MG.60.I3.02 - VLT is a registered Danfoss trademark
Safety and precautions
■
Cascade Controller Option
Cascade Controller Option
175ZA677.11
for
VLT 6000 HVAC
and
Safety and precautions
VLT 8000 AQUA
Operating Instructions
When reading through this Operating Instructions,
you will come across various symbols that
require special attention.
The symbols used are the following:
Indicates a general warning.
NB!:
Indicates something to be noted by the reader.
Indicates a high-voltage warning.
MG.60.I3.02 - VLT is a registered Danfoss trademark
3
Cascade Controller Option
The voltage of the frequency converter
is dangerous whenever the equipment is
connec
of the motor or the frequency converter may cause
damage to the equipment, serious personal injury
th. Consequently, the instructions in this
or dea
manual, as well as national and local rules and
safety regulations, must be complied with.
NB!:
UsingtheVLTDialogSoftwareorthe
FC protocol for serial communication can
cause unintended behaviour of motors
and plant and must be avoided.
Safety regulations
■
1. The VLT frequency converter must be
on-nected from mains if repair work is to be
disc
carried out.Check that the mains supply has been
disconnected and that the necessary time has
sed before removing motor and mains plugs.
pas
2. The [OFF/STOP] key on the control panel of the
VLT frequency converter does n
equipment from mains and is thus n
the
to be used as a safety switch.
ted to mains. Incorrect instal-lation
ot disconnect
ot
necessary time has passed before removing
motor and mains plugs.
7. Reliab
8. Please note that the VLT frequency converter
Warning against unintended start
■
1. The motor can be brought to a stop by
2. While parameters are being changed, the
le galvanic isolation (PELV) is not complied
with if the RFI switch is placed in OFF position.
This means that all control in- and outputs
ly be considered low-voltage terminals
can on
with basic galvanic isolation.
has mo
the DC-bus terminals are used. Check that
all voltage inputs have been disconnected and
that t
repair w o rk is commenced.
means of digital commands, bus commands,
references or a local stop, while the frequency
converter is connected to mains.
If personal safety considerations make it necessary
to ensure that no unintended start occurs, t
stop functions are not sufficient.
motor may start. Consequently,
[OFF/ STOP] must always be activated, after
which data can be modified.
re voltage inputs than L1, L2, L3 when
he necessary time has passed before
the stop key
hese
NB!:
The IMMEDIATE STOP function will release all
slave relays a
switch. The SEQUENCED STOP will stage off
the slave relays a
3. Correct protective earthing of the equipment
st be established, the user must be protected
mu
against supply voltage, and the motor must be
protected against overload in accordance with
plicable national and local regulations.
ap
4. The earth leakage currents are higher than 3.5 mA.
5. Protection against motor overload is included
the factory setting. Parameter 117, Motor
in
thermal protection, default value is ETR trip
1. For the North American market: The ETR
unctions ensure overload protection of the motor,
f
Class 20, in accordance with NEC.
NB!:
Motor Thermal Protection is initialised at 1.0 x
rated motor current and rated motor frequency
(see parameter 117, Motor thermal protection).
nd can not be used as a safety
nd can not be used as a safety switch
6. Do n
4
ot remove the plugs for the motor and
mains supply while the VLT frequency converter
is connected to mains. Check that the mains
supply has been disconnected and that the
MG.60.I3.02 - VLT is a registered Danfoss trademark
Cascade Controller Option
Warning:
Touching the electrical parts may be fatal - even after the equipment has
been disconnected from mains.
200-240 and 380-480 V:wait at least 15 minutes
550-600 V: VL T 6002/8002 - 6027/8027:wait at least 15 minutes
550-600 V: VL T 6032/8032 - 6300/8300:wait at least 30 minutes
175ZA678.11
Safety and precautions
MG.60.I3.02 - VLT is a registered Danfoss trademark
5
Operation modes
■
Cascade Control Operation
■
With the cascade controller option card, the frequency
converter can automatically control up to five
motors. Staging motors on or off is done cyclically,
in accordance with operating hours. This function
assures equal use over time and eliminates concern
about starting a seldom used motor. The cascade
controller includes four Form C relays having contacts
rated 250 V, 2 A (non-inductive) that are used to
control the motor con tactors. The controller option
card installs in the frequency converter control card
cassette and can be ordered factory installed. The
cascade controller is effective in applications where
multiple motors are used to control a common flow,
level or pressure involving pumps, fans, and blowers.
eedback Signals
F
An important advantage to the cascade controller
option is that it is based upon the VLTs advanced
PID controller. This means that programming is
done in selected units of measurement appropriate
to the application and that the feedback and
setpoints can be displayed. Unlike drives that base
staging upon frequency, feedback allows precise
control in response to actual system demand. The
VLTs PID controller accommodates two feedback
signals and two setpoints which allows regulating
a system with different setpoint zones.
Cascade Controller Option
In pumping applications, when a pressure feedback
signal is not practical, the feedback signal may be
taken near the pump by measuring flow. When the
flow rate is low, the pressure needed is low. At
increased flow, the pumps need to provide greater
pressure to compensate for the increased pressure
drop in the piping. The setpoint should be adjusted
to match the flow in these cases. While difficult
to accomplish with standard PID controllers, the
cascade controller provides an easy solution. By
programming one setpoint for minimum flow and
the other for maximum flow, the VLT calculates
intermediate setpoints based on the flow required.
Cascade control operation depends on the general
system design. Two operational modes are available:
1. Standard Cascade Control, with one speed
controlled pump/fan and up to four fixed
speed pumps/fans. Programming for this
mode is described in Chapter 6, StandardCascade Control Mode Setup.
2. Master / Slave Cascade Control has all
pumps/fans speed controlled through the Master
drive. Programming is described in Chapter 7,
Master/Slave Cascade Control Mode Setup.
Standard Cascade Control Mode
6
MG.60.I3.02 - VLT is a registered Danfoss trademark
Standard Cascade Control Mode
■
In standard cascade control, a frequency converter
e Cascade Controller option card installed
with th
controls a variable speed motor and is used to
stage additional constant speed motors on and
y varying the speed of the initial motor,
off. B
variable speed control is provided for the system.
This maintains constant pressure while eliminating
ure surges, resulting in reduced system
press
stress and quieter operation.
The motors can be of equal or differing sizes. The
controller offers a selection of eight pre-defined pump
combinations. Selections allow mixing pumps of
100%, 200% and 300% capacity. This provides a
dynamic capacity range of 9 to 1. The VLT drives
internal PID controller directs the cascade option
card based upon the feedback signal. The cascade
controller will continue operation of the constant speed
motors to meet demand should the drive trip.
Cascade Controller Option
When the master drive is the only one running, the
drives sleep mode can discontinue system operation
when not needed while staying ready to start on
demand. Variable speed control with fixed speed
motors optimizes energy consumption and avoids
damaging a pump running at near no flow condition
L
evel Control
With level control, multiple pumps can be used to
keep a constant level in applications such as a buffer
tank. Typically, a water level sensor provides a
feedback signal for the VLT’s built-in PID controller.
Precise level control is maintained in response to
the system setpoint. With a cascade controller,
additional fixed speed pumps will be staged on or
off, as required, to maintain level control.
stage Timer
D
eA de-stage timer takes effect in standard control
when the drive runs continuously at minimum speed
h one or more constant speed motors running.
wit
Since a variable speed pump at minimum speed
adds no or very limited flow to the system, it is
visable to stop a constant speed motor and
ad
allow the drive to provide the required flow. The
de-stage timer is programmable to avoid frequent
taging of the constant speed motors.
s
Operation modes
Level Control in Standard Cascade Control Mode
MG.60.I3.02 - VLT is a registered Danfoss trademark
7
Master/Slave Cascade Control Mode
■
Master/slave systems control multiple pumps in
el at the same output frequency. Pumps are
parall
staged on and off as required to meet the systems
demand. The master/slave control mode of operation
des maximum system efficiency.
provi
In master/salve control, each motor has its own
adjustable frequency drive which responds to control
from a master drive which contains the cascade
option card. The master drive sends a pulse speed
reference signal to the drives under control to ensure
that all operate at the same speed. The motors
must be of equal size. In some applications, it may
be advisable for a second drive with a cascade
card to act as an auxiliary controller.
Sequential staging of drives on or off is provided by
master drive in response to system feedback,
the
maintaining precise setpoint control. Pressure surge
and water hammer are eliminated. Because all
he operating pumps run at the same speed,
of t
the possibility of running a pump continuously into
a closed check valve is all but eliminated. This
duces pump maintenance by minimizing the
re
wear on pump seals and bearings.
Cascade Controller Option
Danfoss has available the Multiple Unit Staging
Efficiency Calculator (MUSEC), a free software program
available on the Danfoss website. By entering pump
and system data, MUSEC provides the programmer
with master drive on and off staging frequencies
at optimal efficiency for each pump: for example,
three motors providing flow at reduced speed rather
than two at full speed. This often results in 10% to
15% additional savings over similar control systems.
For a free download, go to www.danfoss.com
and enter MUSEC in the search box.
Best efficiency is attained when a pressure transmitter
is placed at the farthest significant load in the system.
If this is not practical and the pressure transmitter
is placed close to the discharge of the pumps, or
when pump data and system characteristics are
not accessible, alternative ways of programming
the cascade controller are provided.
Master/Slave Cascade Control Mode
8
MG.60.I3.02 - VLT is a registered Danfoss trademark
Installation and Wiring Instructions
■
Installing the cascade controller option card
■
This chapter provides instructions for installing the
cascade controller option card into a VLT adjustable
frequency drive. In Standard cascade control mode,
the option card installs into the VLT controlling up to
four additional motors. In Master/Slave mode, the
option card installs in the Master drive controlling
up to four additional slave drives.
Cascade Controller Option
DANGER
VLT adjustable frequency drive
contains dangerous voltages when
connected to line voltage. After
disconnecting from line, wait at least 14 minutes
before touching any electrical components.
Relay o utput connections vary according to the mode
of operation and configuration of the system. Typical
wiring diagrams are also provided in this chapter.
Adhere to all safety guidelines provided in
the VLT Operating Instructions. See the
VLT Operating Instructions for details and for
instructions on drive operation.
orque tightening requirements
T
Tighten all fittings described in this chapter to 7.1
in-lbs (0.8 Nm), unless specified otherwise.
O
ptional transmitter connections
VLT drive terminals12 and 13 provide a 24 VDC,
200 mA power supply. This supply can be used
to power remote transmitters without need for an
external power supply. See wiring instructions in
Chapter 10, Feedback Transmitter Wiring.
WARNING
Only a competent electrician should
carry out electrical installation.
Improper installation of motor or VLT
can cause equipment failure, serious injury
or death. Follow this manual and National
Electrical Code and local safety codes.
CAUTION
Electronic components of VLT
adjustable frequency drive are
sensitive to electrostatic discharge
(ESD). ESD can reduce performance or destroy
sensitive electronic components. Follow
proper ESD procedures during installation
or servicing to prevent damage.
Installation and
Wiring Instructions
MG.60.I3.02 - VLT is a registered Danfoss trademark
9
Cascade Controller Option
1. Access to Control Card Cassette
■
•
Remove Local Control Panel (LCP) keypad by
g out from top by hand. LCP connector
pullin
on panel back will disconnect.
•
Remove terminal protective cover by gently
prying with screw driver at top notch and lift
cover o
•
Open access cover to internal VLT components.
(Drive configurations vary.)
ut of guide pin fittings.
2. Disconnect VLT Drive Control Wiring
■
Touching electrical parts may be fatal
– even after equipment has been
disconnected from AC line. To be sure
that capacitors have fully discharged, wait 14
minutes after power has been removed before
touching any internal component.
•
Remove control wiring by unplugging
connector terminals.
•
Remove wiring clamp by removing two
screws. Save for reassembly.
•
Loosen two captive screws securing control
board cassette to VLT chassis.
10
MG.60.I3.02 - VLT is a registered Danfoss trademark
Cascade Controller Option
3. Remove VLT Cassette and Ribbon Cables
■
•
Lift control board cassette from bottom.
•
4. Remove LCP Keypad Cradle
■
•
•
nect two ribbon cables from VLT
Discon
control board.
Push tabs at side of LCP cradle to release clips.
Pull out to disengage and lift cradle free.
•
Unhinge cassette at top to remove.
Installation and
Wiring Instructions
MG.60.I3.02 - VLT is a registered Danfoss trademark
11
5. Cascade OptionCard Ribbon Cable Routing
■
Electronic components of VLT and
cascade controller option card are
sensitive to electrostatic discharge
(ESD). Follow proper ESD procedures to
prevent component damage. ESD procedures
to prevent component damage.
