Danfoss Cascade HFC, Cascade HC Application Manual

Application guide
AKS 32 R
GD/DGS
AKS 11
AKS 2050
AKS 11
AK-PC 740/780
GD/DGS
AKS 11
AKD 102
AKS 11
DCR
Pump
SGN
AKS 2050
AKS 11
EKC 313
EVR
ETS
DCR
AKD 102
AKD 102
AK-CC 450
AKS 11
AKVH
AK-CC 550 A
AKS 11
AK-PC 740/780
Danfoss
R64-2050.11
AK-SC 255/ AK-SM 350/ AK-SM 720/ AKA 245
AKS 11
EVRH
Cascade HC/HFC - CO2 system
How to control the system
www.danfoss.com/co2
2 Application guide RA8AB102 © Danfoss 10/2010 Cascade HC/HFC - CO2 system
General description
EKC 313
AK-CC 550
AK-CC 450
Cascade systems are typical not used in FR ap­plications with traditional refrigerants. There are a few reasons for this such as the need to maintain two different refrigerants in one system; system control strategy (especially that of a cascade heat exchanger) is more complex. At the same time using CO2 in cascade systems gives a number of advantages:
• Eciency of the system is high even in the hot
climates
• Only a small amount of refrigerant is needed for
high temperature stage
• Temperature dierence for cascade heat ex­changer is relatively low
• On the high side various refrigerants can be used ex HC/HFC or NH3.
Ammonia/CO2 cascade systems have the highest efficiency of all. If HFC is to be used at a high tem-
perature stage, R134a is a preferable option due
to its thermo dynamical properties and lower
(compared to R404A) GWP potential.
Temperatures and pressures in cascade systems
Intermediate temperature in a cascade system is selected based on the required temperature for high temperature cases in a store which means they can be cooled by CO2 directly. Intermediate temperature can also be optimised for the high­est energy efficiency if the system is used for low temperature only. Since a cascade system actually consists of two different refrigeration systems which are inter­faced but isolated at the cascade heat exchanger, the design working pressure for each can be different. CO2 design pressure is normally based on the availability of components and is equal to 40-45 bar (corresponding to +5 - +10°C). In order to prevent pressure from increasing above the previously mentioned measurements, standstill systems are recommended. Safety valves should have the highest setting. Stand still pressure can be achieved by raising the desing pressure to 80-90 bar.
For example: CO2 side
• System design working pressure (saturated suc­tion temperature): 40 bar (+5°C)
• Safety valve settings: 36 bar (-10% MWP)
• System emergency relief setting: 34 bar (-1°C)
• CO2 discharge pressure setting: 30 bar (-5°C)
The higher the efficiency of the cascade heat exchanger, the lower the difference between the condensation temperature of CO2 and the evaporating temperature of the refrigerant on the high temperature side. As the temperature difference on the cascade condenser increases, the overall efficiency of the refrigeration system decreases!
AK-PC 740/780
AK-PC 740/780
Cascade HC/HFC - CO2 system Application guide RA8AB102 © Danfoss 10/2010 3
Temperatures and pressures in cascade systems (contin­ued)
On systems with low temperatures of the dis­charge CO2 gas (low superheat), the superheat of the expansion valve can be the dimensioning factor for the heat exchanger. If a CO2 system has high superheat, then desu­per-heaters need to be used in order to reduce the load on the high temperature side.
Optimal intermediate pressure in CO2 cascade systems depends on a number of parameters (high temperature refrigerant, load pattern etc.). Generally 2 cases need to be considered:
1) Systems with load at the medium temperature. In this case intermediate pressure should be as high as possible in order to reduce the load at the high temperature stage. The limitations are therefore required temperature on the intermedi­ate level and pressure rating of the system.
2) Systems without load at medium temperature. In this case the intermediate temperature should be in the range of -10 - 0°C (due to the high pres­sure of the CO2 LT) where lower limit is defined by efficiency and higher by system pressure rating
Operating sequence of cas­cade systems
Injection into cascade heat exchanger
In Cascade Systems, it is essential that at least one compressor in the high temperature side is running before the first compressor in the low temperature side can start. Otherwise, the com­pressor in the low temperature side may be cut out due to high pressure.
