Danfoss AME 25, AME 35 Operating guide [da]

Operating Guide
AME 25, AME 35
ENGLISH
DANSK
DEUTSCH
ESPAÑOL
SUOMI
NEDERLANDS
POLSKI
РУССКИЙ
ROMÂNĂ
AME 25, AME 35 +
Adapter (0 6 5Z 0311) +
VRB 2, VRG 2 (D N 15-50)
AME 25, AME 35 www.danfoss.com Page 5
AME 25, AME 35 www.danfoss.dk Side 6
AME 25, AME 35 www.danfoss.de Seite 7
AME 25, AME 35 www.danfoss.fr Page 8
AME 25, AME 35 www.danfoss.es Página 9
AME 25, AME 35
AME 25, AME 35 www.danfoss.nl Bladzijde 11
AME 25, AME 35
AME 25, AME 35
AME 25, AME 35 www.incalzire.danfoss.com Pagina 14
AME 25, AME 35 +
Adapter (0 6 5Z 0311) +
VRB 3, VR3 2 (D N 15-50)
AME 25, AME 35 +
Adapter (0 6 5Z 0311) +
VF 2, VL 2 (DN 15-50)
www.danfoss.fi Sivu 10
www.danfoss.pl Strona 12
www.danfoss.ru Страница 13
AME 25, AME 35 +
Adapter (0 6 5Z 0311) +
VF 3, VL 3 (DN 15-50)
AME 25, AME 35 +
VFS 2 (DN 15-50)
中文
© Danfoss | 2016.11
AME 25, AME 35 www.danfoss.com.cn 16
EI.LF.M1.2V | 1
AME 25, AME 35
=
AUTO
MAINTENANCE
FREE
5-95 % RH
no condensing
or
=
4 – 6 mm × 1 mm T 10 2 / 4 mm
BLUE
RED
B
A
A B
T
≤150 ° C T
max
=150 … 200° C
max
≈5°
065Z 7548
≈5°
2 | © Danfoss | 2016.11
EI.LF.M1.2V
AME 25, AME 35
Wiring for modulating mode
Proportional 3 point/ RL
Wiring fo r 3-point flo ating mode Controll er with relay outpu t
SN 0 V Neutral
SP 24 VAC Power supply
Y
1
3
X 0(2) -10 V Output
0(2)-10 V
0(4) -20 mA
0 V Input
Input
Proportional 3 point/ RL
Wiring fo r 3-point flo ating mode Controll er with triacs out put
Proportional 3 point/ RL
SN 0 V Neutral
SP 24 VAC Pow er supply
1
24 VAC Input
3
X 0(2)-10 VDC Output
SN
SP
1
3
24 VAC Neutral
0 V Power suppl y
24 VAC Input
EI.LF.M1.2V
X 0(2)-10 V DC Output
© Danfoss | 2016.11 | 3
AME 25, AME 35
155
179
16
47, 5
min . 160
83
EI.LF.M1.2V
© Danfoss | 2016.11 | 4
AME 25, AME 35
ClampXO
O
OOO
YokeXO
O
OOO
ENGLISH
Safety Note
To avoid injury of persons and damages to the device, it is absolutely
instructions carefully.
Necessary assembly, start-up, and maintenance work must be performed by qualified and authorized personnel only.
Please comply with the instructions of the system manufacturer or system operator.
Disposal instruction
Mounting
Fix the actuator on the valve Admissible Installation Positions
Wiring
Control signal
Control signal from the controller must be connected to terminals Y (input signal) and SN (common) on the AME printed board.
Output signal
Output signal from the terminal X can be used for indication of the current position. Range depends on the DIP switch settings.
Supply voltage
Supply voltage (24 V~ –15 to +10 %, 50 Hz) must be connected to the terminals SN and SP.
DIP switch settings
necessary to read and observe these
Do not remove the cover before th e power supply is ful ly switched off.
This product shou ld be dismantled and its components so rted, if possible, in various groups befo re recycling or disposal.
Always follow the local d isposal regulations.
Do not touch anythin g on the PCB! Switch off the power lin e before wire
the actuator! Lethal voltage! Wire the actuator according to the wi ring diagram.
