Danfoss AVTQ DN 15 Data sheet

Data sheet
Flow-compensated temperature controller
AVTQ DN 15
Description AVTQ prevents high temperatures in the heat
exchanger when no hot water is tapped by rapidly shutting off the heat supply (e.g. hot district heating water). AVTQ can be used with most plate heat exchangers. However, the heat exchanger manufacturer should be contacted to ensure that the chosen heat exchanger has been approved for use with the AVTQ.
• Pressure-controlled opening/closing on start/stop tapping.
• Infinite adjustment of operating temperature.
AVTQ controller consist of a thermostatic actuator, diaphragm element, main valve and pilot valve. Thermostatic actuator with diaphragm element and main valve are installed on the district heating (primary) side. The diaphragm element is, via impulse tubes, connected to the pilot valve on the domestic hot water (secondary) side.
Main data:
• DN 15
• kVS 1.6
• PN 16 - Main valve
AVTQ is a self-acting flow-compensated temperature controller primarily for use in district heating systems with plate heat exchangers for instantaneous hot water production. It closes on rising sensor temperature.
It has permanent no-load (idle) temperature setting on about 40 °C which is offset by a pilot valve using flow-compensation principle during tapping. Tapping temperature can be set individually.
PN 10 - Diaphragm element and pilot valve
• Suitable for domestic hot water (DHW) production in range of 45 … 60 °C
• Permanent no-load (idle) temperature (approx. 40 °C)
• Temperature (primary):
- Circulation water / glycolic water up to 30 %: 2 … 100 °C
• Connections:
- Ext. thread (weld-on and thread tailpieces)
• Return mounting
Ordering
Example: Flow-compensated temperature controller, DN 15, kVS 1.6, PN 16, setting range 45 … 60 °C, t
100 °C, ext. thread
max
- 1× AVTQ controlle r, 45 … 60 °C Code No: 00 3 L70 15
Option:
- 1× Weld-on tailpieces Code No: 003H690 8
The controlle r package (code 003 L7 015) does not inclu de copper impulse tubes . Two standard Ø6 × 0.8 mm copp er tubes, of the l enght required for the particula r application, must be obta ined separately by th e customer in order to instal the produ ct. The compression fittings f or mounting the tubes onto the controller are p rovided in the package.
© Danfoss | 2017.11
AVTQ controller
Picture
* Controller incl. gla nd and compression fitt ings for mounting on Ø6 × 0.8 mm co pper impulse tube (standard cop per impulse tube not
included in th e package).
DN
(mm)
15 1.6 G ¾ A
k
vs
(m3/h)
Main valve ISO 228/1 Pilot valve ISO 228/1
Connection
G 1 A
(DN 20)
Code No .*
003L7015
Accessories
Picture Type designation DN Connection Code No.
Weld-on tailpieces
External thread tailpieces
15
Conical ex t. thread
acc. to EN 10226-1
003H6908
R ½” 003H6902
VD.LJ.A2.02 | 1
Data sheet Flow-compensated temperature controller AVTQ DN 15
1
4
Ordering (continuous)
Technical data
Service kits
Picture Type designation Code No.
Gasket for diaphragm housing 003L 3154
Thermostatic actuator incl. sensor stuff ing box 003L7100
Compression fittings for Ø6 mm copper tube (4 ferrules and 4 nuts) 003 L7101
Pilot valve excl. compression fittings 003 L7108
Main valve incl. complete valve insert 00 3L7109
Diaphragm element excl. compression fittings 003 L7111
Sensor stuffing box incl. gasket
Nominal diameter DN 15
kVS value m3/h 1.6
Control ratio 100 : 1
Cavitation factor z ≥ 0.6
Leakage acc. to standard IEC 534 < 0.05 %
Nominal pressure
Max. differential pressure
Max. closing pressure 12
PN
bar
Medium
Medium pH Min. 7, max. 10
Medium temperature °C
Connections
valve Ext. thread
tailpieces Weld-on and external thread
Setting range Xs °C 45 … 60
Time constant T acc. to EN 14597 s 4
Max. adm. temperature at sensor °C 130
Max. water velocit y around the sensor m/s 1.5
Capillary tube length m 1
Materials
Valve body RG5, DIN 1705, W.no. 2.1096.01
Valve insert and valve cone
Valve seat, pressure relief cylinder CrNi steel, DIN 17440, W.no. 1.4404
Temperature controller
Valve spindle CrNi steel, DIN 17440, W.no. 1.4435
Valve plate, O-ring, diaphragm EPDM
Diaphragm housing CrNi steel, DIN 17440, W.no. 1.4435
Diaphragm plate CrNi steel, DIN 17440, W.no. 1.4436
Diaphragm spindle
Diaphragm housing stuffing box
Housing
Spindle CrNi steel, DIN 17440, W.no. 1.4401
Sensor
Sensor
Sensor stuffing box EPDM
Gasket Carbon dioxide (CO2)
Charge
Valve body
Valve base
Pilot valve
Valve spindle CrNi steel, DIN 17440, W.no. 1.4401