Cascade Controller Option
•
•
•
•
6. Secure Option Card
■
•
ribbon cables from cascade controller
Route
option card through slot at side of VLT
control board cassette. Option card mounts
component side down.
with
Feed plastic option card insulation pad through
terminal opening in control board cassette.
rt edge of option card into slot (A)
Inse
in side of cassette.
Align opposite side of card with mounting
s (B) provided.
hole
Secure option card to control board cassette
with 3 self-tapping screws and washers provided.
Use a Torx T-10 screw driver.
12
MG.60.I3.02 - VLT is a registered Danfoss trademark
7. Connect Option Card Ribbon Cable to
■
VLT Control Board
•
Pull up
cable socket.
•
DO NOT remove blue insulation on end of
option
into corresponding socket (B) on VLT control
board and push collar closed. Be sure not
to cri
•
Repeat procedure for all ribbon cables.
collar (A) of control board ribbon
card ribbon cable. Insert ribbon cable
mp ribbon cables.
Cascade Controller Option
Installation and
Wiring Instructions
MG.60.I3.02 - VLT is a registered Danfoss trademark
13
Cascade Controller Option
8. Chassis Ground Connection
■
•
Location of holes to mount grounding strips in VLT
chassis can vary with drive configuration.
•
When applicable, remove mounting screws
located in chassis using Torx T-20 screw driver
and save for reassembly. Otherwise, grounding
strips attach with screws provided.
14
MG.60.I3.02 - VLT is a registered Danfoss trademark
Attach LCP keypad craddle to VLT control
board cassette removed in step 4. Ensure not
to crimp option card ribbon cables.
•
Connect two ribbon cables to control board in
corresonding connectors as removed in step 3.
•
Hinge VLT cassette at top of VLT chassis and
reposition into place. Use Torx T-20 screwdriver
to fasten two captive screws. Ensure not to
crimp control board ribbon cables.
provided, as necessary. Use a
Cascade Controller Option
11. Relay Output Connection
■
•
Connect relay output cables to terminal blocks
provided as required by application. (See
wiring diagrams in this chapter.)
•
Insert relay terminal blocks firmly into corresponding
terminal sockets on control board.
•
Secure relay wiring with bottom right wiring
clamp and fasten.
Relay 6-9: A-B make, A-C break
Max. 240 VAC, 2 A
Max. cross-section: 1.5 mm
Torque: 0.22 - 0.25 Nm
2
(28-16 AWG)
Installation and
Wiring Instructions
MG.60.I3.02 - VLT is a registered Danfoss trademark
15
12. Remove Wiring Clamp Mounting Fixture
■
•
Option card insulation pad is designed to use top
most ca
•
Use screw driver to remove top most wiring clamp.
13. Reconnect VLT Control Terminals and
■
Secure Option Card InsulationPad
•
Reconnect VLT control terminals removed in step
2bypressingfirmlyintocorresponding
terminal socket.
•
Crease option card insulation pad flap and insert
into slot in side of control card cassette.
•
Attach insulation pad to top most clamp position
with one screw from removed wiring clamp.
•
Route VLT control terminal wiring through
bottom left wiring clamp and fasten.
ble wiring clamp screw hole for attaching.
Cascade Controller Option
14. Final Reassembly
■
•
Secure access cover to internal VLT components.
•
Replace LCP keypad by positioning guide slots
at bottom of cradle and snaping into place.
•
Attach terminal protective cover by positioning
guide pins at bottom of cover into control card
cassette and snaping into place.
Transmitter wiring
■
Please refer to chapter 10, Feedback
Transmitter Wiring.
16
MG.60.I3.02 - VLT is a registered Danfoss trademark
Standard cascade control wiring diagram
■
The wiring diagram shows an example for a
rd cascade control system with 4 fixed
standa
speed motors, a 4-20 mA pressure transmitter,
and external safety interlock.
Cascade Controller Option
Power terminal connectionsControl board terminal
connections
Option card terminal connections
Installation and
Wiring Instructions
MG.60.I3.02 - VLT is a registered Danfoss trademark
17
Optional Hand/Off/Auto Switch
■
ptional Hand/Off/Auto Switch
O
dard cascade control mode, an optional
In stan
Hand/Off/Auto switch on the constant speed motor
starter is common. During normal operation, the
switch
automatic start and stop commands to the motor.
The HAND position allows manual operation of the
motor
switch to OFF. For a motor in the OFF position, the
is set to AUTO and the drive will signal
. The motor can be disabled by setting the
Cascade Controller Option
cascade controller will try to start it by triggering
its relay. Since no contribution will occur, the next
pump will be switched on. The relay timer will,
however, assume operation for a disabled motor.
See Chapter 12, Service Parameters.
The diagram below provides wiring instructions
for an optional Hand/Off/Auto switch.
18
MG.60.I3.02 - VLT is a registered Danfoss trademark
Cascade Controller Option
Master drive inmaster/slave control wiring diagram
■
The wiring diagram below shows an example of a
Master
system demonstrates a 4-20 mA pressure transmitter,
drive in Master/Slave cascade control. The
Power terminal connectionsControl board terminal
connections
an external safety interlock and four slave drives. The
slave drive speed reference is provided from terminal
17 as a p
used for the Start/Stop command to the slave drives.
ulse signal. The relays on the option card are
Option card terminal connections
Master Drive
Installation and
Wiring Instructions
MG.60.I3.02 - VLT is a registered Danfoss trademark
19
Cascade Controller Option
Slave drive in master/slave control wiring diagram
■
Each slave drive is wired in the same way, receiving
the Sta
from the master drive. The speed reference and its
common are typically looped from Slave-to-Slave.
Power terminal connectionsControl board terminal connections
rt/Stop command and a pulse speed reference
20
Slave Drive
MG.60.I3.02 - VLT is a registered Danfoss trademark
Cascade Controller Option
Changed Drive functions
■
Introduction
■
Installation of the Cascade Controller Option card
into the VLT adjustable frequency drive overrides
some existing drive functions. Changes to the default
parameter setting are shown in the tables below.
Data entered into the drive parameters are used
to program the drive and cascade controller for
system operation. The modified parameter default
settings make programming the cascade controller
easier. See Chapter 5, User Interface, for instructions
on programming drive parameters.
Changed Default Settings with the Cascade Controller Option Card
ParameterDescriptionPrevious defaultNew default
100ConfigurationOpen loopClosed loop
201Minimum output freq.0.0 Hz40% of nominal frequency
205Maximum reference60 Hz100%
206Ramp-up timeVaries with unitSee table below
207Ramp-down timeVaries with unitSee table below
304Terminal 27 (digital input)Safety interlockCoasting stop, inverse
308Terminal 53 (analog in V)ReferenceNo operation
314Terminal 60 (analog in A)ReferenceFeedback (4 20 mA)
318Function after time outNo functionStop (sequence stop)
417Feedback FunctionMaximumVirtual Control Curve
427PID lowpass filter time0.01 sec.0.20 sec.
In addition, parameters that need to be programmed
for cascade control operation are assembled
sequentially in a new and expanded 39 item Quick
Menu. Programming is simplified by following the
Quick Menu items in sequence for either Standard
cascade control or Master/Slave cascade control.
The new Quick Menu is described in Chapter 6, VLT
Drive and Cascade Controller Card Setup.
New options are also available to stop pumps or fans
controlled in cascade operation. A summary of VLT
changed functionality is presented in this chapter.
MG.60.I3.02 - VLT is a registered Danfoss trademark
21
Changed systemstop functions
■
Two stop functions are provided by the cascade
ller option. One function quickly stops a
contro
system. The other stages off pumps in a sequence,
allowing for a controlled pressure stop.
Do not use these functions as emergency
stops. Some functions do not turn
off all pumps.
Standard cascade control mode
Stop functions in Standard cascade control are
described in the table below. In a sequenced
stop, there is a one ramp-down time delay
between each staging off of motors.
Standard Cascade Control
FunctionDescription
OFF/STOP keyProvides a sequenced stop
for all constant speed motors
in opposite order as staged
on. Controller decelerates its
motortoastop.
STOP via
Terminals 16 and
17 (parameters
300 and 301)
Controller decelerates its
motortoastop.Withmotor
stopped, controller provides
sequenced stop for constant
speed motors.
STOP via
Terminal 18
(parameter 302)
Constant speed motors
continue to operate normally
with feedback signal from
drive. Controller decelerates
its motor to a stop.
STOP via
Terminal 27
Coast Inverse
Constant speed motors stop
immediately. Controller coasts
its motor to a stop.
(parameter 304)
STOP via
Terminal 27
Safety Interlock
Constant speed motors stop
immediately. Controller coasts
its motor to a stop.
(parameter 304)
Cascade Controller Option
Master/Slave cascade control mode
Stop fu
are described in the table below.
OFF/STOP keyProvides a sequenced
STOP vi
and 17 (parameters 300
and 301)
STOP via Terminal 18
(parameter 302)
STOP v
27 Coast Inverse
(parameter 304)
STOP via Terminal
27 Safety Interlock
(parameter 304)
Serial communications(parameter 500)
■
The Danfoss FC protocol may be used only with
VLT Dialog software for programming and setting
up drive and cascade controller parameters.
nctions in Master/Slave cascade control
Master/Slave Cascade Control
FunctionDescription
stop for all slave motors
in opposite order as
staged on.
Master decelerates its
motortoastop.
aTerminal16
Slave m
otors all stop
together. Master
decelerates its motor to
.
astop
Slave motors all stop
together. Master
decelerates its motor to
astop.
ia Terminal
motors all stop
Slave
together. Master coasts
its motor to a stop.
Slave motors all stop
together. Master coasts
its motor to a stop.
22
MG.60.I3.02 - VLT is a registered Danfoss trademark
User Interface
■
How to use the LCP for programming
■
The combined display and keypad on the front of the
VLT is called the Local Control Panel (LCP).
The LCP is the user interface to the VLT
adjustable frequency drive.
The LCP has several user functions: programming
the VLT; displaying operational data, along with
warnings and cautions; to reset the drive after
a fault; and, in local control, to start/stop and
control the speed of the drive.
Control keys for parameter setup
■
Each parameter determines an operational function
the drive. Many parameters are used in combinations
with others. The keys shown below are used for
programming the drive by selecting from parameter
options or entering data in the parameter, as
applicable. The LCP keys are also used for selecting
the data displayed during normal operation of the drive.
Cascade Controller Option
[+/-] are used to scroll through parameters and for
changing a selected parameter. These keys can also
be used to change the drive speed as a function of
the local reference. In addition, the keys are used in
Display mode to switch between readouts.
[<>] are used when selecting a parameter group
and for moving the cursor to the desired digit
when changing numerical values.
Indicator lamps
■
At the bottom of the control panel are three indicator
lamps: a red alarm lamp, a yellow warning lamp,
and a green voltage (power on) lamp.
If pre-determined threshold values are exceeded,
the alarm and/or warning lamp is activated,
and a status or alarm text is displayed. The
power-on light is activated when the VLT adjustable
frequency drive receives voltage.
[DISPLAY/MODE] is used to change display modes
or to return to the Display mode from either the
Quick Menu or the Extend Menu mode.
[QUICK MENU] gives access to the programming
parameters in the Quick Menu. These are the
most commonly used parameters in setting
up the drive functions.
[EXTEND MENU] gives access to all drive parameters,
including Quick Menu items.
[CHANGE DATA] is used for changing a parameter
setting selected in either the Extend Menu
or the Quick Menu mode.
[CANCEL] is used if a change to a selected
parameter is not to be carried out.
[OK] is used for confirming a change to a
selected parameter.
Drive Control
■
Keys for control of the drive are described below.3
[HAND START] is used if the VLT drive is to be started
and controlled from the LCP. The VLT drive will start
the motor when [HAND START] is pressed.
NB!:
The motor will start when [HAND START]
is activated if parameter 201, Outputfrequency low limit, is set to an output
frequency greater than 0 Hz.
The following control signals are active on the control
terminals when [HAND START] is activated:
•
Hand Start - Off Stop - Auto Start - Reset
•
Safety interlock
•
Coasting stop inverse
•
Reversing
User Interface
MG.60.I3.02 - VLT is a registered Danfoss trademark
23
Cascade Controller Option
•
Setup select lsb - Setup select msb
•
Jog
•
Run per
•
Lock for data change
•
Stop command from serial communication
missive
[OFF/STOP] is used for stopping the connected
motor in Hand or Auto mode. This key can be
diabled in parameter 013. If the stop function is
activated, the main display will flash.
[AUTO START] is used if the VLT is to be controlled
through the control terminals. When a start
signal is act ive on the control terminals and/or
serial bus, the VLT drive will start.
