Thermo. operated water valves are used for
proportional regulation of ow quantity, depending
on the setting and the sensor temperature.
The Danfoss range of thermo. operated water
valves includes a series of products for both
refrigeration and heating regulation.
The valves are self-acting, i.e. they operate without
the supply of auxiliary energy such as electricity or
compressed air.
The required temperature is maintained constant
without unnecessary use of:
• cooling water in cooling systems,
• hot water or steam in heating systems.
The operating economy and-eciency are
maximized.
AVTA SS for aggressive media.
A valve body in stainless steel means that the
valve can be used for aggressive media in such
applications as the marine sector and the chemical
industry.
Features• Insensitive to dirt
• Insensitive to water pressure
• Needs no power supply – self acting
• Opens on rising sensor temperature
• Dierential pressure: 0 – 145 psi
• Maximum working pressure (MWP): 232 psi
Maximum test pressure: 365 psi
• The valves are pressure-relieved, i.e. the degree
of opening is not aected by dierential pressure
Δp (pressure drop).
• The regulation range is dened for the point at
which the valve begins to open.
• Cooling media temperature range: -13 – 266 °F
• Ethylene glycol as a cooling media up to 40%
Data sheet | Thermo. operated water valve, AVTA
3N1103.13
Danf
3N1101.13
How it works
Thermo. operated water valves
consist of three main elements:
1. Setting section with knob,
reference spring and setting
scale.
2. Valve body with orice,
closing cone and sealing
elements.
3. Hermetically sealed
thermostatic element with
sensor, bellows and charge.
When the three elements have been assembled
together, the valve installed and the sensor located
at the point where the temperature is to be
regulated, the function sequence is as follows:
1
1. The pressure changes in the sensor as a result of
a change in temperature - builds up in the sensor.
2. This pressure is transferred to the valve via the
capillary tube and bellows and acts as an
oss
opening or closing force.
3. The knob on the setting section and the spring
exert a force that acts counter to the bellows.
Danfoss
3N1102.12
2
4. When balance is created between the two
opposing forces, the valve spindle remains in its
position.
5. If the sensor temperature changes – or if the
settings are changed – the point of balance
becomes displaced and the valve spindle moves
until balance is re-established, or the valve is fully
3
open or closed.
6. The ow quantity change is approximately
proportional to sensor temperature change.
The illustrations show an AVTA cooling water valve,
but the function principle applies to all types of
thermostatic valves.
Danfoss
AVTA applicationsAVTA thermo. operated water valves are widely
used for temperature regulation in many dierent
machines and installations where cooling is
required. AVTA cooling water valves always open to
admit ow on rising sensor temperature.
The valve can be installed in either the cooling
water ow line or the return line.
The standard version of the ATVA thermo. operated
water valve can be used with fresh water or neutral
brine.
For immersion pockets, see
“Spare parts and accessories”,
page 8.
The charge is a mix of liquid and gas where the
liquid surface (regulating point) is always inside the
sensor. Which charge medium is used depends on
the regulation range.
y Sensor dimensions ø0.7 × 8.3 iny Sensor can be installed in a place where it is
either colder or warmer than the valve
y Sensors must be orientated as shown in the
The charge is a mix of liquid and gas. Due to the
mixture of liquid and gas the sensor must be
installed in an area or environment that is warmer
than the valve.
Connection1)
Regulating
range
Max. temp.
sensor
Cv value
y Small sensor dimensions – ø0.4× 7.5 iny Short time constanty Max. pressure on sensor 365 psiy Only codes with G thread available
The valves can be installed in any position.
An arrow on the valve body indicates the direction
of ow.
AVTA valves are marked so that the letters RA are
the right way up when the valve is held as shown.
The installation of an FV lter ahead of the valve is
recommended.
Capillary tube
Install the capillary tube without sharp bends (no
”kinks”). Make sure that there is no strain on the
capillary tube at the ends. Relief is important where
vibration might occur.
