Danfoss C118L-EZ, C118L-EZ-F Data sheet

Data Sheet
Micro Plate Heat Exchanger Type C118L-EZ and C118L-EZ-F
For more ecient Chillers
21% lower hold-up volume enables signicant reduction in refrigerant charge.
The C118L-EZ and the C118L-EZ-F are evaporators optimized for high density refrigerants like the R410A and its replacement R454B and R32 for use in high-eciency chillers with capacities of 70-250 kW.
The Z-pattern channel plate technology pushes the performance of heat exchangers to the limits by fully mixing the liquid and gas refrigerant through a “zigzag” ow, which increases the heat transfer coecient. At the same time, inheriting from the dimple features, C118L-EZ reduces the water side pressure drop and the amount of material used. In the reversible mode of the chiller as a condenser, C118L-EZ also has outstanding performance.
To meet demands for higher seasonal
eciency, the C118L-EZ is designed to work eciently and increase comfort in modern
buildings without increasing the carbon footprint. Helping chillers perform more eciently, it reduces both energy costs and environmental impact. The low hold-up volume reduces the system refrigerant charge and oers valuable savings.
Features:
• Improved heat transfer - equals higher eciency chillers
• Reduced water side pressure drop – equals higher eciency chillers
• Minimal hold-up volume - equals less refrigerant charge
• Smaller footprint - enables more compact chillers
• High heat transfer and minimal refrigerant charge - equals a reduced CO₂ footprint
AI353341419461en-000201
Model
Refrigerant
Evaporating temperature [°C]
Max capacity
(1)
[kW]
C118L-EZ
R410A
5
115
4.5
1554195
R454B / R452B
5
150
4.5
1904225
C118L-EZ-F
R32
4.5
1454250
Max water
ow (@6 m/s)
49 m3/h
Micro plate heat exchanger, type C118L-EZ and C118L-EZ-F
Portfolio overview
C118L-EZ: Evaporator optimized for R410A, R452B and R454B C118-EZ: Evaporator for medium density refrigerants PS: 30bar C118L-EZ -F: Evaporator optimized for R32
Applications
The C118L-EZ and C118L-EZ-F are single circuit evaporators specically designed for high ecient chiller systems dedicated to comfort applications, cooling-industrial process, data centers. The evaporators are design to operate also in reversable systems in condenser mode, in co or counter current ow conguration.
The models are characterized by dierent distributor system the make the evaporator optimized for the high­density refrigerants. Even if equipped with distributor device, the C118L-EZ and C118L-EZ-F can run properly in condenser mode.
Media
Refrigerants
R410A, R32, R452B, R454B For other refrigerants please contact your Danfoss Sales representative.
Performance
(1)
(1)
EWT/LWT: 12/7 °C; Tliq.:43 °C, Sh: 5K; max N °P: 250
EWT/LWT: 12/7 °C; Tliq.:43 °C, Sh: 5K; max N °P: 250
© Danfoss | Climate Solutions | 2021.02 AI353341419461en-000201 | 2
665 [26, 2”]
613 [24, 1”]
186 [7, 3”]
92 [3, 6”]
98 [3, 9”]
90 [3, 5”]
250 [9, 8”]
519 [20, 4”]
16+1,94xN ºP
[0,63+0,076xN ºP
H1
H2
H3
H4
Item
Material
Specication
Cover plates
Stainless steel
AISI 304L
Plates
Stainless steel
AISI 316L
Connections
Stainless steel
AISI 304L
Brazing
ller
Pure copper
Cu
Micro plate heat exchanger, type C118L-EZ and C118L-EZ-F
Product specication
Dimensions
Figure 1: Dimensions
Operating conditions
Preconditions:
N = number of plates Max number of plates: 250
Pressure and temperature data*:
Min. working temperature: -196 °C (-320 °F) Max. working temperature: 200 °C (390 °F) Max. working pressure: 49 bar (710psi) refrigerant side** / 25 bar (362psi) water side *For details, refer to the “Third party Approvals” chapter ** A lower pressure version (30bar) also available
Weight
C118L-EZ(-F): 7.94 + 0.29 x N[kg] // 17.5 + 0.64 x N[lb] C118-EZ: 5.95 + 0.29 x N[kg] // 13.12 + 0.64 x N[lb] N:Number of Plate
Material specication
Table 1: Standard materials
Other material combinations are available on request. Please contact your Danfoss sales representative for more information.
© Danfoss | Climate Solutions | 2021.02 AI353341419461en-000201 | 3