NB!:
Drive can start at anytime with a start signal
through digital inputs. Digital inputs have
higher priority than control keys [HAND
START] and [AUTO START].
[RESET] is used for manually resetting the drive after
a fault trip (alarm). In this case, the top line of the
display will show TRIP (RESET). If the top line of the
display shows TRIP (AUTO START), the drive will
automatically restart. If the top line of the display
shows TRIPLOCK (DISC. MAINS), input power to the
drive must be removed before the trip can be reset.
Display modes
■
In Auto operational mode, information is displayed in
any of three programmable displays. Pressing the
[DISPLAY MODE] key enters display mode and toggle
between modes I and II. In Display mode, the [+] and
[-] keys scroll through all data display options. When
in Mode II, holding down the [DISPLAY MODE] key
identifies the units the display is showing on the top
line. Mode IV is available only in local Hand operation.
In normal operation, three data readouts can be
shown on the first (top) line of the display. One readout
is available for line 2 (the large display). Parameters
008, 009 and 010 select the data displayed on the
top line. Parameter 007, Large Display Readout,
selects the data displayed on line 2.
The list on the next page defines the operating
data that can be selected for the display readouts.
Line 4 (bottom line) automatically displays the
operating status of the drive.
The active setup number and an arrow indicating
the direction of motor rotation is shown on the right
side of the large display. Clockwise indicates forward
and counterclockwise indicates reverse. The arrow
body is removed if a stop command is given or if
the output frequency falls below 0.01 Hz.
Warnings and alarms (fault trips) will also be displayed.
During an alarm, ALARM and the alarm number
is shown on the large display. An explanation is
given in line 3 or in lines 3 and 4. For a warning,
WARN. and the warning number is shown with an
explanation in line 3 and/or 4. Both alarms and
warnings cause the display to flash.
VAR 1.1 VAR 1.2 VAR 1.3
VAR 2
SETUP
1
STATUS
The list below gives the operating data options for
the first and second line of the LCP display.
Data Item:Unit:
Resulting reference, %[%]
Resulting reference, unit[unit]
Frequency[Hz]
%ofmaximumoutput
frequency
Motor current[A]
Power[kW]
PowerPower [HP]
Output energy[kWh]
Hours run[hours]
User-defined readout[unit]
Setpoint 1[unit]
Setpoint 2[unit]
Feedback 1[unit]
Feedback 2[unit]
Feedback[unit]
Motor voltage[V]
DC-link voltage[V]
Thermal load on motor[%]
Thermal load on VLT[%]
Input status, digital input[binary code]
Input status, analog
terminal 53
Input status, analog
terminal 54
Input status, analog
terminal 60
Output status, relay status[binary code]
Pulse reference[Hz]
External reference[%]
Heat sink temperature[
User-defined text[-]
[%]
[V]
[V]
[mA]
C]
24
MG.60.I3.02 - VLT is a registered Danfoss trademark
Cascade Controller Option
Three operating data values can be shown in the
first display line and one in the large display line,
mmed via parameters 007, 008, 009, and 010.
progra
D
isplay mode I
InDisplaymodeI,thedriveisinAutomodewith
reference and control determined via t he control
terminals. Below is an example in which the drive
is running in setup 1, in Auto mode, with a remote
reference, and at an output frequency of 40 Hz.
The text in line 1, FREQUENCY, describes the
r shown in the large display. Line 2 (large
mete
display) shows the current output frequency (40.0
Hz), direction of rotation (reverse arrow), and active
p (1). Line 3 is blank. Line 4 is the status line
setu
and the information is automatically generated for
display by the drive in response to its operation. It
ws that the drive is in auto mode, with a remote
sho
reference, and that the motor is running.
´
FREQUENCY
40.0Hz40.0Hz
40.0Hz
40.0Hz40.0Hz
AUTO REMOTE RUNNING
SETUP
1
175ZA683.10
The last part of line 4 indicates the drive’soperational
status, for example: RUNNING, STOP, or ALARM.
D
isplay mode II
This display mode shows three operating data values
in the top line programmed v ia parameters 007,
008, and 009. Pressing the [DISPLAY MODE] key
toggles between Display modes I and II.
100% 7.8A 5.9kW
SETUP
50.0Hz
AUTO REMOTE RUNNING
Display mode III
Press and hold the [DISPLAY MODE] key while in Mode
II. Mode III is visible as long as the key is depressed.
The top line changes to identify the data names and
units displayed. Lines 2 and 4 are unchanged. When
the key is released, the display returns to Mode II.
REF% CURR.A.POW.,KW
60.0Hz
1
SETUP
1
175ZA685.10
175ZA686.10
Status line (Line 4): Additional automatic displays
forthedrivestatuslineareshownbelow.
80.0% 5.08A 2.15kW
SETUP
40.0Hz
AUTO REMOTE RUNNING
HAND LOCAL STOP
OFF RAMPING
JOGGING
.
.
.
.
STAND BY
The left indicator on the status line displays the
active control mode of the VLT drive. AUTO is
displayed when control is via the control terminals.
HAND indicates that control is local via the keys
ontheLCP.OFFindicatesthatthedriveignores
all control commands and will not run.
The center part of the status line indicates the
reference element that is active. REMOTE means that
reference from the control terminals is active, while
LOCAL indicates that the reference is determined
via the [+] and [-] keys on the control panel.
1
175ZA684.10
AUTO REMOTE RUNNING
Display mode IV
This display mode is used for local operation, where
the local speed reference is given from the keypad. In
this display mode, the reference is determined via the
[+] and [-] keys. Control is carried out through the
bottom keys on the keypad. The first line indicates
the requ ired reference. The third line gives the relative
value of the output frequency in the form of a bar
graph in relation to the maximum frequency.
USE +/- 40Hz
40.0Hz
HAND LOCAL RUNNING
Changing data
■
Regardless of whether a parameter has been selected
under the Quick Menu or the Extend Menu, the
procedure for changing data is the same. Pressing
the [CHANGE DATA] key gives access to changing
the selected parameter. Line 3 displays the parameter
175ZA688.10
User Interface
MG.60.I3.02 - VLT is a registered Danfoss trademark
25
Cascade Controller Option
number and title. The underlined function or number
flashing in line 4 on the display is subject to change.
The procedure for changing data depends on
whether the selected parameter represents a
numerical data value or a function.
hanging numeric values
C
If the chosen parameter represents a number
, the flashing digit can be changed by means
value
of the [+] and [-] keys. Position the cursor by
using the [<] and [>] keys, then change the data
e using the [+] and [-] keys.
valu
The selected digit is indicated by a flashing cursor.
Thebottomdisplaylinegivesthedatavaluethat
will be entered (saved) by pressing the [OK] button.
Use [CANCEL] to ignore the change.
FREQUENCY
24.2 Hz
205 MAX. REFERENCE
000060.000 Hz
6
SETUP
1
175ZA687.10
2. Use [+] and [-] keys to find parameter
you choose to edit.
3. Press [
4. Use [+] and [-] keys to select correct parameter
5. Press [Cancel] key to disregard change, or press
Example of how to change parameter data
■
Assume Quick Menu item 9 (parameter 206, Ramp
Up Time) is set at 60 seconds. Change the ramp
up time to 100 seconds as follows:
1. Press [Quick Menu] key.
2. Press [+] key until you reach Quick Menu item
3. Press < key twice hundreds digit will flash.
4. Press [+] key once to change hundreds digit to 1.
5. Press
6. Press [-] key until 6 counts down to 0 and setting
7. Press [
Change Data] key.
setting. To move to a different digit within a
c parameter, use < and > arrows. Flashing
numeri
cursor indicates digit selected to change.
ey to accept change and enter new setting.
[OK] k
9of35
for Ramp Up Time reads 100 s.
(parameter 206), Ramp Up Time.
> key once to move to tens digit.
OK] key to enter new value.
Changing functional values
If the selected parameter is a functional value,
the selected text value can be changed by
meansofthe[+]and[-]keys.
MOTOR CURRENT
SETUP
3.90 A
210 REFERENCE TYPE
SUM
The functional value flashes until signing off by pressing
the [OK] button. The functional value has then been
selected. Use [CANCEL] to ignore the change.
C
hanging listed numeric values
A few parameters offer numeric lists of values that
can be selected from or changed. This means
that if the numeric value is not listed, a value
may be entered using the procedure for changing
numeric values. This applies to parameter 102,
Motor power, parameter 103, Motor voltage,and
parameter 104, Motor frequency.
1
175ZA689.10
Manual initialization
■
The drive can be initialized to return to
factory default settings.
NB!:
Initializing the drive will remove all values and
settings entered into drive. Some factory default
ngs may be for European applications.
setti
1. Remove AC power to drive.
2. Press and hold [DISPLAY MODE] + [CHANGE
DATA]+[OK]keysdownwhileatsametime
applying AC power to drive.
3. Release keys. VLT reverts to factory setting.
It is also possible to carry out initialization via
parameter 620, Operating mode, by selecting Initialize.
Parameter setting procedure
■
Enter or change parameter data or settings as follows:
1. Press [Quick Menu] or [Extended Menu] key.
26
MG.60.I3.02 - VLT is a registered Danfoss trademark
Cascade Controller Option
The following parameters are not reset when
using manual initialization:
500, Protocol
600, Operating hours
601, Hours run
602, kWh counter
603, Number of power-ups
604, Number of overtemperatures
605, Number of overvoltages
724 - 737, Operating hours/counters
User Interface
MG.60.I3.02 - VLT is a registered Danfoss trademark
27
VLT Drive and Cascade Controller Setup
■
Introduction
■
A new quick menu list is activated when a cascade
controller option card is installed in the VLT adjustable
frequency drive. The original 12 items are expanded
to 39 quick menu items that allow programming
additional drive and cascade controller functions.
See Chapter 4, Changed Drive Functions.
The first 20 items on the new quick menu must
be programmed in sequ ence for initial drive and
cascade controller setup. (See block diagram.) These
20 items are common to both Standard cascade
control mode and Master/Slave control mode. After
initial setup is complete, additional quick menu
items program the drive for the selected mode of
operation. Those instructions are available in Chapter
7, Standard Cascade Control Mode Setup and
Chapter 8, Master/ Slave Control Mode Setup.
Chapter 9, System Optimization, provides instructions
for final adjustments to reach maximum drive and
controller efficiency after system start up.
Cascade Controller Option
selects the mode of operation for further setup.
The Quick Menu Summary table on the next
page describes the menu items.
The VLT adjustable frequency drive has four
independent setups that can be programmed.
The initial programming in this chapter is stored
as Setup 1. See Alternative Programming at
the end of this chapter for instructions on using
the drives multi-setup capability.
VLT drives delivered with the cascade controller
option card already installed, or prepared for field
installation, have been programmed with factory
settings typical for operation. These settings may be
satisfactory for initial start up of the system.
See Chapter 5, Use Interface, for instructions
on programming the VLT drive.
Items 2 6 are motor characteristics. In Standard
cascade control mode, only the motor data from the
variable speed motor run by the cascade controller
are entered. In Master/Slave control, only data from
the motor controlled by the Master drive are entered
at this time. Items 7 19 are basic cascade controller
settings used in either mode of operation. Item 20
28
MG.60.I3.02 - VLT is a registered Danfoss trademark
Quick Menu Summary
■
Cascade Controller Option
Quick Menu
numbe
Basic Drive Set Up parameters
001001Language10 languagesSee VLT 6000 H VAC or VLT
002102Motor PowerKW/HP1.1-450/1.5-600
003103Motor Volta geVolts200 - 480
004104Motor FrequencyHz50 / 60
005105Motor CurrentAmps0-IVLT max
006106Rated Motor SpeedRPM0- fm,n x 60
007201Min. Fr equencyHz0.0 -fmax2/5 of fnom (NEW)
008202Max. FrequencyHzFmin-120/1000Fnom x 1.1 (NEW)
009206Ramp up timeSeconds1-3600See table above in 2.4.8
010207Ramp down timeSeconds1-3600
011323Relay 1 OutputDepending on cho iceSee VLT 6000 HVAC Manual.
012326Relay 2 Output
Basic Set Up for Standard Cascade and Master/Slave.
013415Closed loop unitsSelected acc or ding to your p ro cess.