The same sequence is also valid for filling up the system. First of all, the high temperature circuit needs to be filled with refrigerant and started up.
When this is done, the CO2 can be filled into the
low temperature system.
Injecting liquid into a plate heat exchanger is not a trivial matter. The heat exchanger is often compact and therefore the time constant is very low. AKV valves are not recommended for this application.
It is recommended to use motor valves or other valves that give constant flow. Desuper-heating of CO2 gas entering the cascade heat exchanger can also be recommended for three reasons.
The high temperature expansion valve (ETS) to
the cascade heat exchanger should begin simul­taneously with the high temperature compres­sors. After this, the valve controls the superheat of the high temperature gas. LT compressors are then started up by the CO2 pressure increase on the suction line.
Danfoss pack controllers such as AK-PC 740 and AK-PC 780 are specially designed with built in
control functions to coordinate these operations.
Distribution on the CO2 side is also a critical issue. This is why the heat exchanger has to be designed for direct expansion to make sure the mixture of gas and liquid is evenly distributed to the heat exchanger.
When the heat exchanger is designed for reason­able pressure drop at part load, the oil transport and distribution should work under most condi­tions.
One reason is that the gas is often 60°C and
therefore the heat can be rejected to the ambient or used for heat recovery without problems. The second reason is to reduce thermal stress in the heat exchanger. The third reason is that the CO2 gas gives very high heat fluxes which therefore create unstable conditions on the evaporation side. Therefore it is recommended to reduce the superheat on the CO2 side.
4 Application guide RA8AB102 © Danfoss 10/2010 Cascade HC/HFC - CO2 system
AKS 32 R
GD/DGS
AKS 11
AKS 2050
AKS 11
AK-PC 740/780
GD/DGS
AKS 11
AKD 102
AKS 11
DCR
Pump
SGN
AKS 2050
AKS 11
EKC 313
EVR
ETS
DCR
AKD 102
AKD 102
AK-CC 450
AKS 11
AKVH
AK-CC 550 A
AKS 11
AK-PC 740/780
Danfoss
R64-2050.11
AK-SC 255/ AK-SM 350/ AK-SM 720/ AKA 245
AKS 11
EVRH
Cascade HFC - CO2 system
Cascade HC/HFC - CO2 system Application guide RA8AB102 © Danfoss 10/2010 5
Controls of Cascade system
Control of cascade systems can be divided into:
• Condenser capacity control
• Compressor capacity control
• Cascade injection control
• MT evaporator CO2 ow control
• LT evaporator injection control
Condenser capacity control
Compressor capacity controls
Capacity control of the condenser can be ac­complished via step regulation or speed control of the fans. As regulating sensor for the capacity distribu­tor the condenser pressure should be selected. The reference for the regulation can be defined
in two ways. Either as a xed reference or as a
reference that varies according to the outdoor temperature. The reference for the condensing pressure is set in °C (°F).
Pack controller AK-PC 740 (up to 4 compressors) or AK-PC 780 (up to 8 compressors) controls the
LT suction pressure and is a standard controller for controlling one suction group in any refrigera­tion system. The controller is capable of regulat­ing variable speed of two compressors combined with one-step compressors of the same or differ­ent sizes, depending on the choice of coupling pattern.
Cap. reqquest
Cap.release
A unique feature in the AK-PC 740/780 make it possible to use the Pc pressure in the LT CO2 side
as control sensor for the HT suction pressure. This to ensure fast and stable control of the condens­ing pressure of LT CO2 side.
Low-pressure / high-pressure coordination
Oil Management / Oil equalisation
The AK-PC 740/780 is also able to coordinate the
LT and HT start to ensure a smooth operation. Here the high-pressure compressors can start either as a result of:
- Load on the high-pressure circuit
- Requirements from the low-pressure circuit
The high-pressure circuit will still ensure that the low-pressure circuit is only permitted to start when at least one high-pressure compressor has started. It will also ensure that security timers and compressor timers are complied with.
