Data sheet
Actuators for modulating control
AME 13 SU/SD-1 - safety function
Description
Ordering
The actuator has some special features:
• The advanced design incorporates load
related ‘switch-off’ to ensure that actuators
and valves are not exposed to overload
• The advanced design incorporates a
diagnostic LED, operational data capture and
self stroking feature
• Low weight and robust
• Sefety function (spring up / spring down)
Main data:
• Nominal voltage:
- 24 VAC, 50 Hz/60 Hz
• Control input signal:
- 0(4)…20 mA
- 0(2) … 10 V
• Force: 300 N
The AME 13 SU/SD-1 is a compact gear motor
actuator that is assembled to ½” to 1-¼” AB-QM
valves sizes.
Safety version is activated automatically in
case of power failure or if the power supply is
switched off by the safety thermostat.
Typ e Supply voltage Code No.
AME 13 SU-1
AME 13 SD-1 082H5007
• Stroke: 5,5 mm
• Speed: 11.75 s/mm (50 Hz) / 14 s/mm (60 Hz)
• Max. medium temperature: 130 °C
• Electronic stroke limitation
• In axxordance with UL 2043 for plenum
installation
24 V~
082H5006
Technical data
© Danfoss | 2019.07
Typ e AME 13 SU/SD-1
Power supply V 24; +10 to –15 %; AC
Power consumption VA 9
Frequency Hz 50/60
Control input Y
Output signal X V 0-10 (2-10)
Closing force lbf (N) 67. 4 (3 00 )
Max. stroke mm 5.5
Speed s/mm 11.75 (50 Hz) / 14 (60 Hz)
Max. medium temperature
Ambient temperature 32… + 131 (0… + 55)
Storage and transpor t temp. -40…+15 8 (- 40…+70 )
Grade of enclosure IP 54
Ambient humidity 95% r.h., non-condensing
Protection class Class 2 (North America) or Safety Extra-Low Voltage (SELV) (Europe)
Weight lbs (kg) 1.76 (0.8)
USA
C US
Canada
Europe
V 0-10 (2 -10)
mA 0-20 (4 -20)
24 8 (120)
°F (°C )
UL Listed , CCN XABE, File E480529 ; to ANSI/UL 60730-1 and ANS I/ UL 60730-2-14
Investig ated and approved f or plenum use in accor dance with UL 2043
UL listed , CCN XABE7, File E480529; to CAN/CS A-E60730-1:13 and CAN/CSA-E60730 -2-14:13
CE Mark - Danf oss declares that t his product comp lies with all relev ant CE-marking d irectives
VD.MJ.A1.22 | 1
Data sheet Actuators for modulating control AME 13 SU/SD-1
Installation
Disposal
AM E 13SU
Mechanical
The actuator should be mounted with the valve
stem in either horizontal position or pointing
upwards.
The actuator is fixed to the valve body by means
of a mounting nut which requires
32 mm screw key. The nut should be tightened
with a torque of max. 25 Nm.
The actuator must be dismantled and the
elements sorted into various material groups
before disposal.
AM E 13SU
Electrical
Electrical connections can be accessed by
removing the cover.
Two M16×1.5 cable entries are provided.
However, in order to maintain the enclosure IP
rating an appropriate cable gland must be used.
2 | VD.MJ.A1.22
© Danfoss | 2019.07
Data sheet Actuators for modulating control AME 13 SU/SD-1
DIP switch setting
The actuator has a function selection DIP switch
under the removable cover.
The switch provides the following functions:
• SW1: U/I - Input signal type selector:
If set to OFF position, voltage input is selected.
If set to ON position, current input is selected.
• SW2: 0/2 - Input signal range selector:
If set to OFF position, the input signal is in the
range from 2-10 V (voltage input) or from 4-20
mA (current input).
If set to ON position, the input signal is in the
range from 0-10 V (voltage input) or from 0-20
mA (current input).
• SW3: D/I - Direct or inverse acting selector:
If set to OFF position, the actuator is direct acting
(stem retracts as voltage increases).
If the actuator is set to ON position, the actuator
is inverse acting (stem extends as voltage
increases).
• SW4: —/Seq - Normal or sequential mode
selector:
If set to OFF position, the actuator is working
normally in 0(2)-10V or 0(4)-20mA range.
If set to ON position, the actuator is working in
a sequential mode with its range dependent on
the position of SW 4.
• SW6: Proportional/Floating point -
Modulating or 3-point mode selector:
If set to ON position, the actuator can operate
as Floating point actuator. Power supply should
be connected on SN and SP ports. On port 1 or 3
24 VAC signal is connected for rising or lowering
of actuator. Return signal X indicates the correct
position.
If set to OFF position, the actuator operates on
modulating input signal.
• SW7: LOG/LIN- Input signal range in sequential
mode:
If set to ON position, the flow through the valve
is equal percentage to the control signal.
If set to OFF position, the valve position is linear
acc. to the control signal.
• SW8:
Set to ON for valve bodies 1/2” to 1-1/4” HF. The
actuator will modulate on max stem travel of
4.5mm.
Set to OFF for valve body 1/2” Low flow. The
actuator will modulate on max stem travel of
2.5mm.
• SW9: Reset:
Toggling the switch will cause the actuator to go
through an auto-calibration cycle.
Function test
The indicator light shows whether the positioner
is in operation or not. Moreover, the indicator
shows the control status and faults.
Constant light
- normal operation
No light
- no operation or no power supply
Intermittent light (1 Hz)
- self adjusting-mode
Intermittent light (3 Hz):
- power supply too low
- insufficient valve stroke (<20 s)
- end-position cannot be reached.
© Danfoss | 2019.07
• SW5: 0-5 V/5-10 V - Input signal range in
sequential mode:
If set to OFF position, the actuator is working in
sequential range 0(2)-5 (6) V or 0(4)-10 (12) mA.
If set to ON position, the actuator is working in
sequential range; 5(6)-10 V or 10(12)-20 mA
VD.MJ.A1.22 | 3