014413Minimum Feedba ck
015414Maximum Feedback
016227Warning low FeedbackUnits-999,999.999- FB High-999,999.999
017228Warning high FeedbackUnitsFB low- 999,999.999999,999.999
018204Ref.min.UnitsMin. feedback - Ref.max0
019205Ref.max.UnitsRef.min - Max. feedback0
020723Operational Mode select-Standard / M/SStan dar d Ca scade
021712Pump combination1-81
022713Staging BandW.%1. 0 - 100.010.0
023714Destaging DelaySec.0.0 - 300015
024715Staging DelaySec.0.0 - 300015
025716Override BW%ofsetpoint2.0 - 10 0.020.0
026717Override TimerSec.0.0 - 3005
027718Transition frequency%offnomfmin - 120.060
028418Setpoint 1 (H0)Bar (or equiv.)Refmin - Refmax6bar
029419Setpoint 2 (H1)Bar (or equiv.)Refmin - Refmax6bar
030721Destage TimerTimer Sec.0.0 - 60030
031722Pump cyclingEnabled/DisabledEnabled
032319Analog/digital outputs-[1] - [43]F out 020mA
033739M/S Stage on frequenciesHzFmin-FmaxFmin
034740M/S stage off frequenciesHzFmin-FmaxFmax
PID Controller tun ing
035420Normal/Inverse controlNormal/InverseNormal mode
036422PID Start up frequencyHzFmin-fmax0Hz
037427PID Lowpass filter timeSec.0.01 10.001. 00
038423PID Proportional GainFactor0.00 10.00. 01
039424PID Integrator timeSec.0.01 9999.0OFF
Parame-
r
ter nu
ber
NameUnitsRangeFactory setting
m-
8000 AQUA manuals.
Controller Setup
VLT Drive and Cascade
Language
■
Quick Menu 001 Par. 001 Language
(LANGU
AGE)
Value:
✭English(ENGLISH)
German(DEUTSCH)
MG.60.I3.02 - VLT is a registered Danfoss trademark
French (FRANCAIS)
Danish (DANSK)
Spanish (ESPAÑOL)
Italian(ITALIANO)
Swedish (SVENSKA)
Dutch (NEDERLANDS)
29
Cascade Controller Option
Portuguese(PORTUGUESA)
Finnish (SUOMI)
Function:
This choice defines the language to be
used on the display.
Description of choice:
Select the display language.
NB!:
It is important that the values set in parameters
102-106, Motor nameplate data, correspond
to the nameplate data of the motor.
Motor nameplate data
■
Quick Menu 002 Par. 102 Motor power
(MOTOR POWER)
Value:
0.1/3 HP (0.25 KW)
0.5 HP (0.37 KW)
0.75 HP (0.55 KW)
1.0 HP (0.75 KW)
1.5 HP (1.10 KW)
2 HP (1.50 KW)
3 HP (2.20 KW)
4 HP (3.00 KW)
5 HP (4.00 KW)
7.5 HP (5.50 KW)
10 HP (7.50 KW)
15 HP (11.00 KW)
20 HP (15.00 KW)
25 HP (18.50 KW)
30 HP (22.00 KW)
40 HP (30.00 KW)
50 HP (37.00 KW)
60 HP (45.00 KW)
75 HP (55.00 KW)
100 HP (75.00 KW)
125 HP (90.00 KW)
150 HP (110.00 KW)
200 HP (132.00 KW)
250 HP (160.00 KW)
300 HP (200.00 KW)
350 HP (250.00 KW)
400 HP (300.00 KW)
450 HP (315.00 KW)
500 HP (355.00 KW)
600 HP (400.00 KW)
This sets the power value that corresponds to the
nameplate power of the motor. The default setting
30
MG.60.I3.02 - VLT is a registered Danfoss trademark
Cascade Controller Option
Quick Menu 005 Par. 105 Motor current
(MOTOR CURRENT)
Value:
0.01 - Drive rating
✭ Depends on motor
Function:
The rated motor current in amps forms part of the
VLT frequency converter calculations for torque
and motor thermal protection.
Description of choice:
Set a value that equals the nameplate data
on the motor.
NB!:
It is important to enter the correct value, since
this forms part of the VVC
+
control feature.
Quick Menu 006 Par. 106 Rated motor speed
(MOTOR
NOM. SPEED)
Value:
100 - 60000 rpm
✭ Depends on parameter 102, Motor power
Function:
This is where the value is set that corresponds to the
rated motor speed found on the nameplate data.
Description of choice:
Set a value that corresponds to the motor
nameplate data.
NB!:
It is important to set the correct value, since
+
this forms part of the VVC
control feature.
Description of choice:
Set a value from 0.0 Hz to the Output frequency high
limit set in Quick Menu item 008 (parameter 202).
Quick Menu 008 Par. 202 Output frequency
high limit
(MAX. FREQUENCY)
Value:
Para 201 setting - Para 200 limit
✭ 60 Hz
Function:
In this parameter, a maximum output frequency can
be selected that corresponds with the maximum motor
speed. The drive will not be able to run continuously
at an output frequency above this value in any mode.
NB!:
e output frequency high limit to 60 Hz
Set th
for US applications. The output frequency
of the VLT frequency converter can never
e a value higher than 1/10 of the switching
assum
frequency (parameter 407, Switching frequency).
Description of choice:
Enter a value between the low frequency limit, set
in Quick Menu item 07 (parameter 201), and the
frequency range limit, set in parameter 200.
Quick Menu 009 Par. 206 Ramp-up time
(RAMPUPTIME)
Value:
1 - 3600 sec.
✭ Depends on unit
Controller Setup
VLT Drive and Cascade
The maximum value equals frequency x 60. Frequency
is set in parameter 104, Motor frequency.
Quick Menu 007 Par. 201 Output frequency
low limit
(MIN. FREQUENCY)
Value:
0.0 - Parameter 202 setting
✭ 0.0 HZ
Function:
This is where to select the minimum output frequency.
The drive will be unable to run continuously
below t
MG.60.I3.02 - VLT is a registered Danfoss trademark
his value in any mode.
Function:
The ramp-up time is the acceleration time from 0 Hz
to the rated motor frequency (parameter 104, Motorfrequency). It is assumed that the output current
does not reach the current limit (set in parameter
215, Current limit). This determines the maximum
acceleration rate for all modes of operation.
31
Description of choice:
Set the desired ramp-up time. Too long of a ramp
up can cause sluggish drive operation. Too short of
a ramp up can cause the drive to go into current
limit during acceleration or cause unaccepta ble
torque pulses in the controlled system.
Quick Menu 010 Par. 207 Ramp-down time
(RAMP DOWN TIME)
Value:
1 - 3600 sec..
Function:
The ramp-down time is the deceleration time from
the rated motor frequency (parameter 104, Motorfrequency) to 0 Hz. This ramp-down time may be
automatically extended to prevent an overvoltage trip if
the load regenerates to the drive. This determines the
maximum deceleration rate for all modes of operation.
Description of choice:
Set the desired ramp-down time. Too long of a
ramp down can cause sluggish operation. Too
short of a ramp down can cause the drive to trip off
due to high DC bus voltage or cause unacceptable
torque pulses in the controlled system.
✭ Depends on unit
Cascade Controller Option
Relay 1
1 - 3 break, 1 - 2 make Max. 240 VAC, 2 Amp. The
relay is with the main and motor terminals.
Relay 2
4 - 5 make Max. 50 VAC, 1 A, 60 VA. Max. 75 VDC,
1A,30W.Therelayisonthecontrolcard.
Quick Menu 011 Par. 323 Output relay 1
(RELAY 1 FUNCTION)
Value:
29 optional settings
Function:
This output activates relay switch 01. This 240 volt,
Form C relay can be used for status and warnings.
There are 29 optional settings. It is generally
programmed to provide a remote alarm indication.
No Alarm is the default setting. This indicates the
drive is operating properly and the contact is closed.
The contact opens to indicate an alarm when there
is a fault condition or when the drive looses power.
Terminal wires 1 and 3 are wired together.
Alarm is selected when a loss of power
should not cause an alarm indication. Wire
terminals 1 and 2 together.
See the VLT Operating Instructionsfora
detailed list of relay options.
✭ NO ALARM
Relay outputs
■
Relay outputs 1 and 2 can be used to give the
present drive status or a warning.
If the output is used as a voltage output (0-10 V),
a pull-down resistor of 500
terminal 39 (common for analogue/digital outputs.
See chapter 10 for additional detail).
Iftheoutputisusedasacurrentoutput,the
resulting impedence of the connected equipment
should not exceed 500 W.
32
should be fitted to
Description of choice:
Select relay 1 function.
MG.60.I3.02 - VLT is a registered Danfoss trademark
Cascade Controller Option
Quick Menu 012 Par. 326 Output relay 2
(RELAY 2 FUNCTION)
Value:
29 optional settings
✭ RUNNING
Function:
This output activates relay switch 02. This low voltage
relay is generally programmed to provide a remote
run indication. There are 29 optional settings.
Running makes this relay close when the drive
is running. This is the default setting.
This unit will be used for the reading in the Display
modeandasaunitforMinimum / Maximum
Feedback, Minimum / Maximum Reference, Warning
Feedback High/Low and for the H1, H0 and thecalculated Hmx parameter settings/readings.
Description of choice:
Select the unit for the reference/feedback signal.
Quick Menu 014 Par. 413 Minimum feedback
(MIN. FEEDBACK)
Value:
-999,999.999 - FB
MAX
✭ 0.000
Function:
Parameters 413, Minimum feedback and 414,
Maximum feedback are used to scale the feedback
signal ensuring that it shows the feedback signal
proportionally to the signal at the input.
Description of choice:
Setthevaluetobeshownonthedisplaywhenthe
feedback signal is at its minimum value.
Quick Menu 015 Par. 414 Maximum feedback
(MAX. FEEDBACK)
Value:
FB
- 999,999.999
MIN
✭ 100.000
Function:
Parameters 413, Minimum feedback and 414,
Maximum feedback are used to scale the feedback
signal ensuring that it shows the feedback signal
proportionally to the signal at the input.
Description of choice:
Setthevaluetobeshownonthedisplaywhenthe
feedback signal is at its maximum value.
Controller Setup
VLT Drive and Cascade
MG.60.I3.02 - VLT is a registered Danfoss trademark
33
Cascade Controller Option
Quick Menu 016 Par. 227 Warning:
Low feedback
(WARN LOW FDBK)
Value:
-999,999.999 - FB
(parameter 228)
HIGH
✭ -999.999,999
Function:
If the feedback signal is below the limit programmed
in this parameter, the display will show a
flashing FEEDBACK LOW.
The warning functions in parameters 221-228
are not active during ramp up after a start
command, ramp down after a stop command
or while stopped. The warning functions are
activated when the output frequency has reached
the resulting reference. The signal output can
be programmed to generate a warning signal via
terminal 42 or 45 or via the relay output.
In Closed loop, the unit for the feedback is programmed
in parameter 415, Units related to closed loop.
Description of choice:
Set the desired value within the feedback range
between parameter 413, Minimum Feedback,and
parameter 414, Maximum Feedback.
Quick Menu 018 Par. 204 Minimum reference
(MIN. REFERENCE)
Value:
Parameter 100 Configuration = Closed loop [1].
-Par.413 Minimum feedback
-par.205Ref
MAX
✭ -999.999,999
Function:
The Minimum Reference sets the minimum value
of the sum of all references. If Closed loop has
been selected in parameter 100, Configuration,
the minimum reference is limited by parameter
413, Minimum Feedback. Minimum reference is
ignored when the local reference is active. In
this case, minimum reference is determined by
parameter 201, Minimum Frequency.
Description of choice:
Set the desired value within the feedback range
between parameter 413, Minimum Feedback and
parameter 414, Maximum Feedback.
QuickMenu 017 Par. 228 Warning High feedback
(WARN. HIGH FDBK)
Value:
FB
(parameter 227) - 999,999.999
LOW
✭ -999.999,999
Function:
If the feedback signal is above the limit programmed
in this parameter, the display will show a
flashing FEEDBACK HIGH.
The warning functions in parameters 221-228 are
not active during ramp-up after a start command,
ramp-down after a stop command or while
stop-ped. The warning functions are activated when
the output frequency has reached the resulting
reference. The signal outputs can be prog rammed
to generate a warning signal via terminal 42 or
45 and via the relay outputs.
Description of choice:
Set the Minimum Reference, which is the lowest
reference value that can be set for the drive. The
unit for this reference is set in parameter 415.
Quick Menu 019 Par. 205 Maximum reference
(MAX. REFERENCE)
Value:
Par. 204 Ref
- par. 414 Maximum feedback
MIN
✭ 50.000 Hz
Function:
The Maximum reference gives the maximum value
that can be assumed by the sum of all references.
The Maximum Reference is limited to be with the
settings of Parameter 414 Maximum Feedback.
The Maximum reference is ignored when the local
reference is active (parameter 203 Reference site).
Description of choice:
Set the Maximum reference, which is the highest
reference value that can be set for the drive.
