.PC.036.A2.02
Check List
Initial Trouble Shooting (visual inspection of the installation)
Input power wiring
Output to motor
Grounding
Control wiring
Programming
Compressor Motor
This list shows a variety of conditions that should be inspected visually as a part of initial troubleshooting.
Check for loose connections. Check for proper fusing. Check for blown fuses.
Check for loose connections. Check for switching components in the output circuit. Check for faulty contacts in the switch gear.
The drive requires a dedicated ground wire from its chassis to the building ground. It is also suggested that the motor be grounded to the drive chassis. The use of conduit or mounting
Check for broken or damaged wires and connections. Check the voltage source of the signals. Though not always necessary depending
Check that the drive parameter settings are correct according to the motor, application and I/O conguration.
Check nameplate of the Compressor. Ensure the compressor matches the drive. Check that drive’s
Display: Warnings, alarms, drive status; fault history and many other items are available on the local control panel of the drive.
of the drive to a metal surface is not considered a suitable ground. Check for good grounding connections that are tight and free of oxidation.
on the installation condition, the use of shield cable or a twisted pair is recommended. Ensure the shield is terminated correctly.
compressor par. 1-13 is set according to the compressor e.g.:
Cable routing
Peripheral equipment (sensors, contactors, etc)
Trip on over Temperature
Drive interior
EMC Precautions
ID Name Setup 1 Factory Setup Unit
113 Compressor Selection VZH117-R410A VZH117-R410A
Avoid routing motor wiring. AC line wiring and signal wiring in parallel. If parallel routing is unavailable, try to maintain a separation of 15-
Look for peripheral equipment such as switches or input fuses circuit breakers that may be in the input power side of the drive or output side of the motor. Examine operation and condition of
Check the operational status of all cooling fans. Check for blockage or constrained air passages.
Drive interior must be free of dirt, metal, chips, moisture and corrosion. Check for burnt or damaged power components or carbon deposits that were the result of a disastrous component
Check for proper installation with regards to electromagnetic capability. Refer to the CDS manual, in the chapter “How to install” and then
20cm between the cables or separate them with a grounded conductive partition. Avoid routing cables through free air.
these items as possible causes for operational faults. Check function and installation of pressure sensors or temperature sensors etc. used for feedback to the drive.
failure. Check for cracks or breaks in the housing of the power semiconductors or pieces of broken components housing loose inside the unit.
“ Electrical Installation – EMC Protection “ for further details.
Vibration
Environmental conditions
Proper clearance
Look for unusual amounts of vibration to which the drive may be subject. The drive should be
Under specic conditions these units can be operated within a maximum ambient temperature of 50°C (24h average maximum
These drives require a top and bottom clearance of 10cm to ensure proper airow for cooling.
mounted solidly or the use of shock mounts employed.
45 °C). Humidity level must be less than 95% non-condensing. Check for harmful airborne contaminates such as sulphur based compounds.
Drives with exposed heat sinks out the back of the drive must be mounted on a at solid surface.
7FRCC.PC.036.A2.02
Check List
Trouble shooting
Fault Symptoms - Display of the drive
No display (blank display)
Figure 3: No Display in the LCP (blank)
A fault must have been ocurred when there is:
a) No Display in the LCP (blank) b) Intermittent display in the LCP
There are three LED indicators lights near the bottom of the LCP.
If the green power on LED is illuminated but the backlit display is dark, this indicates that the LCP itself is defective and must be replaced.
It should be certain that the display is completely dark. An error code exists in the drive which
indicates that communications may have failed with the control card.
This is typically seen when an option card has been installed in the drive and is either not connected properly or is malfunctioning.
• If neither indication is available, then the source of the problem may be elsewhere.
Intermittent display
Figure 4: intermittent display
8 FRCC.PC.036.A2.02
Cutting out or ashing of the entire display and power LED indicates that the power supply (SMPS) is shutting down as a result of being overloaded.
This may be due to improper control wiring or a fault within the drive itself.
Check List
Figure 5: Check control cables
Trouble shooting
• The rst step is to rule out the problem in the control wiring.
Figure 6: Disconnect all control wiring
Fault Symptoms in the compressor (motor):
Motor will not run
• Disconnect all control wiring by unplugging the control terminal blocks from the control card.
All control wiring should be checked for shorts or incorrect connections.
• First verify that the unit is properly powered up and there is no warning or alarm .
• The most common cause of this is either incorrect control logic or an incorrectly programmed drive.
• If the display stays lit then the problem is in the control wiring.
• If the display continues to cut out, the fault can be located in either the LCP itself or on the Power card.
Such occurrences will result in one or more of the following status messages being displayed:
LCP Stop
Figure 7: LCP stop = OFF key pressed
Stand by (gure 8)
The LCP stop message is displayed when the OFF key has been pressed.
The stand by message is displayed when there is no start signal at terminal 18.
The bottom section of the display will also be ashing when this occurs.
Ensure that a start command is present at terminal 18.
9FRCC.PC.036.A2.02
Check List
Trouble shooting
Stop (gure 9)
Figure 9: Check pressure switch
Run OK: 25Hz
Quick tip:
Message displayed when the Terminal 27 is low (no signal).