The build in oil management system covers most systems found on the market to day. Can be used with CO2 as well as all other conventional refrig­erants and support input signals from :
• Level switch on compressor
• Level switch on oil separator
• Level switch on oil receiver
• Pressure transmitter on oil receiver
HT comp. release output
LT comp. release. input
Here both a relay output and an On/off input are used on both control­lers.
HT comp. request input
LT comp. request output
Oil supply to the compressors is managed by activating solenoid valves with user defined ON/ Off pulse sequences.
6 Application guide RA8AB102 © Danfoss 10/2010 Cascade HC/HFC - CO2 system
Cascade injection control
In systems with cascade regulating and CO2 as refrigerant on the low temperature circuit
EKC 313 can regulate liquid injection (by means of an ETS stepper expansion valve) into the cas-
cade heat exchanger in one of two ways:
• Optimize superheat
• Regulate the condensation pressure at the low
temperature circuit while ensuring that the superheat does not become too low.
If there are no evaporators on the high tempera­ture circuit the cascade controller should be set in control mode 1 to optimise superheat. In this application the condensation pressure on the low temperature circuit should be controlled by the compressor capacity controller in the high tem-
perature circuit. Here the LT PC signal is received at the HT P0 input.
MT evaporator CO2 flow control
LT evaporator injection control
The air temperature in the medium temperature display cases or rooms is controlled by opening/ closing a solenoid valve/motor valve in the CO2 supply to the evaporator. The actual temperature control can take place in two ways: as ordinary ON/OFF regulation with a differential, or as modulating control (PWM) where the tempera­ture variation will not be nearly as big as in ON/ OFF control. In a system with several evaporators supplied by the same CO2 liquid pump, modulating tem­perature control should be chosen as this also provides a more constant flow of CO2 to the CO2 pump.
Injection control for the low temperature case and cold room evaporators is an AK-CC 550A utilizing pulse-width-modulating injection valves AKVH and patented adaptive software algorithms to optimise system performance and operation.
Period time, n63
Pressure control
The Danfoss CO2 controllers have more pressure safety functions which prevents safety valves to open and hereby loss of charge.
AK PC 740 pack controller
A max compressor discharge pressure safety function will reduce compressor capacity
Cascade HC/HFC - CO2 system Application guide RA8AB102 © Danfoss 10/2010 7
AK-PC 740
Flexible controller for capacity control of compressors and condenser fans. Number of
I/O can be extended with AK-XM extension
modules.
• 4 compressors with up to 3 un-loaders
• 6 fans
• Max. 60 inputs/outputs
• Variable speed control on lead compressor and
condenser fans
• Build in oil Management functions
Release-request function for coordination between
high-pressure and low-pressure compressors.
AK-PC 780
As AK-PC 740 plus:
AK-CC 450
Complete refrigeration appliance control with great flexibility to adapt to all types of refrigera­tion appliances and cold storage rooms.
AK-CC 550A
As AK-CC 450 +
AK-CC 750
Flexible refrigeration appliance controller for control of up to 4 evaporators.
• 8 compressors with up to 3 un-loaders
• 8 fans.
• Max. 100 inputs/outputs.
• For cooling with brine or pumped CO
• For use with a thermostatic expansion valve.
• Energy optimisation of the whole refrigeration
appliance
• One controller for several dierent refrigeration
appliances
• Natural, electric or hot gas defrost
• For cooling with Electronic expansion valve
• Adaptive control of superheat
• Adaptive defrosting based on evaporator perform-
ance
2
EKC 313
Controller for liquid injection in cascade heat exchangers with CO2 as refrigerant on the low temperature circuit.
ETS
ETS is a series of electrically operated (stepper
motor) expansion valve
• Stepper motor driver for ETS or CCM expansion
valve.
• 0 - 10 V output for ICMTS valves
• Electrically operated expansion valves for precise
liquid injection in evaporators
• Fully balanced, providing bi-ow feature as well as
solenoid tight shut-off function in both flow direc­tions.
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
8 Application guide RA8AB102 © Danfoss 10/2010 Cascade HC/HFC - CO2 system
FC-SPMC
Loading...