In Closed loop, the unit for the feedback is programmed
in parameter 415 Units related to closed loop.
34
Quick Menu 020 Par. 723 Mode Select
(MODE SELECT)
Value:
Standard Control
✭ Master/Slave
Master/Slave Control
MG.60.I3.02 - VLT is a registered Danfoss trademark
Function:
Standard cascade control mode operation is a system
consisting of one adjustable speed pump and up to
four constant speed pumps. Master/Slave cascade
control mode operation is for a system using variable
speed pumps controlled by a Master drive.
NB!:
Set the correct control option. Improper setting
may result in system damage, operational
errors, or wasted energy.
Description of choice:
Select Standard Control for operating the cascade
controller option card in Standard control mode.
Select Master/Slave Control for operating the cascade
controller option card in Master/Slave control mode.
Cascade Controller Option
Controller Setup
VLT Drive and Cascade
MG.60.I3.02 - VLT is a registered Danfoss trademark
35
Cascade Controller Option
Alternate programming
■
etup configuration and copying parameters
S
The fre
setups that can be programmed. Each setup
acts independently in controlling the drive. An
exampl
setups for day/night or summer/winter operation.
Any of the four setups can be used.
The setup is selected in Extended Menu parameter
002, Active Setup, for programming and operation.
Setups are changed manually by switching between
active setups in parameter 002. It is also possible
to change setups through digital inputs or serial
communication by selecting Multi-Setup in parameter
002 and providing an external signal.
The number of the active setup selected is
show
the second line of the display.
The Extended Menu is accessed by pressing the
[EXTEND. MENU] key on the LCP keypad.
A short cut to programming more than one setup is
pos
Setup Copy. This enables copying one setup to
another. After an active setup has been programmed
an
other setups need be changed.
All setups can be transferred from one frequency
converter to another (in the same VLT series) by
using the frequency converter’s removeable keypad.
Extended Menu parameter 004, LCP Copy,allows
this function. First, upload all parameter values to
the keypad. The keypad can then be removed and
plugged into another frequency converter where
all parameter values can be downloaded. If motor
or drive sizes differ, Download Power-independentParameters can be selected in parameter 004 to omit
downloading motor and current dependent data.
✭Setup 1 (SETUP 1)
This parameter defines the setup number that controls
the drive. All parameters can be programmed in four
individual parameter setups: Setup 1, Setup 2, Setup
3 and Setup 4. There is also a pre-programmed
nly setup, called the Factory Setup.
read-o
Description of choice:
Factory Setup contains the parameter values preset at
the factory. This setup can be used as a data source if
the other setups are to be returned to a known state.
Setups 1 through 4 are four individual setups that
can be programmed and selected as required.
Multi-Setup is used if remote switching between
different setups is required. Terminals 16, 17, 29,
32, 33 and the serial communication port can be
used for switching between setups.
Extended MenuExtended Par. 003 Setup Copy
(SETUP COPY)
Value:
✭No copying (NO COPY)
Copy active Setup to Setup 1
(COPY TO SETUP 1)
Copy active Setup to Setup 2
(COPY TO SETUP 2)
Copy active Setup to Setup 3
(COPY TO SETUP 3)
Copy active Setup to Setup 4
(COPY TO SETUP 4)
Copy active Setup to All
(COPY TO ALL)
Function:
A copy is made from the active setup selected
in parameter 002, Active Setup, to the setup
or setups selected here.
NB!:
Copying is only possible when drive is stopped.
Description of choice:
The copying starts when t he required copying function
has been
display indicates when copying is in progress.
Extended Menu Par. 004 LCP Copy
Value:
✭No copying (NO COPY)
Upload all parameters
(UPLOAD ALL PARAMET.)
Download all parameters
selected and the [OK] key pressed. The
(LCP COPY)
[0]
[1]
[2]
[3]
[4]
[5]
[0]
[1]
36
MG.60.I3.02 - VLT is a registered Danfoss trademark
Cascade Controller Option
(DOWNLOAD ALL PARAM.)
Download power-independent parameters
(DOWNLOAD SIZE INDEP.)
Function:
This parameter is used to copy all parameter setups to
or from the Local Control Panel (LCP) keypad. It can
be used to store a backup copy of all parameters in the
LCP or to copy all setups from one drive to another.
Description of choice:
Select Upload all parameters to copy all parameter
values from the drive to the LCP.
Select Download all parameters to copy all
parameter values from the LCP to the drive on
which the keypad is mounted.
Select Download power-independent parameters
if only the power-independent parameters are
to be downloaded. This allows the parameters
from one drive to be easily copied to another
drive of a different size. Settings in parameters
102, 103, 104, 105, 106, 215, 221, and 222 are
not downloaded using this function.
[2]
[3]
Controller Setup
VLT Drive and Cascade
NB!:
Copying is only possible when drive is stopped.
MG.60.I3.02 - VLT is a registered Danfoss trademark
37
Standard Cascade Controller Setup
■
Introduction
■
In standard cascade control, a frequency converter
with the cascade option card controls a motor in
response to system feedback signals w hile staging
additional constant speed motors on and off. By
varying the speed of the initial motor, variable speed
control is provided for the system.
The motors can be of equal or differing sizes. The
controller offers a selection of eight pre-defined
pump combinations (see parameter 712).
A de-stage timer takes effect in standard control mode
when the drive runs continuously at minimum speed
with one or more constant speed motors running. The
de-stage timer is programmable to avoid frequent
staging on and off of the constant speed motors.
Although pump applications are highlighted in this
chapter, the procedures and settings are nearly
identical for other applications. The feedback process
setup described, assumes that a pressure feedback
signal is measured at the outlet of the pumps.
P
rogramming instructions:
Instructions for programming Quick Menu items
1-20 are presented in Chapter 5, VLT Drive andCascade Controller Card Setup. Parameters
1-20 must be programmed before programming
Standard cascade control options.
Cascade Controller Option
S
ensor placement:
Best efficiency is attained when the pressure
transmitter is placed at the farthest significant load
in the system. This setup allows measurement of
actual system peformance. If this is not practical,
the pressure transmitter is usually placed close
to the discharge of the pumps.
The cascade controller uses the feedback to estimate
the setpoint required at various rates of flow. Setpoint
1 is the minimum pressure required when the system
is running with only the frequency converter operating
at full speed. Setpoint 2 is the maximum pressure
required when the system is running with all pumps at
full capacity. A theoretical value calculates pressure
loss in the system under minimum and maximum
loads. The controller adjusts the loading based
upon the number of pumps in operation.
When the pressure transmitter is placed at the farthest
significant load in the system, common in HVAC
applications, see alternative ways of programming
the cascade controller described in AlternateProgramming at the end of this chapter.
General information on how to program the frequency
converter through the local control panel keypad
are presented in Chapter 4, User Interface.
The instructions in this chapter describe procedures
for programming the frequency converter for standard
cascade control mode operation. The Quick
Menu simplifies setup since the 39 parameters
are programmed in sequence. Procedures for
programming are in the following order:
Initial Setup: Quick Menu items 1-20
Step 1: Standard control mode programming
Step 2: Optimization of the process regulator
Alternate Programming
Optimizing the process regulator is performed after
system start up. The procedures are described
in Chapter 9, System Optimization.
38
MG.60.I3.02 - VLT is a registered Danfoss trademark
Cascade Controller Option
Initial Setup
■
Instructions for programming Quick Menu items
1-20 ar
Cascade Controller Card Setup. Parameters
1-20 must be programmed before programming
addit
The combinations of pumps and their rated capacities
are selected in this parameter. The lead pump (or fan)
with the cascade contol option must have a capacity
of 100% and its speed is controlled by the VLT
adjustable frequency drive. This enables the highest
accuracy in regulation of the system. In Standard
cascade control mode, additional pumps can be either
100%, 200% or 300% relative to the VLT driven p ump.
e presented in Chapter 5, VLT Drive and
ional options described below.
Quick Menu 021 Par. 712 Motor Pump
Combinations
(PUMP COMBINATION)
Value:
(See options in table below)
Function:
Motor Pump Combinations
Value:
Additional Constant Speed Pumps Operated by Cascade Control
Select the pump combination and capacities
from the choices offered.
1 pump controlled
by relay 7
2 pumps controlled
by relays 7, 8
1 pump controlled
by relay 8
2 pumps controlled
by relays 8, 9
Controller Setup
Standard Cascade
MG.60.I3.02 - VLT is a registered Danfoss trademark
39
Quick Menu 022 Par. 713 Staging Bandwidth %
(STAGING BANDW%)
Value:
1 - 100%
Function:
In cascade control systems, to avoid frequent
switching of fixed speed pumps, the desired system
pressure is typically kept within a bandwidth rather
than at a constant level. The staging bandwidth
(SBW) is programmed as a percentage of the setpoint
(desired pressure). For example, if the setpoint is 5
bar and the SBW set at 10%, a system pressure
between 4.5 and 5.5 bar is tolerated. No staging or
destaging will occur within this bandwidth.
Description of choice:
Set the staging bandwidth percentage to accomodate
m pressure fluctuation.
syste
✭ 10%
Cascade Controller Option
Description of choice:
Set the staging bandwidth off time delay. A delay
time of 30 seconds (factory setting) is sufficient
in most systems. When encountering frequent
staging, add to the delay time.
NB!:
Should the drive trip for any reason, the
cascade controller can continue operation
with the remaining C/S pumps or fans. It is
recommend, however, that the user consider a wider
bandwitdth for parameter 716, Override Bandwidth.
Otherwise, unnecessary staging could occure.
Quick Menu 023 Par. 714 SBW staging off time
(DESTAGING DELAY)
Value:
0 - 3000 sec.
Function:
Immediate destaging of a fixed speed pump is not
desirable when a momentary pressure increase in
the system that exceeds the staging bandwidth
(SBW). Destaging is delayed by the length of time
programmed. If the pressure decreases to within the
SBW before the timer has elapsed, the timer is reset.
✭ 30 sec.
Quick Menu 024 Par. 715 SBW staging on time
(STAGING DELAY)
Value:
0 - 3000 sec.
Function:
Immediate staging of a fixed speed pump is not
desirable when a momentary pressure drop in
the system that exceeds the staging bandwidth
(SBW). Staging on is delayed by the length of time
programmed. If the pressure increases to within the
SBW before the timer has elapsed, the timer is reset.
Description of choice:
Set the staging on time delay. A delay time
of 30 seconds (factory setting) is sufficient in
most sys tems. When encountering freq uent
staging, decease delay time.
✭ 30 sec.
40
MG.60.I3.02 - VLT is a registered Danfoss trademark
Quick Menu 025 Par. 716 Override bandwidth
(OVERRIDE BANDW%)
Value:
2 - 100 % (100 = OFF)
Function:
When a large and quick change in the system
demand (such as a sudden water demand), the
system pressure rapidly changes and an immediate
staging or destaging of a fixed speed pump becomes
necessary to match the requirement. The override
bandwidth (OBW) is programmed to override the
staging/destaging timer for immediate response. The
override bandwidth is a percentage of the setpoint and
defines the feedback (pressure) at which the timers
(set in parameters 714, 715) are overridden. For
example, if the setpoint is 5 bar and the override is set
to 20%, the low limit is 4 bar and the high limit 6 bar.
✭ 100 = OFF
Cascade Controller Option
Commissioning the Cascade Controller
To avoid unintended staging during the commissioning
phase and fine tuning of the controller, initially leave
the OBW at the factory setting of 100%. When the
fine tuning is completed, the OBW should be set to
the desired value. A good initial value may be 10%.
Quick Menu 026 Par. 717 Override Bandw. timer
(OVERRIDE TIMER)
Value:
0 - 300 sec.
Function:
Staging a fixed speed pump creates a momentary
pressure peak in the system, which might exceed
the override bandwidth (OBW). It is not desirable
to destage a pump in response to a staging
pressure peak. The override bandwidth timer can
be programmed to prevent st aging until the system
pressure has stabilized and normal control established.
✭ 10 sec.
Controller Setup
Standard Cascade
Description of choice:
The OBW must always be programmed to a higher
value than the staging bandwidth (SBW) set in
parameter 713. Setting the OBW too close to
the SBW could defeat the purpose with frequent
staging at momentary pressure changes. Setting
the OBW too high might lead to unacceptably
high or low pressure in the system while the SBW
timers are running. The value can be optimized
with increased familiarity with the system. See
parameter 717, Override Bandwidth Timer.
Description of choice:
Set the timer to a value that allows the system to
stabilize after staging. The 10 second factory setting
is appropriate in most applications. In highly dynamic
systems, a shorter time might be desirable.
