Data sheet
Actuators for modulating control
AME 13SU, AME 23SU - safety function (spring up)
Description
AME 13SU AME 23SU
Ordering
The actuators with safety function are mainly
used with VZ valve (AME 13SU) or with VS, VM
and VB valves (AME 13SU, AME 23SU). Safety
version is activated automatically in case of
power failure or if the power supply is switched
off by the safety thermostat.
The actuator has some special features:
• The advanced design incorporates load
related ‘switch-off’ to ensure that actuators
and valves are not exposed to overload;
• The advanced design incorporates a
diagnostic LED, operational data capture
and self-adjusting feature;
• Low weight and robust;
• Safety function (spring up).
Typ e
AM E 13SU
AME 23SU 082G3042
Supply voltage
(V)
24
Code No.
082H3044
Main data:
• Nominal voltage:
- 24 Vac, 50 Hz/60 Hz
• Force:
- AME 13 SU.......................300 N
- AME 23 SU ......................450 N
•
Stroke:
-
AME 13 SU .......................
-
AME 23 SU ......................
• Speed:
- AME 13 SU.......................14 s/mm
- AME 23 SU ......................15 s/mm
• Max. medium temperature: 130 °C
• Self stroking
5.5 mm
10 mm
© Danfoss | 2018.12 VD.AB.U5.02 | 1

Data sheet Actuators for modulating control AME 13SU, AME 23SU
Technical data
Typ e AM E 13SU AME 23SU
Power supply Vac 24; +10 to –15 %
Power consumption VA 9
Frequency Hz 50/60
Control input Y
Output signal X Vdc 0 -10 (2-10)
Closing force N 300 450
Max. stroke mm 5.5 10
Speed s/mm 14 15
Max. medium temperature
Ambient temperature 0 … 55
Storage and transpor t temp. –40 … 70
Ambient humidity 5-95 % r.h., non-condensing
Protection Class II I (230V); III(24V)
Grade of enclosure IP 54
Weight kg 0.8 1.45
- marking in accordance with standards
Vdc
mA 0-20 (4 -20)
°C
Low Voltage Directive (LVD) 2014/35/EU: EN 60730-1, EN 60730-2-14
Electromagnetic Compatibility Directive (EMC) 2014/30/EU: EN 61000-6 -2,
EN 61000-6-3
Safety function The safety function will fully open or close the
valve when the power is removed, depending
upon the spring action selected. Valve selection
will also affect the spring action. The safety
function unit is factory fitted to the rear of the
actuator.
0-10 (2 -10)
130
or
=
SU
Note: Do not use safet y activations for
ON/OFF regulation.
Valve t ype
VZ CLOSED
VS OPENED
VM OPENED
VB OPENED
If safety version is activated
than port A-AB will be
2 | VD.AB.U5.02 © Danfoss | 2018.12

Data sheet Actuators for modulating control AME 13SU, AME 23SU
Installation
AME 13 SU
AME 23 SU
Disposal
Mechanical
The actuator should be mounted with the valve
stem in either horizontal position or pointing
upwards.
The actuator is fixed to the valve body by means
of a mounting ring, which requires no tools for
mounting. The ring should be tightened by
hand.
The actuator must be dismantled and the
elements sorted into various material groups
before disposal.
Electrical
Important: It is strongly recommended that the
mechanical installation is completed before the
electrical installation.
Note: Two cable entries are provided for M 16×1.5
cable glands. One entry is provided with a rubber
grommet. Note that in order to maintain the
enclosure’s IP rating, appropriate cable glands must
be used.
VD.AB.U5.02 | 3© Danfoss | 2018.12