Setting spring CrNi steel, DIN 17440, W.no. 1.4568
Cone, spring retainer PPS-plastic
O-ring EPDM
1)
Valid for primary side (main valve)
2)
Valid for secondar y side (pilot valve and diap hragm element)
3)
In case of domesti c hot water (secondary side) pH lowe r than 7 -> the hardne ss of the water must be larger than th e sulphate element
4)
at T idle nom. + 10 °C
4)
1)
16
2)
10
6
Circulation water / glycolic water up to 30%
1)
Domestic hot water (chlorine (cl) content max. 200 ppm)
1) ,2) ,3)
1)
2 … 100
2)
2 … 90
Dezincification resistant brass BS 2874
Ecobrass (CW724R)
Ecobrass (CW724R)
Dezincification resistant brass BS 2874
Ecobrass (CW724R)
Ecobrass (CW724R)
Ecobrass (CW724R)
2)
00 3L7120
HCO
3
––SO
2 | VD.LJ.A2.02
© Danfoss | 2017.11
Data sheet Flow-compensated temperature controller AVTQ DN 15
Application principle
The controller AVTQ must be installed in the return pipeline only.
Design
1. Thermostatic actuator with
sensor stuffing box
2. Pressure spindle
3. Diaphragm housing
stuffing box
4. Nut
5. Diaphragm housing
6. Diaphragm spindle
7. Control diaphragm
8. Compression connection for
impulse tube
9. Intermediate ring
10. Nameplate
11. Main spring
12. Damping + teflon ring
13. Valve spindle
14. Valve ins ert
15. Pressure relief c ylinder
16. Valve body (main valve)
17. Handle for temperature setting
18. Spindle
19. Valve b ase
20. Spring retainer
21. Setting spring
22. Pressure equalizing hole
23. Valve cone
24. Valve body (pilot valve)
25. Compression connection for
impulse tube
26. Sealing bolt of sensor stuffing box
27. Gasket of sensor stuf fing box
28. Housing of sensor stuffing box
When domestic hot water (DHW) is tapped, flow through the pilot valve creates a pressure drop (force in the diaphragm housing) which is used to increase the temperature level from no-load (idle) to set tapping temperature.
This temperature increase causes the main valve to open for flow on the district heating side and close when the temperature level again falls to the no-load operating level. No-load operation prevents the district heating line becoming cold. Tapping temperature can be set individually.
© Danfoss | 2017.11
VD.LJ.A2.02 | 3
Data sheet Flow-compensated temperature controller AVTQ DN 15
Installation
One-way heat exchanger Two-way heat exchanger Three-way heat exchanger Fig. 3
AVTQ can be used with most types of plate heat exchangers.
The AVTQ manufacturer should be contacted to ensure:
- that the AVTQ is approved for use with the chosen heat exchanger
- the correct material selection when connection the heat exchangers
- the correct connection of one pass plate heat exchangers; layer distribution might occur, i.e. reduced comfort
The system functions optimal when the sensor is installed right inside the heat exchanger (see page 3). However, the sensor head should be placed approx. 5 mm from the plate which divides the primary and the secondary side of the exchanger. If the sensor head is placed too close to the dividing plate, the sensor might measure the temperature of the plate and not the temperature of the medium. For correct no­load operation, thermal flow should be avoided since hot water rises and increases the no-load consumption.
Note: water velocity around the sensor must be in accordance with the requirements for copper tube.
The temperature controller (main valve):
- must be installed in the return pipeline on the district heating (primary) side of the heat exchanger
- the diaphragm element can be turned in any position in relation to the valve body so that impulse tube can be connected in the required direction
The pilot valve:
- must only be installed in the flow pipeline on the secondary side of the heat exchanger
- in systems where it cannot be excluded that drinking water is contaminated with fine dust from time to time, it is recommended not to mount the pilot valve with the impulse tube connections downwards (fig.2) to avoid dirt ingress in the impulse tubes and diaphragm housing
The sensor can be installed in any position (fig.1)
It is strongly recommended that:
- the primary and secondary sides of the heat exchanger should be flushed through before the heating system is used the first time. In addition the (+) and (–) side of the diaphragm should be vented.
- dirt strainers with a mesh size of max. 0.6mm should be installed in both, the cold tap water pipeline ahead of the pilot valve and in the flow pipeline from the district heating network.
