Danfoss BD1.4F-VSD Data sheet

BD1.4F-VSD

Direct Current Compressor R134a

12-24V

General

Code number (without electronic unit)

 

109Z0200

Electronic unit

 

101N2100, 30 pcs: 101N2101

Approvals

 

Compressors on pallet

 

180

Application

 

 

Application

 

LBP/MBP

Evaporating temperature

°C

-30 to 0

Voltage range

VDC

12 (9.6 - 17) / 24 (19 - 34)

Max. condensing temperature continuous (short)

°C

60 (70)

Max. winding temperature continuous (short)

°C

125 (135)

Cooling requirements

Application

LBP

MBP

HBP

32°C

S

S

38°C

S

S

43°C

S

S

Remarks on application:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S

= Static cooling normally sufficient

O

= Oil cooling

F1

= Fan cooling 1.5 m/s

 

 

 

 

(compressor compartment temperature

F2

equal to ambient temperature)

= Fan cooling 3.0 m/s necessary

SG

= Suction gas cooling normally sufficent

= not applicable in this area

Motor

Motor type

 

permanet magnet, brushless DC

Speed

rpm

variable speed

Resistance, all 3 windings (25°C)

50

Design

 

 

Displacement

cm3

1.41

Oil quantity (type)

cm3

75 (polyolester)

Maximum refrigerant charge

g

150

Free gas volume in compressor

cm3

500

Weight - Compressor/Electronic unit

kg

2.1/0.17

Standard battery protection settings (refer to 101N2100 Instructions for optional settings)

Voltage (0.1 steps)

 

 

Min. value

Default

Max. value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12V

± 0.3V DC,

Cut out

VDC

 

9.6

10.4

17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

all values

Cut in diff.

VDC

 

0.5

1.3

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24V

± 0.3V DC,

Cut out

VDC

 

19

21.3

27

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

all values

Cut in diff.

VDC

 

0.5

1.3

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dimensions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

 

 

mm

A

 

96.25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

91.25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B1

 

81.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B2

 

38.50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Suction connector

location/I.D. mm | angle

C

 

6.2 | 15°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

material | comment

 

Cu-plated steel | Al cap

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Process connector

location/I.D. mm | angle

D

 

6.2 | 25°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

material | comment

 

Cu-plated steel | Al cap

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Discharge connector

location/I.D. mm | angle

E

 

5.0 | 15°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

material | comment

 

Cu-plated steel | Al cap

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connector tolerance

 

I.D. mm

 

±0.09, on 5.0 +0.12/+0.20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remarks

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

July 2012

DEHC.ED.100.W3.02

1/2

Danfoss BD1.4F-VSD Data sheet

Capacity (EN 12900 Household/CECOMAF)

 

12V DC, static cooling

 

watt

 

 

rpm \ °C

-30

 

 

-25

-23.3

 

-20

 

-15

 

-10

-6.7

 

-5

 

0

 

2,000

 

 

 

 

 

9.3

11.0

 

15.0

 

22.4

31.4

38.2

 

42.0

 

54.3

 

2,500

6.9

 

 

12.7

15.1

 

20.4

 

29.9

41.3

49.9

 

54.6

 

69.8

 

3,000

8.7

 

 

16.1

19.2

 

25.7

 

37.4

51.2

61.5

 

67.1

 

85.2

 

3,500

10.4

 

 

19.5

23.1

 

31.0

 

44.8

61.0

73.0

 

79.6

 

100.6

 

4,000

12.1

 

 

22.8

27.1

 

36.2

 

52.2

70.8

84.5

 

92.1

 

115.9

Capacity (ASHRAE LBP)

 

 

 

 

 

 

 

 

 

 

 

 

 

12V DC, static cooling

 

watt

 

 

rpm \ °C

-30

 

 

-25

-23.3

 

-20

 

-15

 

-10

-6.7

 

-5

 

0

 

2,000

 

 

 

 

 

11.6

13.8

 

18.7

 

27.9

39.1

47.6

 

52.4

 

67.7

 

2,500

8.6

 

 

15.8

18.8

 

25.3

 

37.1

51.3

61.9

 

67.8

 

86.8

 

3,000

11.0

 

 

20.2

23.9

 

32.0

 

46.5

63.6

76.4

 

83.5

 

106.0

 

3,500

13.1

 

 

24.3

28.8

 

38.5

 

55.6

75.7

90.6

 

98.8

 

124.9

 

4,000

15.4

 

 

28.6

33.9

 

45.1

 

64.9

88.0

105.0

 

114.3

 

144.0

Power consumption

 

 

 

 

 

 

 

 

 

 

 

 

 

12V DC, static cooling

 

watt

 

 

rpm \ °C

-30

 

 

-25

-23.3

 

-20

 

-15

 

-10

-6.7

 

-5

 

0

2,000

 

 

 

 

 

15.7

16.6

 

18.5

 

21.7

25.3

28.0

 

29.4

 

33.8

2,500

16.2

 

 

19.7

21.0

 

23.6

 

27.7

32.2

35.2

 

36.9

 

41.9

3,000

19.3

 

 

24.1

25.7

 

29.0

 

34.1

39.3

42.9

 

44.7

 

50.3

3,500

22.8

 