The RUN OK status display indicates that a run command has been given to the drive but the reference (speed command) is zero or missing.
Improperly connected wiring or interrupted wiring is a common service issue for a motor
Ensure that terminal 27 is logic 1 (pressure switch).
Check the control wiring to ensure that a proper reference signal is present at the drive input terminals and that the unit is properly programmed to accept the signal provided.
not operating or the drive not responding to a remote input.
10 FRCC.PC.036.A2.02
Check List
Common drives and motor problems
Control logic problems
Figure 10: checking control signal in the control card
The common drives and motor problems occur due to an error in the
• Control logic
• Programming
Control logic problem occurs when the drive does not respond to a given command.
Control logic problem is located by using the status information displayed by the drive.
Correct reading indicates that the desired signal is detected by the microprocessor of the drive.
• Motor/load
• Internal drive
If there is not a correct indication, the next step is to determine whether the signal is present at the control terminals of the drive.
This can be performed with a voltmeter or oscilloscope.
Programming problems
If the signal is present at the terminal,
the control card is defective and must be replaced.
• If the signal is not present, the problem is external to the drive.
Three areas where programming errors may aect the drive and motor operation are motor settings, references and limits, and I/O conguration.
The drives must be set up correctly for the compressors connected to it. If not, the compressor may fail to start or use higher than normal amount of current.
Check if the correct compressor is selected in pa r. 1-13.
The circuitry providing the signal along with its associated wiring must then be checked.
Any references or limits set incorrectly will result in less than acceptable drive performance.
In case of doubt, reset the drive to factory settings using par. 14-22.
Download again the OEM settings using the copy and paste function in par. 0-50.
11FRCC.PC.036.A2.02
Check List
Common drives and motor problems
IGBT, Motor or load problems
Procedure to conduct the dynamic test to check the IGBT
The motor or motor wiring can develop a phase to phase or phase to ground short resulting in alarm indication and a trip of the unit.
A motor with the unbalanced or non­symmetrical impedances on all the three phases can result in uneven or rough operation or unbalanced output current.
• To determine whether the problem is internal or external to the drive, disconnect the motor from the drive output terminals.
Dynamic tests have to be done without the compressor connected to UVW connector, and the Drive has to be programmed to a proxy 50Hz at start.
The Dynamic test can indicate if one of the IGBT doesn’t switch, and the output voltage will drop on the fault terminal, UVW.
Program the multimeter to AC 1000V RM.
• Connect the positive terminal of the multimeter lead to the U connector, and connect the negative terminal to the V terminal.
• Perform the dynamic output test procedure on all three phases with a digital voltmeter.
If the three voltage measurements are
balanced, the drive is functioning correctly. The problem is therefore external to the drive.
If the voltage measurements are not balanced, the drive is malfunctioning.
This typically means that one or more output IGBT is not switching on and o correctly.
If one of the IGBT fails, the drive is damaged and must be replaced.
• Connect the positive terminal of the multimeter lead to the U connector, and connect the negative terminal to the W terminal.
• Connect the positive terminal of the multimeter lead to the V connector, and connect the negative terminal to the W terminal.
The meter reading will be between 360V - 380V when performing the dynamic test at 400V mains and 50Hz/3000RPM output depending on instrument used.
The reading should be within ±1.5 percent. When the reading exceeds this, the IGBT is damaged.
Figure 11: Dynamic test
Faults in the drive
Drive temperature sensor / Over temperature fault
Current sensor fault
• If the drive is stopped and cooled, the LCP reading shall show the ambient temperature.
When a current sensor fails, it is indicated sometimes by an earth fault alarm that cannot be reset, even with the motor leads disconnected.
• Disconnect the motor from the drive, and then observe the current in the display of the drive.
Note: Both faults above are non-reparable. Drive needs to be replaced
• If not, the temperature sensor or temperature measurement circuit is defective.
• If the motor is disconnected from the unit, the LCP shall read out 0.00A.
• If anything else is shown, this indicates a defective current sensor.
12 FRCC.PC.036.A2.02
Check List
EMC - Electro Magnetic Compatibility
Common drives and motor problems
Eects of EMI
Sources of EMI
Electro Magnetic compliance or EMC are the voltage and current which are not sinusoidal but pulsating.
Electromagnetic Compatibility (EMC) concerns for typical commercial and industrial equipment.
EMI related disturbances to drive operation are uncommon, but the following detrimental EMI eects may be seen:
• Motor speed uctuations
• Serial communication transmission errors
• Drive CPU exception faults
• Unexplained drive trips
Drives utilize Insulated-Gate Bipolar Transistors (IGBTs) to provide an ecient and cost eective means to create the Pulse Width Modulated (PWM) output waveform necessary for accurate motor control.
Detrimental Eects To These Systems May Include The Following:
• Pressure/ow/temperature signal transmitter signal distortion or aberrant behaviour
• Radio and TV interference
• Telephone interference
• Computer network data loss
• Digital control system faults
These devices rapidly switch the xed DC bus vo ltage creating a variable frequency, variable voltage PWM waveform.
