DescriptionAVTQ prevents high temperatures in the heat
exchanger when no hot water is tapped by
rapidly shutting off the heat supply (e.g. hot
district heating water). AVTQ can be used with
most plate heat exchangers. However, the heat
exchanger manufacturer should be contacted to
ensure that the chosen heat exchanger has been
approved for use with the AVTQ.
• Pressure-controlled opening/closing on
start/stop tapping.
• Infinite adjustment of operating temperature.
AVTQ controller consist of a thermostatic
actuator, diaphragm element, main valve
and pilot valve. Thermostatic actuator with
diaphragm element and main valve are
installed on the district heating (primary) side.
The diaphragm element is, via impulse tubes,
connected to the pilot valve on the domestic hot
water (secondary) side.
Main data:
• DN 15
• kVS 1.6
• PN 16 - Main valve
AVTQ is a self-acting flow-compensated
temperature controller primarily for use in
district heating systems with plate heat
exchangers for instantaneous hot water
production. It closes on rising sensor
temperature.
It has permanent no-load (idle) temperature
setting on about 40 °C which is offset by a
pilot valve using flow-compensation principle
during tapping. Tapping temperature can be set
individually.
PN 10 - Diaphragm element and pilot valve
• Suitable for domestic hot water (DHW)
production in range of 45 … 60 °C
• Permanent no-load (idle) temperature
(approx. 40 °C)
• Temperature (primary):
- Circulation water / glycolic water up to 30 %:
2 … 100 °C
• Connections:
- Ext. thread (weld-on and thread tailpieces)
• Return mounting
Ordering
Example:
Flow-compensated temperature
controller, DN 15, kVS 1.6, PN 16,
setting range 45 … 60 °C,
t
The controlle r package (code 003 L7 015)
does not inclu de copper impulse tubes .
Two standard Ø6 × 0.8 mm copp er
tubes, of the l enght required for the
particula r application, must be obta ined
separately by th e customer in order to
instal the produ ct. The compression
fittings f or mounting the tubes onto the
controller are p rovided in the package.
Data sheet Flow-compensated temperature controller AVTQ DN 15
Application principle
The controller AVTQ must be
installed in the return pipeline
only.
Design
1. Thermostatic actuator with
sensor stuffing box
2. Pressure spindle
3. Diaphragm housing
stuffing box
4. Nut
5. Diaphragm housing
6. Diaphragm spindle
7. Control diaphragm
8. Compression connection for
impulse tube
9. Intermediate ring
10. Nameplate
11. Main spring
12. Damping + teflon ring
13. Valve spindle
14. Valve ins ert
15. Pressure relief c ylinder
16. Valve body (main valve)
17. Handle for temperature setting
18. Spindle
19. Valve b ase
20. Spring retainer
21. Setting spring
22. Pressure equalizing hole
23. Valve cone
24. Valve body (pilot valve)
25. Compression connection for
impulse tube
26. Sealing bolt of sensor
stuffing box
27. Gasket of sensor stuf fing box
28. Housing of sensor stuffing box
When domestic hot water (DHW) is tapped, flow
through the pilot valve creates a pressure drop
(force in the diaphragm housing) which is used
to increase the temperature level from no-load
(idle) to set tapping temperature.
This temperature increase causes the main valve
to open for flow on the district heating side and
close when the temperature level again falls to
the no-load operating level. No-load operation
prevents the district heating line becoming cold.
Tapping temperature can be set individually.
AVTQ can be used with most types of plate heat
exchangers.
The AVTQ manufacturer should be contacted to
ensure:
- that the AVTQ is approved for use with the
chosen heat exchanger
- the correct material selection when
connection the heat exchangers
- the correct connection of one pass plate heat
exchangers; layer distribution might occur, i.e.
reduced comfort
The system functions optimal when the sensor
is installed right inside the heat exchanger
(see page 3). However, the sensor head should
be placed approx. 5 mm from the plate which
divides the primary and the secondary side of
the exchanger. If the sensor head is placed too
close to the dividing plate, the sensor might
measure the temperature of the plate and not
the temperature of the medium. For correct noload operation, thermal flow should be avoided
since hot water rises and increases the no-load
consumption.
Note: water velocity around the sensor must be in
accordance with the requirements for copper tube.