 

28.7

30.8

 

34.7

 

40.8

46.8

50.8

 

52.9

 

59.0

4,000

26.6

 

 

33.8

36.2

 

40.8

 

47.8

54.7

59.1

 

61.4

 

68.1

Current consumption (for 24V applications the following must be halfed)

 

A

 

 

rpm \ °C

-30

 

 

-25

-23.3

 

-20

 

-15

 

-10

-6.7

 

-5

 

0

 

2,000

 

 

 

 

 

1.25

1.33

 

1.48

 

1.74

2.02

2.22

 

2.32

 

2.65

 

2,500

1.25

 

 

1.53

1.63

 

1.83

 

2.15

2.48

2.72

 

2.84

 

3.22

 

3,000

1.49

 

 

1.84

1.96

 

2.20

 

2.59

2.98

3.25

 

3.40

 

3.82

 

3,500

1.77

 

 

2.19

2.34

 

2.63

 

3.07

3.53

3.84

 

4.00

 

4.47

 

4,000

2.08

 

 

2.58

2.75

 

3.08

 

3.59

4.10

4.45

 

4.63

 

5.16

COP (EN 12900 Household/CECOMAF)

 

 

 

 

 

 

12V DC, static cooling

 

W/W

 

 

rpm \ °C

-30

 

 

-25

-23.3

 

-20

 

-15

 

-10

-6.7

 

-5

 

0

 

2,000

 

 

 

 

 

0.59

0.66

 

0.81

 

1.03

1.24

1.37

 

1.43

 

1.60

 

2,500

0.43

 

 

0.64

0.72

 

0.86

 

1.08

1.29

1.42

 

1.48

 

1.67

 

3,000

0.45

 

 

0.67

0.74

 

0.89

 

1.10

1.30

1.43

 

1.50

 

1.69

 

3,500

0.46

 

 

0.68

0.75

 

0.89

 

1.10

1.30

1.44

 

1.51

 

1.70

 

4,000

0.45

 

 

0.68

0.75

 

0.89

 

1.09

1.30

1.43

 

1.50

 

1.70

COP (ASHRAE LBP)

 

 

 

 

 

 

 

 

 

 

 

 

 

12V DC, static cooling

 

W/W

 

 

rpm \ °C

-30

 

 

-25

-23.3

 

-20

 

-15

 

-10

-6.7

 

-5

 

0

2,000

 

 

 

 

 

0.74

0.83

 

1.01

 

1.29

1.55

1.71

 

1.79

 

2.01

2,500

0.54

 

 

0.80

0.89

 

1.07

 

1.34

1.60

1.76

 

1.84

 

2.08

3,000

0.57

 

 

0.84

0.93

 

1.11

 

1.37

1.62

1.79

 

1.87

 

2.11

 

3,500

0.58

 

 

0.85

0.94

 

1.11

 

1.36

1.62

1.79

 

1.87

 

2.12

 

 

4,000

0.58

 

 

0.85

0.94

 

1.11

 

1.36

1.61

1.78

 

1.87

 

2.12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operational errors (TOOL4COOL® or LED flashes)

Error code

Error type

or LED

Can be read out in the software TOOL4COOL®

flashes

6

Thermostat failure

 

(If the NTC thermistor is short-circuit or has no connection,

 

the electronic unit will enter manual mode).

5

Thermal cut-out of electronic unit

 

(If the refrigeration system has been too heavily loaded,

 

or if the ambient temperature is high, the electronic unit

 

will run too hot).

4

Minimum motor speed error

 

(If the refrigeration system is too heavily loaded, the

 

motor cannot maintain minimum speed at approximately

 

1,850 rpm).

3

Motor start error

 

(The rotor is blocked or the differential pressure in the

 

refrigeration system is too high (>5 bar)).

2

Fan over-current cut-out

 

(The fan loads the electronic unit with more than

 

0.65Apeak).

1

Battery protection cut-out

 

(The voltage is outside the cut-out setting).

Wire Dimensions DC

Size

Max. length*

Max. length*

Cross

AWG

12V operation

24V operation

section

 

 

 

 

 

[mm2]

[Gauge]

[m]

[ft.]

[m]

[ft.]

2.5

12

2.5

8

5

16

4

12

4

13

8

26

6

10

6

20

12

39

10

8

10

33

20

66

*Length between battery and electronic unit

Accessories for BD1.4F-VSD

 

Code number

Bolt joint for one compressor

Ø:16 mm

118-1917

Bolt joint in quantities

Ø:16 mm

118-1918

Snap-on in quantities

Ø:16 mm

118-1919

Terminal cover for electronic unit

 

105N9120

Automoblie fuse

12V: 15A

Not

DIN 7258

24V: 15A

deliverable

Main switch

min. 20A

from Secop

Test conditions

 

 

EN 12900

ASHRAE

 

 

 

 

 

 

 

CECOMAF

LBP

Condensing temperature

 

 

55°C

54.4°C

Ambient temperature

 

 

32°C

32°C

Suction gas temperature

 

 

32°C

32°C

Liquid temperature

no subcooling

32°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

refer to 101N2100 Instructions for details

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.

All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

2/2

Designed by Secop for Danfoss - DEHC.ED.100.W3.02