Danfoss C118L-EZ, C118L-EZ-F Data sheet

Data Sheet

Micro Plate Heat Exchanger

Type C118L-EZ and C118L-EZ-F

For more e€cient Chillers

21% lower hold-up volume enables significant reduction in refrigerant charge.

The C118L-EZ and the C118L-EZ-F are evaporators optimized for high density refrigerants like the R410A and its replacement R454B and R32 for use in high-e€ciency chillers with capacities of 70-250 kW.

The Z-pattern channel plate technology pushes the performance of heat exchangers to the limits by fully mixing the liquid and gas refrigerant through a “zigzag” flow, which increases the heat transfer coe€cient. At the same time, inheriting from the dimple features, C118L-EZ reduces the water side pressure drop and the amount of material used. In the reversible mode of the chiller as a condenser, C118L-EZ also has outstanding performance.

To meet demands for higher seasonal e€ciency, the C118L-EZ is designed to work e€ciently and increase comfort in modern buildings without increasing the carbon footprint. Helping chillers perform more e€ciently, it reduces both energy costs and environmental impact. The low hold-up volume reduces the system refrigerant charge and offers valuable savings.

Features:

• Improved heat transfer - equals higher e€ciency chillers

• Reduced water side pressure drop – equals higher e€ciency chillers

• Minimal hold-up volume - equals less refrigerant charge

• Smaller footprint - enables more compact chillers

• High heat transfer and minimal refrigerant charge - equals a reduced CO footprint

AI353341419461en-000201

Micro plate heat exchanger, type C118L-EZ and C118L-EZ-F

Portfolio overview

C118L-EZ: Evaporator optimized for R410A, R452B and R454B

C118-EZ: Evaporator for medium density refrigerants PS: 30bar

C118L-EZ -F: Evaporator optimized for R32

Applications

The C118L-EZ and C118L-EZ-F are single circuit evaporators speciˆcally designed for high e€cient chiller systems dedicated to comfort applications, cooling-industrial process, data centers. The evaporators are design to operate also in reversable systems in condenser mode, in co or counter current flow conˆguration.

The models are characterized by different distributor system the make the evaporator optimized for the highdensity refrigerants. Even if equipped with distributor device, the C118L-EZ and C118L-EZ-F can run properly in condenser mode.

Media

Refrigerants

R410A, R32, R452B, R454B

For other refrigerants please contact your Danfoss Sales representative.

Performance

Model

Refrigerant

Evaporating temperature [°C]

Max capacity(1) [kW]

 

 

5

115

 

R410A

4.5

155

C118L-EZ

 

4

195

 

5

150

 

 

 

R454B / R452B

 

 

 

4.5

190

 

 

4

225

C118L-EZ-F

R32

4.5

145

4

250

 

 

 

 

 

 

Max water flow (@6 m/s)

 

49 m3/h

 

 

 

 

 

(1) EWT/LWT: 12/7 °C; Tliq.:43 °C, Sh: 5K; max N °P: 250

© Danfoss | Climate Solutions | 2021.02

AI353341419461en-000201 | 2

Danfoss C118L-EZ, C118L-EZ-F Data sheet

Micro plate heat exchanger, type C118L-EZ and C118L-EZ-F

Product specification

Dimensions

Figure 1: Dimensions

186 [7, 3”]

92 [3, 6”]

<![if ! IE]>

<![endif]>665 [26, 2”]

<![if ! IE]>

<![endif]>613 [24, 1”]

<![if ! IE]>

<![endif]>519 [20, 4”]

98 [3, 9”]

250 [9, 8”]

16+1,94XN ºP [0,63+0,076XN ºP

H1 H4

H2 H3

90 [3, 5”]

Operating conditions

Preconditions:

N = number of plates

Max number of plates: 250

Pressure and temperature data*:

Min. working temperature: -196 °C (-320 °F) Max. working temperature: 200 °C (390 °F)

Max. working pressure: 49 bar (710psi) refrigerant side** / 25 bar (362psi) water side *For details, refer to the “Third party Approvals” chapter

** A lower pressure version (30bar) also available

Weight

C118L-EZ(-F): 7.94 + 0.29 x N[kg] // 17.5 + 0.64 x N[lb]

C118-EZ: 5.95 + 0.29 x N[kg] // 13.12 + 0.64 x N[lb]

N:Number of Plate

Material specification

Table 1: Standard materials

Item

Material

Specification

Cover plates

Stainless steel

AISI 304L

Plates

Stainless steel

AISI 316L

Connections

Stainless steel

AISI 304L

Brazing ˆller

Pure copper

Cu

 

 

 

Other material combinations are available on request. Please contact your Danfoss sales representative for more information.

© Danfoss | Climate Solutions | 2021.02

AI353341419461en-000201 | 3