Data sheet
Actuators for modulating control
AME 13 SU/SD-1 - safety function
Description |
|
The actuator has some special features: |
||
|
|
• The advanced design incorporates load |
||
|
|
|
related ‘switch-off’ to ensure that actuators |
|
|
|
|
and valves are not exposed to overload |
|
|
|
• The advanced design incorporates a |
||
|
|
|
diagnostic LED, operational data capture and |
|
|
|
|
self stroking feature |
|
|
|
• Low weight and robust |
|
|
|
|
• Sefety function (spring up / spring down) |
||
|
|
Main data: |
|
|
|
|
• |
Nominal voltage: |
|
|
|
|
- 24 VAC, 50 Hz/60 Hz |
|
|
|
• |
Control input signal: |
|
|
|
|
- 0(4)…20 mA |
|
|
|
|
- 0(2) … 10 V |
|
|
|
• |
Force: 300 N |
|
|
The AME 13 SU/SD-1 is a compact gear motor |
• |
Stroke: 5,5 mm |
|
|
actuator that is assembled to ½” to 1-¼” AB-QM |
• |
Speed: 11.75 s/mm (50 Hz) / 14 s/mm (60 Hz) |
|
|
valves sizes. |
• |
Max. medium temperature: 130 °C |
|
|
Safety version is activated automatically in |
• |
Electronic stroke limitation |
|
|
case of power failure or if the power supply is |
• |
In axxordance with UL 2043 for plenum |
|
|
switched off by the safety thermostat. |
|
installation |
|
Ordering |
Type |
|
Supply voltage |
Code No. |
|
AME 13 SU-1 |
|
24 V~ |
082H5006 |
|
AME 13 SD-1 |
|
082H5007 |
|
|
|
|
Technical data
Type |
|
AME 13 SU/SD-1 |
|
Power supply |
V |
24; +10 to –15 %; AC |
|
|
|
|
|
Power consumption |
VA |
9 |
|
Frequency |
Hz |
50/60 |
|
|
|
|
|
Control input Y |
V |
0-10 (2-10) |
|
mA |
0-20 (4-20) |
||
|
|||
|
|
|
|
Output signal X |
V |
0-10 (2-10) |
|
Closing force |
lbf (N) |
67.4 (300) |
|
|
|
|
|
Max. stroke |
mm |
5.5 |
|
Speed |
s/mm |
11.75 (50 Hz) / 14 (60 Hz) |
|
|
|
|
|
Max. medium temperature |
|
248 (120) |
|
Ambient temperature |
°F (°C) |
32… + 131 (0… + 55) |
|
|
|
|
|
Storage and transport temp. |
|
-40…+158 (-40…+70) |
|
Grade of enclosure |
|
IP 54 |
|
|
|
|
|
Ambient humidity |
|
95% r.h., non-condensing |
|
Protection class |
|
Class 2 (North America) or Safety Extra-Low Voltage (SELV) (Europe) |
|
|
|
|
|
Weight |
lbs (kg) |
1.76 (0.8) |
|
USA |
UL Listed, CCN XABE, File E480529; to ANSI/UL 60730-1 and ANSI/ UL 60730-2-14 |
|
|
Investigated and approved for plenum use in accordance with UL 2043 |
||
C |
US |
||
|
|||
|
Canada |
UL listed, CCN XABE7, File E480529; to CAN/CSA-E60730-1:13 and CAN/CSA-E60730-2-14:13 |
|
|
Europe |
CE Mark - Danfoss declares that this product complies with all relevant CE-marking directives |
© Danfoss | 2019.07 |
VD.MJ.A1.22 | 1 |
Data sheet |
Actuators for modulating control AME 13 SU/SD-1 |
Installation
AME 13SU
Mechanical
The actuator should be mounted with the valve stem in either horizontal position or pointing upwards.
The actuator is fixed to the valve body by means of a mounting nut which requires
32 mm screw key. The nut should be tightened with a torque of max. 25 Nm.
AME 13SU
Electrical
Electrical connections can be accessed by removing the cover.
Two M16×1.5 cable entries are provided. However, in order to maintain the enclosure IP rating an appropriate cable gland must be used.
Disposal |
The actuator must be dismantled and the |
|
elements sorted into various material groups |
|
before disposal. |
2 | VD.MJ.A1.22 |
© Danfoss | 2019.07 |
Data sheet |
Actuators for modulating control AME 13 SU/SD-1 |
DIP switch setting
The actuator has a function selection DIP switch under the removable cover.
The switch provides the following functions:
• SW1: U/I - Input signal type selector:
If set to OFF position, voltage input is selected. If set to ON position, current input is selected.
• SW2: 0/2 - Input signal range selector:
If set to OFF position, the input signal is in the range from 2-10 V (voltage input) or from 4-20 mA (current input).
If set to ON position, the input signal is in the range from 0-10 V (voltage input) or from 0-20 mA (current input).
• SW3: D/I - Direct or inverse acting selector:
If set to OFF position, the actuator is direct acting (stem retracts as voltage increases).
If the actuator is set to ON position, the actuator is inverse acting (stem extends as voltage increases).
• SW4: —/Seq - Normal or sequential mode selector:
If set to OFF position, the actuator is working normally in 0(2)-10V or 0(4)-20mA range.
If set to ON position, the actuator is working in a sequential mode with its range dependent on the position of SW 4.
• SW5: 0-5 V/5-10 V - Input signal range in sequential mode:
If set to OFF position, the actuator is working in sequential range 0(2)-5 (6) V or 0(4)-10 (12) mA. If set to ON position, the actuator is working in sequential range; 5(6)-10 V or 10(12)-20 mA
• SW6: Proportional/Floating point - Modulating or 3-point mode selector:
If set to ON position, the actuator can operate as Floating point actuator. Power supply should be connected on SN and SP ports. On port 1 or 3 24 VAC signal is connected for rising or lowering of actuator. Return signal X indicates the correct position.
If set to OFF position, the actuator operates on modulating input signal.
•SW7: LOG/LIN- Input signal range in sequential mode:
If set to ON position, the flow through the valve is equal percentage to the control signal.
If set to OFF position, the valve position is linear acc. to the control signal.
•SW8:
Set to ON for valve bodies 1/2” to 1-1/4” HF. The actuator will modulate on max stem travel of 4.5mm.
Set to OFF for valve body 1/2” Low flow. The actuator will modulate on max stem travel of 2.5mm.
• SW9: Reset:
Toggling the switch will cause the actuator to go through an auto-calibration cycle.
Function test
The indicator light shows whether the positioner is in operation or not. Moreover, the indicator shows the control status and faults.
Constant light
-normal operation No light
-no operation or no power supply Intermittent light (1 Hz)
-self adjusting-mode Intermittent light (3 Hz):
-power supply too low
-insufficient valve stroke (<20 s)
-end-position cannot be reached.