The temperature controller (main valve):
- must be installed in the return pipeline on
the district heating (primary) side of the heat
exchanger
- the diaphragm element can be turned in
any position in relation to the valve body so
that impulse tube can be connected in the
required direction
The pilot valve:
- must only be installed in the flow pipeline on
the secondary side of the heat exchanger
- in systems where it cannot be excluded that
drinking water is contaminated with fine dust
from time to time, it is recommended not to
mount the pilot valve with the impulse tube
connections downwards (fig.2) to avoid dirt
ingress in the impulse tubes and diaphragm
housing
The sensor can be installed in any position (fig.1)
It is strongly recommended that:
- the primary and secondary sides of the heat
exchanger should be flushed through before
the heating system is used the first time. In
addition the (+) and (–) side of the diaphragm
should be vented.
- dirt strainers with a mesh size of max. 0.6mm
should be installed in both, the cold tap
water pipeline ahead of the pilot valve and
in the flow pipeline from the district heating
network.
Data sheet Flow-compensated temperature controller AVTQ DN 15
()
86.0x42
86.0xP
[
]
SizingExample
Given data:
T1 = 65 °C
T3 = 50 °C
T4 = 10 °C
Q2 = 0.3, 0.6, 0.9 m3/h (300, 600, 900 l/h)
Primary Secondary
T1 - District heating water flow temperature
T3 - Hot water temperature
T4 - Cold water temperature
Q2 - Hot water service flow
District
heating
flow line
District
heating
return line
Fig. 4
The maximum heating power P
according to formula:
TxQ
p
max
p
max
∆
=
=
=
86.0
()
86.0
86.0
1050x900
−
=
TTxQ
−
43222
kW42
is calculated
max
Based on max. heating power heat exchanger
could be selected. Information about the cooling
across the primary side of heat exchanger
can be acquired either by contacting the
manufacturer of the heat exchanger or by using
the manufacturer’s dimensioning diagram.
In the example chosen cooling on primary side
(ΔT1) is 43 °C, 40 °C or 39 °C, the differential
pressure across the AVTQ main valve (Δpv) is
0.2 bar.
Hot water
C old water
Chosen AVTQ main valve has kvs 3.2 m3/h and
therefore is big enough. Values for flows of 300
and 600 l/h are calculated on the same way and
entered in the table.
Tab.1
Secondary flowPrimary flowCooling
W
(kW)
143002800.3943
286006000.8540
429009251.3139
Q
(l/h)
Q
2
(l/h)
k
1
v
(m3/h)
∆T
(°C)
1
They can be plotted on the diagram overleaf
(fig. 5) and connected. The temperature variation
can be read from the diagram as the difference
between the temperature lines intersected by
the curve
The primary flow Q1 can be calculated according
to formula:
max
Q
=
1
=
T
∆
1
h/l925Q1=
39
Using the above data, the needed capacity of the
main valve (kv) can be calculated:
Data sheet Flow-compensated temperature controller AVTQ DN 15
Sizing (continuous)
The pressure drop across the pilot valve can be
read from the diagram below.
Fig. 6 Pressure drop (Δp
) across pilot valve as a function of the setting value and secondary flow
pilot
Setting
The AVTQ controller can be used with plate heat
exchangers of up to 75 kW. As a result of the flow
compensation principle an actual dimensioning
of the valve is unnecessary, because the
valve will always adjust around the required
temperature without regard to the flow.
This means that if the controller is set to 50 °C
(this is done at 75% of max. tapping flow to
obtain optimum control), then this temperature
will be maintained whether or
not the actual
is 120 l/h, 900 l/h or more. Between 120 l/h and
900 l/h the temperature will vary approx. 4 °C.
Typical settings:
Minimum:
DesignationApplication valuesPilot valve setting
Flow temperature, primaryTp = 65 °C
Dierential pressure across the AVTQ main valve∆p = 0.5 bar
Hot water temperature, secondaryTs (hot) = 50 °C
Cold water temperature, secondaryTs (cold) = 10 °C
Secondary owQs = 800 l/h
3.0
Maximum:
DesignationApplication valuesPilot valve setting
Flow temperature, primaryTp = 100 °C
Dierential pressure across the AVTQ main valve∆p = 6.0 bar
Hot water temperature, secondaryTs (hot) = 50 °C
Cold water temperature, secondaryTs (cold) = 10 °C
Secondary owQs = 750 l/h
The values mentioned above are reference
values and therefore corrections of pilot valve
settings might be necessary in order to obtain
Other approx. setting values:
Tapping temperature = 50 °C
Tapping flow = 800 l/h
Danf
already on order pro
All trademarks in this material are property of the respec
Data sheet Flow-compensated temperature controller AVTQ DN 15
oss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
vided that such alterations can be made without subsequential changes being necessaryeady agreed.
8 | VD.LJ.A2.02
tive companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.