Data Sheet
Check valve
Type CCV
Magnetic type
Magnetic type check valves are designed for
installation in commercial refrigerating systems
and in residential or industrial air conditioning
plants. They are used to control the
unidirectional ow of refrigerant to prevent
backow; the magnetic actuator guarantees a
high reliability standard.
Features:
• Ensure the correct ow direction
• Hermetic construction design
• Magnetic closure element for high reliability
standard
• Low pressure drop during operation
• 100% copper connections for easier soldering
• Can be installed in any position and direction
in the system
• Soft sealing by NBR is less sensitive to dirt in
system
AI221586433855en-000601
When the dierential pressure is less than Min.
opening pressure or has reverese pressure, CCV is
closed. The diaphragm is attracted by magnet and
stay in the left of the bracket.
When the refrigerant ows through the valve and
the dierential pressure is more than Min. opening
pressure, the diaphragm will move to the right of
bracket, then the valve will open.
Check valve,Type CCV
Functions
Figure 1: CCV closed
Figure 2: CCV opened
Application
Typical applications for CCV valves are:
• Cold room
• Heat pump
• Chillers
• VRF
Figure 3: Application Diagram
© Danfoss | Climate Solutions | 2021.02 AI221586433855en-000601 | 2
CCV 6s - 28s: 45 bar / 653 psig
CCV 35s: 35 bar / 508 psig
Max. backward dierential pressure
CCV 6s - 22s: 45 bar / 653 psig
CCV 28s: 30 bar / 435 psig
CCV 35s: 24 bar / 348 psig
-40 – 130 °C /-40 – 266 °F
Environmental transport/storage temperature and humidity
-40 – 65 °C /-40 – 150 °F. Air humidity: RH≤95%.
Max. working pressure in bar and psig
Code for production place and time (BE = Wuqing,
week 39, year 2020, weekday C = Wednesday)
Manufacturing site acc. to EN standards
Barcode for individual code no.
identication accord-
ing to EAN standard
Check valve,Type CCV
Media
Table 1: Media
NOTE:
• For a complete list of approved refrigerants, visit http://store.danfoss.com/ and search for individual code
numbers, where refrigerants are listed as part of product details.
• CCV 35s cannot be used with R404A
Product specication
Technical data
Table 2: Technical data
Identication
Relevant product data is available on the product and box label. An example of a box label and product label are
shown, including an explanation of the content.
Table 3: Product and label text
© Danfoss | Climate Solutions | 2021.02 AI221586433855en-000601 | 3