This high rate of voltage change [dV/dt] is the primary source of the drive generated EMI.
13FRCC.PC.036.A2.02
Check List
Static test procedures
Rectier test (static)
Symptom:
Step 1
Figure 12: Multimeter should read a voltage drop of 0,4V
Step 2
POWER MUST BE OFF / MAINS AND MOTOR CABLES DISCONECTED!
Verication of: Rectier (input, mains) / IGBT (Output, motor)
Failure of the rectier module will usually result in blown input line fuses.
• Connect the negative terminal of the multimeter meter lead to the positive DC bus.
• Connect the positive terminal of the multimeter lead to the input terminal L1,L2,L3 in turn.
Now reverse the meter leads, i.e. connect the positive terminal of the meter lead to the positive DC bus.
If rectier or IGBT fail, the complete power
card has to be exchanged, since in the CDS drives, the rectier and IGBT are integrated in one power card.
Procedure to conduct the static test on rectier:
The multimeter should show the diode drop
of around 0.44 volt on the three terminals.
• Connect the negative terminal of the meter lead to the input terminals L1, L2, L3 in turn.
The multimeter should show diode open.
Figure 13: Multimeter should show diode open
Step 3
Figure 14: Multimeter should show a diode drop of 0,44V
Now repeat the procedure by connecting to the negative DC bus in order to the test the lower
part of the rectier bridge which consist of diodes
• Connect the negative terminal of the meter lead to the input terminals L1, L2, L3 in turn.
The multimeter should show the diode drop
of around 0.44 volt on the three terminals.
14 FRCC.PC.036.A2.02
Check List
Static test procedures
Step 4 Now reverse the meter leads, i.e. connect the
negative terminal of the meter lead to the negative DC bus.
Figure 15: The multimeter should show diode open
Note: A diode drop reading will vary depending on the model of the ohm meter
IGBT static test IGBT's are placed on the output of the CDS drives
Step 1
Figure 16: The multimeter should show diode open
• Connect the positive terminal of the multimeter lead to the positive DC bus.
• Connect the positive terminal of the meter lead to the input terminals L1, L2, L3 in turn.
The multimeter should show diode open.
• Connect the negative terminal of the multimeter lead to the motor terminal U, V, W in turn.
The multimeter should show the diode open.
Step 2
Figure 17: The multimeter should show the diode drop of around 0.4 volt on the three terminals
Step 3
Figure 18: The multimeter should show open diode
Now reverse the meter leads, i.e. connect the negative terminal of the meter lead to the positive DC bus.
Now repeat the procedure by connecting to the negative DC bus in order to test the second set of IGBTs.
• Connect the positive terminal of the meter lead to the motor terminals U, V, W in turn.
The multimeter should show the diode drop
of around 0.4 volt on the three terminals.
• Connect the negative terminal of the multimeter lead to the negative DC bus.
• Connect the positive terminal of the multimeter lead to the motor terminal U, V, W in turn.
The multimeter should show open diode.
15FRCC.PC.036.A2.02
Check List
Static test procedures
Step 4 Now reverse the meter leads, i.e. connect
the positive terminal of the meter lead to the negative DC bus.
Figure 19: The multimeter should show diode drop around 0.4 volts
• Connect the negative terminal of the meter lead to the motor terminals U, V, W in turn.
The multimeter should show diode drop
around 0.4 volts.
16 FRCC.PC.036.A2.02
Danfoss Commercial Compressors
Danfoss Inverter Scrolls
is a worldwide manufacturer of compressors and condensing units for refrigeration and HVAC applications. With a wide range of high quality and innovative products we help your company to find the best possible energy efficient solution that respects the environment and reduces total life cycle costs.
We have 40 years of experience within the development of hermetic compressors which has brought us amongst the global leaders in our business, and positioned us as distinct variable speed technology specialists. Today we operate from engineering and manufacturing facilities spanning across three continents.
Danfoss Turbocor Compressors
Danfoss Scrolls
Danfoss Optyma Condensing Units
Danfoss Maneurop Reciprocating Compressors
Danfoss Light Commercial Refrigeration
Compressors
Our products can be found in a variety of applications such as rooftops, chillers, residential air conditioners, heatpumps, coldrooms, supermarkets, milk tank cooling and industrial cooling processes.
http://cc.danfoss.com
Danfoss Commercial Compressors, BP 331, 01603 Trévoux Cedex, France | +334 74 00 28 29
askcc@danfoss.com
Danfoss ca n accept no responsi bility for pos sible errors in ca talogues, bro chures and other pr inted material. Da nfoss reserves t he right to alter its p roducts with out notice. This als o applies to produ cts already o n order provided t hat such alteratio ns can be made with out subsequenti al changes being n ecessary in spe cications alre ady agreed. All trade marks in this mate rial are proper ty of the respec tive companies . Danfoss and the Danf oss logotyp e are trademark s of Danfoss A/S. Al l rights reserv ed.
FRCC.PC.036.A2.02 © Danfoss | DCS (CC) | 2015.07
Loading...