Danfoss C118L-EZ Data sheet

Fact sheet
C118 L- E Z Evaporator Micro Plate Heat Exchanger
21%
lower hold-up volume enables signicant reduction in refrigerant charge
C118L-EZ Evaporator
Danf already on order pro All trademarks in this material are property of the respec
Micro Plate Heat Exchanger
92
[3.6” ]
Introduction
Key features
Technical data
n = number of plates
Standard materials
Standard connections
Q4
Q1
613
[24.1” ]
Q3 Q2
186
[7. 3”]
The C118L-EZ is an evaporator optimized for R410A for use in high-eciency chillers with capacities of 70-250 kW. The Z-pattern channel plate technology pushes the performance of heat exchangers to the limits by fully mixing the liquid and gas refrig­erant through a “zigzag” ow, which increases the heat transfer coecient. At the same time, inheriting from the dimple features, C118L-EZ reduces the water side pressure drop and the amount of material used. In the reversible mode of the chiller as a condenser, C118L-EZ also has outstanding performance. To meet demands for higher seasonal eciency, the C118L-EZ is designed to work eciently and increase comfort in modern buildings with­out increasing the carbon footprint. Helping chillers perform more eciently, it reduces both energy costs and environmental impact. The low hold-up volume reduces the system refrigerant charge and oers valuable savings.
- Improved heat transfer - equals higher eciency chillers
- Reduced water side pressure drop - equals higher eciency chillers
- Minimal hold-up volume - equals less refrigerant charge
- Smaller footprint - enables more compact chillers
- High heat transfer and minimal refrigerant charge - equals a reduced CO₂ footprint
Min. working temperature: -196°C Max. working temperature: 200°C Max. working pressure: 45 bar (refrigerant side) / 25 bar (water side)* Hold-up volume: Q1-Q2/ Q3-Q4 (l): 0.193×n/2 / 0.143×(n-2)/2 Weight (kg): 5.95+0.29xn Max. no. of plates: 250
* A lower pressure version (30 bar) also available
Cover plates: AISI 304L Connections: AISI 304L
Other material combinations are available on request. Please contact your Danfoss sales representative for more information.
Standard connections as below are optimzed for this product as an evaporator in chiller systems. For other connections, please contact your Danfoss representative, (Internal threaded, R thread (BSPT), NPT and Victaulic are also available).
Q3 (Refrigerant inlet): Soldering 3/8”, 1/2”, 5/8”, 3/4”, 7/8” or 1 1/8” Q4 (Refrigerant outlet): Soldering 1/2”, 5/8”, 3/4” , 7/8”, 1 1/8”, 1 3/8”, 1 1/2”, 2” or 2.5” Q1-Q2 (Water side): External threaded G 1/2”, G 3/4”, G 1”, G 1 1/4”, G 1 1/2”, G 2” or G 2.5”
519
[20.4”]
15+1.94*NoP [0.59+0.076*NoP]
Plates: AISI 316L Brazing ller: Pure copper
H4H1
H2 H3
Third-party approvals
Accessories – stud bolts
Corresponding condensers
oss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
DKQB. PD.310.O2.02
Europe: Pressure Equipment Directive (PED). America: Underwriters Laboratory Inc (UL). The third-party approvals stated are standard for all our products. For details of other existing approvals or to discuss how we can meet your local needs, please contact your Danfoss representative.
Stud bolts and feet on front and/or back cover plates for mounting support are available upon request. Contact your Danfoss sales repre­sentative for further information.
A corresponding Micro Plate heat exchanger for condenser duties (C118 L-C)) is also available.
vided that such alterations can be made without subsequential changes being necessary eady agreed.
tive companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
© Danfoss | DSC (im) | 2017.03