Danfoss Calculation standards for safety relief valves User guide

Danfoss Calculation standards for safety relief valves User guide

Calculation standards for safety relief valves

In Coolselector®2

Niels P. Vestergaard & Morten Juel Skovrup

2019-02-21

Version 1.00

1 Introduction

Safety valves can be calculated and selected in Coolselector®2 according to either EN 13136 or ISO 5149.

In general, EN 13136 describes a more complete calculation and selection method than ISO 5149. Whether to use one or the other, is often a matter of local legislation or customer requirements, but it is in any case important to understand the differences between the two standards.

The page below describe the most important differences between the standards, but you should refer to the latest version of the standards for a complete overview.

Calculation standards for safety relief valves

2 EN 13136

Calculation of required valve capacity

Vessel heat load:

Assumes a constant heat flow acting on the total external surface of the

 

vessel. The heat of evaporation is dependent on the actual refrigerant

 

and pressure.

Compressor overflow valve:

Included in EN 13136.

Trapped liquid:

Included in EN 13136.

Calculation of selected valve capacity

Based on valve characteristics (rated flow area & discharge coefficient) and calculated flow with actual refrigerant and refrigerant properties.

Calculation of inlet and outlet pipe lines

Inlet pressure drop calculation: Required (maximum allowed pressure drop is 3% of relief pressure for standard safety valves). Changeover valve is included in calculation.

Outlet pressure drop calculation: Required (maximum allowed pressure drop is 10% of relief pressure for standard safety valves).

3 ISO 5149

Calculation of required valve capacity

Vessel heat load:

Assumes a constant heat flow acting proportional to the shell area of the

 

vessel (not including end caps). Using the area and a factor f depending

 

on the refrigerant, the corresponding required mass flow of air through

 

the safety relief valve can be calculated. The factor f is constant in the

 

whole application range.

Compressor overflow valve:

Not included in ISO 5149 (but EN 13136 is mentioned as possible

 

calculation method in notes).

Trapped liquid:

Not included in ISO 5149 (but EN 13136 is mentioned as possible

 

calculation method in notes).

Calculation of selected valve capacity

Rated air capacity stamped on the valve (in SCFM or kg/s).

Calculation of inlet and outlet pipe lines

Inlet pressure drop calculation: Not included in ISO 5149 (neither pipes and fittings nor changeover valve).

Outlet pressure drop calculation: Required. But described procedure is not consistent in current version of the standard (ISO 5149-2:2014), and calculation is therefore not included in Coolselector®2.