Quick Menu 027 Par. 718 Transition frequency
(TRANSITION FREQ %)
Value:
0 - 120 % of F
Function:
The adjustable speed pump typically runs at maximum
speed when staging on an additional fixed speed
pump to match the system demand.
max
✭ 90%
MG.60.I3.02 - VLT is a registered Danfoss trademark
41
Cascade Controller Option
The instant effect of the fixed speed pump creates
a momentary overpressurization until the adjustable
speed pump decelerates. This is undesirable in
most situations. To avoid this, this drive can be
programmed to decelerate to a transition frequency
before starting the fixed speed pump.
the transition frequency might cause the check valve
at the discharge of a variable speed pump to close
the transition, which could add pressure in the
during
system. Ensure that the transition frequency setting
allows the check valve to remain open.
Example:
Maximum frequency (F
um frequency (F
Minim
max
)= 30Hz
min
) = 60Hz
Transistion frequency to be programmed exactly
nd F
a
F
max
Then, transition frequency = 45/F
min
= 45/60 =75%
max
Quick Menu 028 Par. 418 Setpoint 1
(SETPOINT 1)
Value:
Feedback Min. to Feedback Max
✭ 0.000
The opposite process occurs during destaging
where a momentary pressure drop is avoided by
increasing the speed of the adjustable speed pump.
Therefore, set a transition frequency roughly half-way
between minimum and maximum frequency.
NB!:
Ensure that the transmission frequency is set
within the minimum frequency and maximum
set in parameters 201 and 202.
Description of choice:
Adjust the transition frequency to the best compromise
to prevent momentary pressure overshoot and a
pressure drop during transition. A very low value for
the transition frequency might cause the check valve
at the discharge of a variable speed pump to close
during the transition, which could add pressure in the
system. Ensure that the transition frequency setting
allows the check valve to remain open.
Adjust the transition frequency to the best compromise
to prevent momentary pressure overshoot and a
pressure drop during transition. A very low value for
Function:
The default feedback process is used when a
pressure feedback signal is measured at the outlet
of the pumps. The cascade controller uses the
feedback to estimate the setpoint required at
various rates of flow. All other reference signals
are ignored. Setpoint 1 is the minimum pressure
required when the system is running with only the
adjustable frequency drive operating at full speed.
Setpoint 1 is a theoretical value that the cascade
controller uses as an internal reference to calculate
pressure loss in the system under minimum load.
The controller adjusts the internal reference based
upon the number of pumps in operation.
The range is determined by Quick Menu item 14
(parameter 413, Minimum Feedback) and Quick Menu
item 015 (parameter 414, Maximum Feedback).
When the pressure feedback signal originates at
the far end of the system, the drive does not
need to compensate for system pressure changes
42
MG.60.I3.02 - VLT is a registered Danfoss trademark
Cascade Controller Option
due to flow. For this system configuration, or
for two setpoint PID control, see Alternative
mming at the end of this chapter.
Progra
Description of choice:
Set the desired feedback minimum within the
programmed minimum and maximum in Quick Menu
items 014 and 015. The process unit is selected
in Quick menu item 013, Process Units.
NB!:
Factory setting is for a single 4 - 20 mA current
signal transmitter for process feedback. In
all other cases, see instructions in Chapter
10, Feedback Transmitter Wiring.
Quick Menu 029 Par. 419 Setpoint 2
(SETPOINT 2)
Value:
Feedback Min. to Feedback Max.
Function:
The default feedback process is used when a pressure
feedback signal is measured at the outlet of the
pumps. The cascade controller uses the feedback to
estimate the setpoint required at various rates of flow.
All other reference signals are ignored. Setpoint 2 is
the maximum pressure required when the system is
running with all pumps at full capacity. A theoretical
value calculates pressure loss in the system under
maximum load. The controller adjusts the loading
based upon the number of pumps in
✭ 0.000
across the outlet of the pumps, see AlternativeProgramming at the end of this chapter.
Description of choice:
Set the desired feedback maximum within the
programmed minimum and maximum in Quick Menu
items 014 and 015. The process unit is selected
in Quick menu item 013, Process Units.Inawater
supply system with little leakage, the difference
between Setpoint 1 (set in Quick Menu item 028) and
Setpoint 2 is typically around 10% to 15%.
Quick Menu 030 Par. 721 De-stage timer
(DESTAGE TIME)
Value:
0 - 300 sec. (301= OFF)
Function:
The de-stage timer starts when the adjustable speed
pump is running a minimum speed with one or more
ant speed pumps in operation and system
const
requirements satisfied. In this situation, the adjustable
speed pump contributes little to the system. When
rogrammed value of the timer expires, a fixed
the p
speed pump is destaged and the adjustable speed
pump accelerated to maintain system requirement.
saves energy and avoids dead head water
This
circulation within the adjustable speed pump.
Description of choice:
Set the de-stage timer interval. When sleep mode is
activated, ensure the interval is set lower or equal to
the value of the sleep mode timer (parameter 403).
✭ 15 sec.
Controller Setup
Standard Cascade
The range is determined by Quick Menu item 014
(parameter 413, Minimum Feedback) and Quick Menu
item 05 (parameter 414, Maximum Feedback).
When the pressure feedback signal originates at
the far end of the system, the drive does not
need to compensate for system pressure changes
due to flow. For this system configuration, or for
two setpoint PID control, or for water pumping
systems where the feedback signal is measured
MG.60.I3.02 - VLT is a registered Danfoss trademark
43
NB!:
Sleep mode activates when the adjustable
speed p
turn off the destage timer, turn off sleep
mode first. Set parameter 403, Sleep Mode to
conds (off), then parameter 721, De-stage
301 se
Timer to 301 seconds (off).
Quick Menu 031 Par. 722 Pump cycling
(PUMPCYCLING)
Value:
Enabled - Disabled
Function:
To achieve equal hours of operation in the constant
speed pumps, pump use can be cycled. Timers
on the relay outputs (relays 6, 7, 8, and 9) monitor
the running hours of each pump. In staging on, the
relay (pump) with the least hours is switched on.
In destaging, the relay (pump) with the most hours
is switched off. Not operating a pump over long
time periods can create corrosion concerns.
ump is the only pump running. To
✭ Enabled
Cascade Controller Option
If cycling is disabled, the controller follows the
fixed pattern of relay activation (6, 7, 8 and
9) regardless of the running hour counters.
Destaging is in the reverse order.
Description of choice:
Choosewhethertodisableorenablethefunction.
Quick Menu 035 Par. 420 PID normal/inverse
rol
cont
(PID NOR/INV. CTRL)
Value:
✭Normal (NORMAL)
Inverse(INVERSE)
Function:
This determines how the d rives PID controller
responds to a difference between the setpoint and
feedback. Normal is when the drive is to reduce the
output frequency as the feedback signal increases.
Inverse is when the drive is to increase the output
frequency as the feedback signal increases.
[0]
[1]
Description of choice:
Select the PID controller response op tion.
44
MG.60.I3.02 - VLT is a registered Danfoss trademark
Cascade Controller Option
Alternate programming
■
In water supply systems, it is o ften impractical to
place a
In HVAC and other applications, however, it is often
possible to place the pressure sensor(s) at the farthest
signi
system. In these cases, the cascade option can
use the drive’s PID controller to respond to system
chang
on and off in response to the system feedback signal.
The most common setup for feedback response
is with a single transmitter located at the farthest
significant load in the system. Programming the
cascade controller option in this manner is described
below. It is also possible for the PID to accept
two feedback signals, making two-zone regulation
available. For two feedback control, and for additional
setting options, see the VLT Operating Instructions.
Setup for feedback response is with a single
tra
the system requires programming parameter 417,
Feedback Function, and parameter 418, Setpoint 1.
Pa
through the Extended Menu. The Extended Menu
is accessed by pressing the [EXTEND. MENU] key
on
be accessed through either the Extended Menu
or as item 28 in the Quick Menu.
pressure sensor at the far end of the system.
ficant load and measure actual pressure in the
es as programmed. Pumps or fans are staged
nsmitter located at the farthest significant load in
rameter 417, Feedback Function, is only accessible
the drive control panel. Parameter 418 may
Description of choice:
Set the feedback function to Maximum for
the drive to use Setpoint 1 as the maximum
reference signal for control.
Quick Menu 028 Par. 418 Setpoint 1
(SETPOINT 1)
Value:
Feedback Min. to Feedback Max.
Function:
Setpoint 1 is used to provide the setpoint reference
for one setpoint PID control or for the setpoint for
zone 1 in two setpoint PID control.
All other reference signals are ignored.
Description of choice:
Set the required value the system is to maintain
during n ormal operation. The value must be between
the minimum and maximum values set in Quick
Menu items 14 and 15 (parameter 413, MinimumFeedback, and parameter 414, Maximum Feedback).
Setpoint 2, Quick Menu item 29, is not used in
one feedback signal applications.
✭ 0.000
Controller Setup
Standard Cascade
EXTENDED MENU Par. 417 Feedback Function
(2 FEEDBACK, CALC.)
Value:
Minimum(MINIMUM)
Maximum(MAXIMUM)
Sum (SUM)
Difference (DIFFERENCE)
Average (AVERAGE)
Two-zone minimum (2 ZONE MIN)
Two-zone maximum (2 ZONE MAX)
✭Virtual Control Curve (VIRTUAL CTRL CURVE)
Feedback 1 Only (FEEDBACK 1 ONLY)
Feedback 2 Only (FEEDBACK 2 ONLY)
Function:
This parameter sets the calculation method whenever
a system feedback signal is used, or when two
feedback signals (Setpoint 1 and Setpoint 2) are used.
MG.60.I3.02 - VLT is a registered Danfoss trademark
45
Master/Slave Cascade Control Setup
■
Introduction
■
In Master/Slave cascade control operation, the
frequency converter with the cascade control option
card is the Master. The Master drive controls the
speed and staging on or off of up to four additional
adjustable speed drives. The Master drive exports
a pulse signal or analog speed signal through its
output relays to the slave drives. It is recommended
that a pulse signal be used for minimum electrical
noise and for precise drive control.
The Master drive and the slave drives are programmed
for different operation, although many parameters
are set the same. The Master drive is programmed
for closed loop operation and responds to system
feedback signals to meet the needs of the system.
The slave drives are programmed for open loop
operation and receive a variable speed signal and
stop/start commands from the Master drive.
Although pump applications are highlighted in this
chapter, the procedures and settings are nearly
identical for other applications. The feedback process
setup described, assumes that a pressure feedback
signal is measured at the outlet of the pumps.
P
rogramming instructions:
Instructions for programming Quick Menu items
1-20 are presented in Chapter 6, VLT Drive andCascade Controller Card Setup. Parameters
1-20 must be programmed before programming
Master/Slave cascade control options.
The instructions in this chapter describe procedures
for programming both the Master and slave drives
for Master/Slave cascade control mode. Procedures
for programming are in the following order:
Initial Setup: Quick Menu items 1-20
Cascade Controller Option
entering pump and system data, MUSEC provides
the programmer with Master drive on and off staging
frequencies for each pump at optimal efficiency.
For a free download, go to www.danfoss.com
and enter MUSEC in the search box.
ensor placement:
S
Best efficiency is attained when the pressure
transmitter is placed at the farthest significant load
in the system. This setup allows measurement of
actual system peformance. If this is not practical,
the pressure transmitter is usually placed close
to the discharge of the pumps.
The default feedback process described for setup
in this chapter is used when a pressure feedback
signal is measured at the outlet of the pumps. The
cascade controller uses the feedback to estimate the
setpoint required at various rates of flow. Setpoint 1
is the minimum pressure required when the system
is running with only the adjustable frequency drive
operating at full speed. Setpoin t 2 is the maximum
pressure required when the system is running with all
pumps at full capacity. A theoretical value calculates
pressure loss in the system under minimum and
maximum loads. The controller adjusts the loading
based upon the number of pumps in operation.
When the pressure transmitter is placed at the farthest
significant load in the system, common in HVAC
applications, see alternative ways of programming
the cascade controller described in AlternateProgramming at the end of this chapter.
Although pump applications are highlighted in this
chapter, the procedures and setting are nearly
identical for fan applications, such as controlling
multiple cooling tower fans. Differences between fan
and pump settings are described in the procedures.
Step 1: Master drive programming
Step 2: Slave drive programming
Step 3: Optimization of the process regulator
Alternate Programming
Optimizing the process regulator is performed after
system start up. The procedures are described
in Chapter 9, System Optimization.
B
est efficiency:
Danfoss has available the Multiple Unit Staging
Efficiency Calculator (MUSEC), a free software
program available on the Danfoss website. By
46
General information on how to program the adjustable
frequency drive through the local control panel keypad
are presented in Chapter 4, User Interface.