Note:
When an AVTA valve is used, the sensor must be
able to react to variations in cooling water
temperature on system start. Therefore a bypass
line with a shut-o valve might be necessary to
ensure ow at the sensor during start-up.
If a mounting bracket is used – see “Spare parts and
accessories”, page 10 – it must always be positioned
between the valve body and the setting section
(see illustration).
When sizing and selecting thermo. operated water
valves, it is most important to ensure that the valve
is able to give the necessary quantity of cooling
water at any time, irrespective of the load.
Therefore, to select a suitable size of valve it is
necessary to know the precise amount of cooling
required. On the other hand, to avoid the risk of
unstable regulation (hunting), the valve should not
be oversized.
The type of charge must be selected on the basis of
the temperature to be maintained, and on an
assessment of the characteristics of each type, as
described in the foregoing.
In general the aim should be to select the smallest
valve capable of giving the required ow.
It is also recommended that the temperature range
be chosen so that the required sensor temperature
lies in the middle of the regulation range.
To help ne-setting the valve, a thermometer
should be installed near the sensor.
Example
A cooling water valve must be selected for the
temperature regulation of a vacuum pump.
Since direct regulation of the oil temperature is
required, an AVTA valve is suitable.
The sensor position is horizontal – and small
dimensions are desired.
Given data:
y Necessary cooling at full load 5 TR.y Oil temperature to be maintained constant at 113 °Fy Cooling water p1 = 60 psi
y Outlet p3 = 0 psi
3
p1+p
y p2 =
y Cooling water temperature t1 = 88 °F
2
(guess)
y Outlet temperature t2 = 68 °F
Valve size
The following data are used when selecting the
valve size:
y Required cooling water ow, Q [US [gpm]]y Temperature rise in cooling water, Δt [°F]y Dierential pressure across valve, Δp [psi].
With fully open valve, the dierential pressure
should be around 50% of the total pressure drop
across the cooling system.
The charts on page 12 are intended to make valve
sizing easier.
Fig. 1 – Relation between heat quantity [kW] and
cooling water quantity
Fig. 2 – Graphs of Cv values
Fig. 3 – Valve operating range
Fig. 4 – Flow quantities as a function of pressure
drop Δp
Operating conditions and other product
requirements in this example mean that a valve
with adsorption charge is the correct choice.
The temperature range 50 – 176 °F is in order.
The table on page 4 gives AVTA 15,
code no.0 03N 6115, which fulll the requirements.
To facilitate the installation a sensor pocket is often
used. A sensor pocket for ø0,4” sensor in brass,
code. no. 017- 436766, or in stainless steel, code no.
003N0196, is listed under “Accessories” on page 10.
1. Using the graph in g.1, you nd the necessary
cooling water quantity at Δt = 20 °F (88 – 68 °F)
for 6 US [gpm].
2. Using the graph in g. 2, you nd the
necessary Cv-value for 6 US [gpm] at Δp = 30 psi
(60 – 0)/2) for 1.17 US [gpm].
3. It can be seen from the columns in g.2 that
all three AVTA valves ca n be used, but the
preferable selection is a valve where the
necessary Cv-value lies in the middle of the
range. So in practice an AVTA 15 ought to be
selected as it fully meets the demand.
Cv values are allways water ow in US gpm for a
pressure drop Δp of 1 psi.
The preferable selection is a valve where the
necessary Cv-value lies in the middle of the range,
as a valve with a Cv-value close to either the max. or
min. value is less stable and less precise due to
either a relatively large Δp or ΔQ.
Example:
AVTA 10 and 15 are the most suitable for a Cv value
of 1.17 US [gpm].
Danfoss
Fig. 4 Valve ow quantity in fully open position, as a function of pressure drop Δp.
Optionsy DZR brass
y Outer thread connectingy Other lengths of capillary tubesy Armouring of capillary tubesy Other combinations of sizes, materials and