4 | VD.LJ.A2.02
Fig. 1 Fig. 2
© Danfoss | 2017.11
Data sheet Flow-compensated temperature controller AVTQ DN 15
()
86.0x42
86.0xP
[
]
Sizing Example
Given data:
T1 = 65 °C T3 = 50 °C T4 = 10 °C Q2 = 0.3, 0.6, 0.9 m3/h (300, 600, 900 l/h)
Primary Secondary
T1 - District heating water flow temperature T3 - Hot water temperature T4 - Cold water temperature Q2 - Hot water service flow
District heating flow line
District heating return line
Fig. 4
The maximum heating power P according to formula:
TxQ
p
max
p
max
=
=
=
86.0
()
86.0
86.0
1050x900
− =
TTxQ
43222
kW42
is calculated
max
Based on max. heating power heat exchanger could be selected. Information about the cooling across the primary side of heat exchanger can be acquired either by contacting the manufacturer of the heat exchanger or by using the manufacturer’s dimensioning diagram.
In the example chosen cooling on primary side (ΔT1) is 43 °C, 40 °C or 39 °C, the differential pressure across the AVTQ main valve (Δpv) is
0.2 bar.
Hot water
C old water
Chosen AVTQ main valve has kvs 3.2 m3/h and therefore is big enough. Values for flows of 300 and 600 l/h are calculated on the same way and entered in the table.
Tab.1
Secondary flow Primary flow Cooling
W
(kW)
14 300 280 0.39 43
28 600 600 0.85 40
42 900 925 1.31 39
Q
(l/h)
Q
2
(l/h)
k
1
v
(m3/h)
∆T
(°C)
1
They can be plotted on the diagram overleaf (fig. 5) and connected. The temperature variation can be read from the diagram as the difference between the temperature lines intersected by the curve
The primary flow Q1 can be calculated according to formula:
max
Q
=
1
=
T
1
h/l925Q1=
39
Using the above data, the needed capacity of the main valve (kv) can be calculated:
3
1
=
k
v
[]
barp
v
925.0
h/mQ
=
2.0
kv = 1.31 m3/h
© Danfoss | 2017.11
VD.LJ.A2.02 | 5
Data sheet Flow-compensated temperature controller AVTQ DN 15
Sizing (continuous)
The pressure drop across the pilot valve can be read from the diagram below.
Fig. 6 Pressure drop (Δp
) across pilot valve as a function of the setting value and secondary flow
pilot
Setting
The AVTQ controller can be used with plate heat exchangers of up to 75 kW. As a result of the flow compensation principle an actual dimensioning of the valve is unnecessary, because the valve will always adjust around the required temperature without regard to the flow.
This means that if the controller is set to 50 °C (this is done at 75% of max. tapping flow to obtain optimum control), then this temperature will be maintained whether or
not the actual is 120 l/h, 900 l/h or more. Between 120 l/h and 900 l/h the temperature will vary approx. 4 °C.
Typical settings:
Minimum:
Designation Application values Pilot valve setting
Flow temperature, primary Tp = 65 °C Dierential pressure across the AVTQ main valve ∆p = 0.5 bar Hot water temperature, secondary Ts (hot) = 50 °C Cold water temperature, secondary Ts (cold) = 10 °C Secondary ow Qs = 800 l/h
3.0
Maximum:
Designation Application values Pilot valve setting
Flow temperature, primary Tp = 100 °C Dierential pressure across the AVTQ main valve ∆p = 6.0 bar Hot water temperature, secondary Ts (hot) = 50 °C Cold water temperature, secondary Ts (cold) = 10 °C Secondary ow Qs = 750 l/h
The values mentioned above are reference values and therefore corrections of pilot valve settings might be necessary in order to obtain
Other approx. setting values: Tapping temperature = 50 °C Tapping flow = 800 l/h
2.0
the required temperature.
T
primary
65 °C 3.0 2.5 2.5 2.5
80 °C 2.75 2.5 2.25 2.25
100 ° C 2.5 2.5 2.25 2.0
0.5 1.0 3.0 6.0
∆p (bar)
flow
6 | VD.LJ.A2.02
© Danfoss | 2017.11
Data sheet Flow-compensated temperature controller AVTQ DN 15
Dimensions
R 3/4
DN
(mm)
L
1
(mm)
L
(mm)
2
L
3
(mm)aISO 228/1bISO 228/1
Weight
15 65 22.5 35 G ¾ A G ¾ A 3.57
(kg)
© Danfoss | 2017.11
VD.LJ.A2.02 | 7
Danf already on order pro All trademarks in this material are property of the respec
Data sheet Flow-compensated temperature controller AVTQ DN 15
oss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
vided that such alterations can be made without subsequential changes being necessary eady agreed.
8 | VD.LJ.A2.02
tive companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
© Danfoss | DHS-SRMT/SI | 2017.11
Loading...