Initial Setup
■
Instructions for programming Quick Menu items
1-20 are presented in Chapter 5, VLT Drive andCascade Controller Card Setup. Parameters 1-20
must be programmed into the Master drive before
programming additional Master/Slave cascade
control options described below.
MG.60.I3.02 - VLT is a registered Danfoss trademark
Cascade Controller Option
Step 1: Master drive programming
■
The following drive parameters are used in
mming the Master drive. Note that while
progra
the menu items are in sequence, not each menu
item in the Quick Menu is programmed.
Quick Menu 021 Par. 712 Motor Pump
Combinations
(PUMP COMBINATION)
Value:
R6 @100%
R6, R7 @100%
R6-R8 @100%
R6-R9 @100%
Function:
The number of slave pumps or fans is selected
in this parameter. In Master/Slave operation,
all motors are the same size.
R6 @100% = one slave controlled by relay 6.
R6, R7 @100% = two slaves controlled
by relays 6 and 7.
R6-R8 @100% = three slaves controlled by
relays 6, 7, and 8.
R6-R9 @100% = four slaves controlled by
relays 6, 7, 8, and 9.
Description of choice:
Select the number of slave pumps or fans.
Quick Menu 023 Par. 714 SBW staging off time
(DESTAGING DELAY)
Value:
0 - 3000 sec.
✭ R6 @100%
✭ 30 sec.
Quick Menu 024 Par. 715 SBW staging on time
(STAGING DELAY)
Value:
0 - 3000 sec.
Function:
Staging delay time is used to prevent the fast cycling
on of the slave pumps or fans. Increase the time
if frequent switching is encountered.
Description of choice:
Set staging on delay time. In Master/Slave operation,
3 secon
The default feedback process is used when a
pressure feedback signal is measured at the outlet
of the pumps. The cascade controller uses the
feedback to estimate the setpoint required at various
rates of flow. Setpoint 1 is the minimum pressure
required when the system is running with only the
adjustable frequency drive operating at full speed.
Setpoint 1 is a theoretical value that the cascade
controller uses as an internal reference to calculate
pressure loss in the system under minimum load.
The controller adjusts the internal reference based
upon the number of pumps in operation.
dsisatypicalvalue.
Quick M
Value:
Feedback Min. to Feedback Max.
Function:
enu 028 Par. 418 Setpoint 1
(SETPOINT 1)
✭ 30 sec.
✭ 0.000
Control Setup
Master/Slave Cascade
Function:
Destaging delay time is used to prevent the fast
cycling off of the slave pumps or fans. Increase the
time if frequent switching is encountered.
Description of choice:
Set staging off delay time. In Master/Slave operation,
3secon
MG.60.I3.02 - VLT is a registered Danfoss trademark
ds is a typical value.
The range is determined by Quick Menu item 14
(parameter 413, Minimum Feedback) and Quick Menu
item 15 (parameter 414, Maximum Feedback). When
the pressure feedback signal originates at the far end
of the system, the drive does not need to compensate
for system pressure changes due to flow. For this
system configuration, or for two setpoint PID control,
see Alternative Programming at the end of this chapter.
47
Cascade Controller Option
Description of choice:
Set the desired feedback minimum within the
programmed minimum and maximum in Quick Menu
items 14 and 15. The process unit is selected in
Quick menu item 13, Process Units.
NB!:
Factory setting is for a single 4 - 20 mA current
signal transmitter for process feedback. In
all other cases, see instructions in Chapter
10, Feedback Transmitter Wiring.
Quick Menu 029 Par. 419 Setpoint 2
(SETPOINT 2)
Value:
Feedback Min. to Feedback Max.
Function:
The default feedback process is used when a pressure
feedback signal is measured at the outlet of the
pumps. The cascade controller uses the feedback to
estimate the setpoint required at various rates of flow.
Setpoint 2 is the maximum pressure required when
the system is running with all pumps at full capacity. A
theoretical value calculates pressure loss in the system
under maximum load. The controller adjusts the
loading based upon the number of pumps in operation.
✭ 0.000
items 14 and 15. The process unit is selected in
Quick menu item 13, Process Units.
Quick Menu 031 Par. 722 Pump cycling
(PUMP C YCLING)
Value:
Enabled - Disabled
Function:
To achieve equal hours of operation, use of pumps
or fans can be cycled. Timers on the relay outputs
(relays 6, 7, 8, and 9) monitor the running hours of
each pump. In staging on, the relay with the least
hours is switched on. In destaging, the relay with the
most hours is switched off. Not operating a pump
over long time periods can create corrosion concerns.
If cycling is disabled, the controller follows the fixed
pattern of relay activation (6, 7, 8 and 9) regardless of
the running hours. Destaging is in the reverse order.
Description of choice:
Choose whether to enable or disable the function.
Quick Menu 032 Par. 319 Analog output,
terminal 42
(AO 42 FUNCTION)
Value:
Output, terminal 42
✭ Output current 4-20 mA
✭ Enabled
The range is determined by Quick Menu item 14
(parameter 413, Minimum Feedback) and Quick Menu
item 15 (parameter 414, Maximum Feedback).
When the pressure feedback signal originates at
the far end of the system, the drive does not
need to compensate for system pressure changes
due to flow. For this system configuration, or
for two setpoint PID control, see AlternativeProgramming at the end of this chapter.
Description of choice:
Set the desired feedback maximum within the
programmed minimum and maximum in Quick Menu
Function:
An analog/digital output is available through terminal
42 and can be programmed to show a status or an
analog value such as frequency. For the analog output,
there are three types of output signals: 0 to 20 mA, 4
to 20 mA, or 0 to 32000 pulses. The pulse rate is set
by parameter 320, Terminal 42, Output, Pulse Scaling.
Description of choice:
Set the output of terminal 42 to Output Frequency
(pulse sequence), (OUT.FREQ.PULSE) for Master/Slave
operation as shown in the wiring diagram in Chapter
4. Using frequency pulse is a reliable way of providing
the same speed reference to all slave drives. Current
output is limited to two slave drives.
System pressure and flow requirements can often be
generated using parallel pumps at different efficiencies.
The cascade controller can automatically configure
the number of pumps in operation to achieve the
highest system efficiency. Running three pumps at full
48
MG.60.I3.02 - VLT is a registered Danfoss trademark
Cascade Controller Option
speed, for example, may satisfy system requirements,
while running four pumps at a lower speed meets
ements and achieves higher efficiency.
requir
Danfoss has available the Multiple Unit Staging
Efficiency Calculator (MUSEC), a free software
program available on the Danfoss website. By
entering pump and system data, MUSEC provides
the programmer with on and off staging frequencies
for each pump at optimal efficiency. Enter the data for
each pump in Extended Menu parameters 739 and
740. For a free download, go to www.danfoss.com
and enter MUSEC in the search box.
Quick Menu 033 Par. 739 Master/Slave
staging on frequencies
(M/S STAGE FREQ)
Value:
Min. freq - Max. freq
(Par. 201 - 202)
Function:
Best efficiency staging on frequency can be calculated
for the cascade controller based on pump and system
curves to meet feedback requirements. Use the
MUSEC software program to determine the most
efficient staging on frequency for each pump.
Description of choice:
Enter the staging on frequency for each pump.
After pressing the CHANGE DATA key in
parameter 739, use the (+) and (-) keys to scroll
through all four slave settings.
Ifthepumporsystemdataisunknown,refer
to the section Alternative Programming at
end of this chapter.
the
✭ Min.freq.
Description of choice:
Enter the staging off frequency for each pump.
After pressing the CHANGE DATA key in
parameter 740, use the (+) and (-) keys to scroll
through all four slave settings.
If the pump or system data is unknown, refer
to the section Alternative Programming at
the end of this chapter.
Step 2: Slave drive programming
■
The slave drives run in open loop mode and recieve
stop/start and speed reference commands from the
Master drive. Each slave drive must be programmed
with the nameplate data from the motor it controls.
All other applicable parameter settings must match
the settings in the Master drive.
All parameter settings can be transferred from one
VLT drive to another by using the r emoveable keypad.
Parameter 004, LCP Copy, allows this function. First,
upload all parameter values to the Local Control Panel
(LCP) keypad. The keypad can then be removed and
plugged into another VLT drive where all parameter
values can be downloaded. If motor or drive sizes
differ, Download Power-independent Parameters can
be selected in parameter 004 to omit downloading
motor and current dependent data.
Manual programming of slave drives is also possible
following the procedure described for Master drive
programming. To copy required Master drive
parameter settings manually into each slave drive,
enter Master drive settings for Quick Menu items
7-13 and 18-19 into each slave drive.
Commisioning slave drives is done in the
following sequence of events:
Control Setup
Master/Slave Cascade
ck Menu 034 Par. 740 Master/Slave
Qui
staging off frequencies
(M/S DESTAGE FREQ)
Value:
Min. freq - Max. freq
(Par. 201 - 202)
Function:
Best efficiency staging off frequency can be calculated
for the cascade controller based on pump and system
curves to meet feedback requirements. Use the
MUSEC software program to determine the most
efficient staging off frequency for each pump.
MG.60.I3.02 - VLT is a registered Danfoss trademark
✭ Min.freq.
E
nter Motor Nameplate Data
Enter the nameplate data from each motor into
its associated drive in accordance with Quick
Menu items 001 - 006 in Chapter 6, VLT Driveand Cascade Control Card Setup.
D
ownload master drive programming data
Use the Master LCP to download parameter settings
into the slave drives in accordance with procedures
in Extended Menu parameter 004, LCP Copy.
The Extended Menu is accessed by pressing the
[EXTEND. MENU] key on the LCP keypad.
49
Cascade Controller Option
Extended Menu Par. 004 LCP Copy
(LCP COPY)
Value:
✭No copying (NO COPY)
Upload all parameters
(UPLOAD ALL PARAMET.)
Download all parameters
(DOWNLOAD ALL PARAM.)
Download power-independent parameters
(DOWNLOAD SIZE INDEP.)
Function:
This parameter is used to copy all parameter setups to
or from the Local Control Panel (LCP) keypad. It can
be used to store a backup copy of all parameters in the
LCP or to copy all setups from one drive to another.
Description of choice:
Select Upload all parameters to copy all parameter
values from the drive to the LCP.
Select Download all parameters to copy all
parameter values from the LCP to the drive on
which the keypad is mounted.
Select Download power-independent parameters
if only the power-independent parameters are
to be downloaded. This allows the parameters
from one drive to be easily copied to another
drive of a different size. Settings in parameters
102, 103, 104, 105, 106, 215, 221, and 222 are
not downloaded using this function.
NB!:
Copying is only possible when drive is stopped.
Alternate programming:
■
ump/system data for MUSEC unavailable:
P
In cases where the pump or system data points are
not known, the best efficiency staging and destaging
frequencies are difficult to calculate. Operation
of the system is possible with an approximation
of the best efficiency function.
1. Set staging on frequency in Quick Menu item
33 (parameter 739, Master/Slave stagingon frequency), to the maximum frequency
set in Quick Menu item 08 (parameter 202,
Output frequency high limit).
2. For an approximation of best efficiency, set
the destaging frequences in Quick Menu item
34 (parameter 740, Master/Slave stagingoff frequency), to half of the frequency set
between Quick Menu item 08 (parameter 202)
[0]
[1]
[2]
[3]
and Quick Menu item 07 (parameter 201,
Output frequency low limit).
A
lternate Feedback Programming :
In water supply systems, it is often impractical to
placeapressuresensoratthefarendofthesystem.
In HVAC and other applications, however, it is often
possible to place the pressure sensor(s) at the farthest
significant load and measure actual pressure in the
system. In these cases, the cascade option can
use the drive’s PID controller to respond to system
changes as programmed. Pumps or fans are staged
on and off in response to the system feedback signal.
The most common setup for feedback response
th a single transmitter located at the farthest
is wi
significant load in the system. Programming the
cascade controller option in this manner is described
ow. It is also possible for the PID to accept
bel
two feedback signals, making two-zone regulation
available. For two feedback control, and for additional
ting options, see the VLT Operating Instructions.
set
Setup for feedback response is with a single
transmitter located at the farthest significant load in
the system requires programming parameter 417,
Feedback Function, and parameter 418, Setpoint 1.
Parameter 417, Feedback Function, is only accessible
through the Extended Menu. The Extended Menu
is accessed by pressing the [EXTEND. MENU] key
on the drive control panel. Parameter 418 may
be accessed through either the Extended Menu
or as item 28 in the Quick Menu.
xtended Menu Par. 417 Feedback Function
E
(2 FEEDBACK, CALC.)