U I
2 V_---V 0 V_---V
Direct Inverse
--- S equential 0(2) V_5(6) V 5(6) V_10 V Proportional 3 point/RL
LOG. fl ow L IN. flow
100 % k
VS
Reset Reset
RED. k
VS
Factory settings:
ALL switches are on OFF position! ❹①
Note: All combinations of DIP switches are
allowed. All functions that are selected are added consecutively. There is only one logic override of functionalities i.e. the switch No.6 Propor tional/3 point, which sets actuator to ignore control signal and works as a “simple” 3-point actuator.
SW1: U/I ❹②
Factory settings:
Voltage control signal (0-10 V).
SW2: 2-10 V/0-10 V ❹③
Factory settings:
2-10 V.
SW3: Direct/Inverse ❹④
Factory settings:
DIRECT
SW4:---/Sequential ❹⑤
Two actuators can be set to work parallel with one control signal. If the SEQUENTIAL is set than an actuator respowwnds to split control signal (see 0(2)-5(6) V/5(6)-10 V).
Note: This combination works in combination
with switch No.5: 0(2)-5(6) V/5(6)-10 V
SW5: 0(2)-5(6) V/5(6)-10 V ❹⑥
Note: This function is available if switch No.4:
---/Sequential is set.
SW6: Proportional/3 point ❹⑦
Actuator needs to pe rform Self stroking prior chan ging DIP 6 to ON. Output signal dep ends on DIP 2, 3&5 setting.
Actuator can operate in modulating (DIP 6 to OFF) or in “simple” 3-point mode, if the 3-point function is selected (DIP 6 to ON).
Connect power supply on terminals SN and SP terminals.
Factory set DIP 6 to OFF for operating actuator in Modulating mode.
Actuator’s stem will run to its totally extended or retracted position by bridging SN signal to terminals 1 or 3 and will remain in this positron as long as potential is present.
Set DIP 6 to ON for operating actuator in 3 point mode.
Look carefully wiring diagram as wiring is different for controllers with triac output (ECL) in comparison to controllers with relay output.
Return signal X indicates the correct position.
Note: If 3 point function is selected actuator
does not respond to any control signal on port Y. It only rises and lowers spindle if power is supplied on port 1 or 3.
SW 7: LOG. flow/LIN. flow ❹⑧
Factory setting is:
LOG. Flow (characteristic of valve is unchanged)
Note: If this function is used in combination
with non-logarithmic valves the characteristic of motorised valve will be anti-logarithm of valve’s characteristic (e.g. valve with linear characteristic will be transformed to quick open characteristic).
SW 8: 100% KVS/RED. KVS ❹⑨
Note: This function works proper only with
logarithmic (equal percentage) valves.
SW9: Reset ❹⑧
After the actuator has been connected to power supply, the actuator will start the self-adjustment procedure. The indicator LED flashes until self adjustment is finished. The duration depends on the spindle travel and will normally last a few minutes. The stroke length of the valve is stored in the memory after self adjustment has been completed. To restart self adjustment, change the position of RESET switch (switch No.9). If the supply voltage is switched off or falls below 80 % in more than
0.1 s, the current valve position will be stored in the memory and all data remain saved in the memory also after a power supply cut-out.
Function test
The indicator light shows whether the positioner is in operation or not. Moreover, the indicator shows the control status and faults. Constant light
- normal operation
No light
- no operation or no power supply
Intermittent light (1 Hz)
- self adjusting-mode
Intermittent light (3 Hz):
- power supply too low
- insufficient valve stroke (<20 s)
- end-position cannot be reached.
Dimensions
Part Name
Housing X O O O O O Bushings X O O O O O
O: Indica tes that this hazar dous substance con tained in all of the h omogeneous ma terial for this par t is below the limi t requirement in GB /T 26572; X: Indica tes that this hazar dous substance co ntained in at least o ne of the homogen eous material fo r this part is above th e limit requirem ent in GB/T 26572;
Lead (P b) Mercur y (Hg) Cadmium (Cd) Hexavalent Chromium (Cr(VI)) Polybrominated biphenyls (PBB) Polybrominated diphenyl ethers (PBDE)
EI.LF.M1.2V
Hazardous Substances Table
© Danfoss | 2016.11 | 5
Loading...
+ 11 hidden pages