Value:
Minimum(MINIMUM)
Maximum (MAXIMUM)
Sum (SUM)
Difference (DIFFERENCE)
Average (AVERAGE)
Two-zone minimum (2 ZONE MIN)
Two-zone maximum (2 ZONE MAX)
✭Virtual Control Curve (VIRTUAL CTRL CURVE)
Feedback 1 Only (FEEDBACK 1 ONLY)
Feedback 2 Only (FEEDBACK 2 ONLY)
Function:
This parameter sets the calculation method whenever
a system feedback signal is used, or when two
feedback signals (Setpoint 1 and Setpoint 2) are used.
Description of choice:
Select the feedback calculation method required.
Maximum uses Setpoint 1 as the maximum
50
MG.60.I3.02 - VLT is a registered Danfoss trademark
reference signal for control. See the VLT OperatingManual for additional information.
Quick Menu 028 Par. 418 Setpoint 1
(SETPOINT 1)
Value:
Feedback Min. to Feedback Max.
Function:
Setpoint 1 is used to provide the setpoint reference
for one setpoint PID control or for the setpoint for
zone 1 in two setpoint PID control.
Description of choice:
Set the required value the system is to maintain
during normal operation. The value must be between
the minimum and maximum values set in Quick
Menu items 14 and 15 (parameter 413, MinimumFeedback, and parameter 414, Maximum Feedback).
Setpoint 2, Quick Menu item 29, is not used in
one feedback signal applications.
✭ 0.000
Cascade Controller Option
Control Setup
Master/Slave Cascade
MG.60.I3.02 - VLT is a registered Danfoss trademark
51
System Optimisation
■
System start up and final adjustments
■
After Master drive and slave programming is
complete, and after all system safety procedures
have been ensured and the system is operational,
final adjustments can be made to reach maximum
efficiency for drive and cascade controller operation.
Final adjustments involves the following:
a. Setting the best efficiency frequency in the cascade
controller for staging and destaging pumps and fans
b. Optimization of the process regulator
Best efficiency frequency
■
Quick Menu 036 Par. 422 PID start-up frequency
(PID START VALUE)
Value:
f
MIN-fMAX
(parameters 201 and 202)
Cascade Controller Option
✭ 0Hz
Function:
Each time the drive is given a start command, the start
up frequency is the speed the drive accelerates to
before PID control is activated. The drive will follow the
acceleration ramp when a start signal is received as if
in open loop. When the programmed start frequency
is reached, it will change to closed loop operation.
ription of choice:
Desc
Set the required start frequency. A setting near the
operating speed will enable the system to stabilize
more quickly. For pump applications, set this high
enough to ensure flow from the pump.
Quick Menu 037 Par. 427 PID lowpass filter time
(PID FILTER TIME)
Value:
0.01 - 10.00
Function:
Noise on the feedback signal can be reduced
with the lowpass filter.
✭ 1.00
The PID controller will then only respond
to changes in the feedback signal whose
frequency is less than 1.6 Hz.
Description of choice:
Select the desired time constant (t). The cut off
p
frequency equals
of 0.1 s is programmed, the cut off frequency for
the lowpass filter will be 1/[2
52
t. For example, if a time constant
p
(.1)] = 1.6 Hz.
MG.60.I3.02 - VLT is a registered Danfoss trademark
Optimization of the process regulator
■
Quick Menu 038 Par. 423 PID proportional gain
(PID PROP. GAIN)
Value:
0.00 - 10.00
Function:
Determines how fast the system responds
to a change in feedback.
Description of choice:
Quick regulation is obtained by a high gain, but
if the ga
unstable. See Optimization of the Process Regulator
for information on proper adjustment.
in is too high, the process may become
Quick Menu 039 Par. 424 PID integration time
(PID INTEGR.TIME)
Value:
0.01 - 9999.00 sec. (OFF)
✭ 0.01
✭ OFF
Cascade Controller Option
PID equation:
The VLT PID controller operates in accordance
to the following equation:
PID out = P[e(t) + 1/ l f e(t) dt] + D e(t)/dt
Function:
Theintegratoraddstheerrorsignalovertimeand
uses this to correct the speed of the drive. The
integration time is the time needed by the integrator
to have the same effect as the proportional gain.
Description of choice:
Fast regulation is obtained by setting a short
integration time. However, if this time is too short,
the pro
See Optimization of the Process Regulator for
information on p roper adjustment.
P
The process regulator is set by Quick Menu items
38 and 39 (parameters 423 and 424). To optimize
the proportional gain and integration time, in most
processes, this can be done as follows:
1. Start
2. Set parameter 423, PID Proportional Gain,to0.3
3. Set p
cess will overcorrect and become unstable.
rocedure for Optimization of the Process Regulator
the motor.
and increase it until the feedback signal becomes
able. Then reduce the value until the feedback
unst
signal has stabilized. Now lower the proportional
gain by about half (40% to 60%).
arameter 424, PID Integration Time,to20
seconds and reduce the value until the feedback
signal becomes unstable. Increase the integration
until the feedback signal stabilizes. Now
time
increase the integration time from 15% to 50%.
System Optimisation
Starting and stopping the drive will produce the
necessary error signal in the process to set the PID.
MG.60.I3.02 - VLT is a registered Danfoss trademark
53
Feedback Transmitter W iring
■
Connecting feedback transmitters
■
Terminal 12 and 13 of the VLT provide access to a
24 VDC, 200 mA power supply. This can be used
to power remote transmitters, so an external power
supply is generally not needed. The diagrams below
show how to wire two- and three-wire transmitters.
ingle 4 - 20 mA feedback transmitter connection:
S
Programming:
ParameterParameterParameter
NumberDescriptionValue
415REF./FDBK UNITProcess unit
413MIN. FEEDBACKTransmitter low limit
414MAX. FEEDBACKTransmitter high limit
308AI [V] 53 FUNCT.NO OPERATION
311AI [V] 54 FUNCT.NO OPERATION
314AI [mA] 60 FUNCTFEEDBACK
315AI 60 SCALE LOW4 mA
316AI 60 SCALE HIGH20 mA
Cascade Controller Option
Single 0 - 10 V feedback transmitter connection:
Programming:
ParameterParameterParamet er
NumberDescriptionValue
415REF./FDBK UNITProcess unit
413MIN. FEEDBACKTransmitter low limit
414MAX. FEEDBACKTransmitter high limit
308AI [V] 53 FUNCT.FEEDBACK
309AI 53 SCALE LOW0 V
310AI 53 SCALE HIGH10 V
314AI [mA] 60 FUNCTNO FUNCTION
Two 0 - 10 V feedback transmitter connections:
When two feedback signals are used with the
VLT, both signals must be voltage signals. Both
transmitters must also have the same range.
54
MG.60.I3.02 - VLT is a registered Danfoss trademark
Two 4 - 20 mA feedback transmitters connection:
When two feedback signals are used, the VLT requires
that they both be connected to its analog voltage
inputs, terminals 53 and 54. Transmitters that produce
a current signal can be used by adding two resistors.
Two feedback signals and two setpoints:
Similar to two feedback signals and one setpoint, the
need fo
r two feedback signals with two setpoints is
frequently encountered. Whenever two critical zones
do not have the same setpoint value, two feedback
wo setpoint control is required. Many pumping
with t
systems require the monitoring and control of two
loads that differ in size and pressure drop. Or this
can be
effective when controlling different temperature
zones in cooling or heating applications.
If the transmitter is capable of producing 10V at 20
mA, the value of the resistor to use is:
The input scaling of the VLT analog inputs in this
case would have to be 2 - 10 Volt.
Programming:
ParameterParameterParameter
NumberDescriptionValue
415Ref./FD BK UNITProcess unit
413MIN . FEEDBACKTransmitter low limit
414MAX. FEEDBACKTransmitter high limit
417FEE D BACK CALC.Desired operation
308AI [V] 53 FUNCT.FEEDBACK
309AI 53 SCA LE LOW2V
310AI 53 SCALE HIGH10V
311AI [54] 54 FUNCT.FE EDBACK
312AI 54 SCA LE LOW2V
313AI 54 SCALE HIGH10V
314AI [mA] 60 FUNCT.NO OPERATION
To enable this setup, the feedback function in
parameter 417, Feedback Function, is selected. When
selecting 2-zone Minimum in parameter 417, the drive
will regulate the system so the feedbacks are equal to
or greater than their associated setpoints. If 2-zoneMaximum is selected, the feedbacks will be equal
to or less than their associated setpoints.
Feedback 1 is associated with Setpoint 1 and
Feedback 2 is associated with Setpoint 2. The two
independent groupings are continuously monitored
to satisfy both zones requirements.
Transmitter connection to the VLT:
The transmitters are connected to the VLT in the
same way as shown above with 1 setpoint and 2
feedbacks. The feedback connected to terminal 53
is assigned to setpoint 1 and the one connected to
terminal 54 to setpoint 2. Both transmitters must
have the same output signal and range.
P
rogramming example for 2 feedback and
2 setpoint controls:
Wiring
Feedback Transmitter
MG.60.I3.02 - VLT is a registered Danfoss trademark
55
Transmitter ratings:
Supply: 15 - 30 VDC
Output: 0 - 10 V
Range: 0 - 100 Pa
The VLT is programmed to match its input to follow
the specification of the transmitter:
The reference range is generally set to equal the
range of the transmitter. In this way, the setpoint
(reference) can be set to any value that the transmitter
can produce. If required, the reference range can be
set to a range that is narrower than the transmitters
range, but it cannot be set to a wider range.
MG.60.I3.02 - VLT is a registered Danfoss trademark
57
Service parameters
■
Cascade Controller Option
Display information
■
Parameters 724 through 738 provide operational
information including the number of hours run, cycles,
and the state of the relay for each pump.
Par. 724 - 727 Pump-on time
(PUMP x ON TIME)
Parameter numberPump number
724Pump 2
725Pump 3
726Pump 4
727Pump 5
Value:
h0 - 130000
Function:
The relay timer accumulates the hours (h) the
pump has run (the relay switched on). The counter
is updated 10 times per hour which means that
cycles less than 6 minutes are not registered.
The hours can be reset to zero when a pump
is replaced since the cascade controller uses
parameter 736, Relay On Time, to determine
cycling patterns.
Par. 728 - 731 Pump cycles
(PUMP x CYCLES)
Parameter numberPump number
728Pump 2
729Pump 3
730Pump 4
731Pump 5
Value:
No.0 - 130000
Function:
The cascade controller counts the number (No.)
of times each relay (pump) is switched on. The
cycle c
ounter can be reset to zero when a pump
is replaced.
Par. 737 Relay cycles
(RELAY CYCLES)
Value:
No.0 - 130000
Function:
The relay timer accumulates the number (No.) of
each relay has been switched on and is used
times
by the cascade controller to determine the cycling
pattern. This counter cannot be reset.
Par. 738 Calculated intermediate setpoint
(SETPOINTS HM 1 - 7)
Value:
(set by Par. 415)sp 1 - sp 2
Function:
The intermediate setpoint is used internally by
the cascade controller to calculate the system
setpoint. This parameter displays the setpoint for
information. Setpoint data is entered in parameters
418, Setpoint 1, and 419, Setpoint 2.
Par. 736 Relay-on time
(RELAY ON TIME)
Value:
h0 - 130000
Function:
The relay timer accumulates the hours (h) each
relay has been switched on and is used by the
cascade controller to determine the cycling pattern.
This counter cannot be reset. A new pump
will not compensate for older pumps. The new
pump will cycle in regular rotation.
58
MG.60.I3.02 - VLT is a registered Danfoss trademark
Relay status
■
The display panel on the VLT allows reading
the sta
Press the [DISPLAY MODE] key. Use the [+] and [-]
keys to scroll through the list to RELAY STATUS. The
relay status readout consists of 8 binary digits. The
first digit (starting from left) indicates the status of
Relay 01 which is located in the power section of the
VLT. The second digit i s Relay 02 which is located
on the VLT control card. Digits 3 - 6 indicate the
four relays of the cascade controller, relays 06, 07,
08 and 09 which are located on the option board.
Digits 7-8 are reserved for future use.
The r
to see how many fixed speed or slave
pumps are in operation.
tus of the relays.
eadout c an be very useful during commissioning
RELAY STATUS
1001010010010100
10010100
1001010010010100
SETUP
1
Cascade Controller Option
175ZA690.10
AUTO REMOTE RUNNING
Value:
Relay open[0]
Relay closed[1]
NB!:
For readout via serial communication,
parameter 537 must be used.
Bit 7 = Relay 01,
Bit 6 = Relay 02,
Bits 5-2 = Relays 06 - 09.
Service parameters
MG.60.I3.02 - VLT is a registered Danfoss trademark
59
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.