Danfoss AME 13 SU Operating guide

Operating Guide
Ste m Trav el
COM
COM
AME 13 SU/SD-1
Travel Speed 11,7 (14) s/mm
MAINTENANCE
FREE
5-95 % RH
no condensing
AME 13 SD-1 +
AB-QM
Washer 003Z0257 Adapter 003Z3960
AME 13 SU-1 +
AB-QM
AUTO
=
=
4 – 6 mm × 1 mm
Do not use as ON/Off actuator.
AME13 SU/SD-1, Modulang
SN SP Y 1 3 X
~ AC 24V 50/60Hz
0(2)-10VDC
0(4)-20mA
+
DC 0-10V
AME13 SU/SD-1, Floang point
SN SP Y 1 3 X
+
~ AC 24V 50/60Hz
DC 0(2)-10V
+
AQ283757724898en-000301 | 1© Danfoss | 2020.03
AME 13 SU/SD-1
Loss of Power
SD
½”
Max. 6 Nm/53 in-lb for AB-QM valves.
Loss of Power
SU
½”
Max. 6 Nm/53 in-lb for AB-QM valves.
AQ283757724898en-000301 2 | © Danfoss | 2020.03
AME 13 SU/SD-1
121 ( 4.76”)
83 (3.27”)
110 (4. 33 ”)
min. 200 (7.87”)
© Danfoss | 2020.03 | 3AQ283757724898en-000301
AME 13 SU/SD-1
ENGLISH
Safety Note
To avoid personal injury and damage to the device or other property, it is necessary to read and follow these
instructions carefully.
Assembly, start-up, and maintenance work must be performed by qualified and authorized personnel.
Comply with the instructions of the system manufacturer or system operator.
Please comply with the instructions of the system manufacturer or system operator.
Do not remove the cover before th e power supply is ful ly switched off.
Disposal
This product shou ld be dismantled and its components sorted, if possible, in various grou ps before
Always follow the local d isposal regulations.
recycling or disposal .
Mounting Position
The actuator should be mounted with the valve stem in either a horizontal position or pointing upwards.
Wiring
AC 24 V
Connect via Class 2 (Nor th America)
or Safety E xtra-Low Voltage (SELV) (Europe). Failure to comply can lead to equipment damage or personal injury.
Switch off power bef ore wiring the
actuator!
1. Make all wiring connections in accordance with local, national, or regional regulations.
2. For applications requiring conduit, a field supplied 1/2” trade size electrician’s fitting and lock nut can be mounted in the actuator enclosure. Use flexible metallic tubing or its equivalent with the field supplied fitting.
3. Insert wiring material through the removable plug or conduit fitting, and connect to the terminal block using the applicable wiring diagram ❷.
Installation
1. Depending on the version of actuator (SU/SD) prior to installation an included washer and adapter is required to be installed: SD, Washer (003Z0257) The washer is placed on the valve neck prior to the installation of the actuator. SU, Adapter (003Z3960) and washer (003Z0257) Hand tighten the adapter to the neck of the valve. The actuator will be installed to the adapter.
2. The actuator should be in the full up position (factory setting). If it is not, refer to the
manual override instructions ❸④.
3. The actuator is fixed to the valve body or adapter by means of a union nut which requires an adjustable wrench to assist in tightening the actuator to the valve.
DIP switch settings
Factory settings: ALL switches are on OFF position! (except SW2 which is in ON position)!
NOTE:
All combinations of DIP switches are allowed. All functions that are selected are added consecutively. There is only one logic override of functionalities i.e. the switch No.6 Propor tional /3 point, which sets actuator to ignore control signal and works as a “simple” 3-point actuator.
SW 1: VDC / mA - Input signal type selector
If set to OFF position, voltage input is selected. If set to ON position, current input is selected.
SW 2: 0/2 - Input signal range selector
If set to OFF position, the input signal is in the range from 2-10 V (voltage input) or from 4-20 mA (current input). If set to ON position, the input signal is in the range from 0-10 V (voltage input) or from 0-20 mA (current input).
SW3: D/I - Direct or inverse acting selector
If set to OFF position, the actuator is direct acting (stem retracts as voltage increases). If the actuator is set to ON position, the actuator is inverse acting (stem extends as voltage increases).
SW4:---/Seq - Normal or sequential mode selector
If set to OFF position, the actuator is working normally in 0(2)-10V or 0(4)-20mA range. If set to ON position, the actuator is working in a sequential mode with its range dependent on the position of SW 4.
SW5: 0-5 V/5-10 V - Input signal range in sequential mode
If set to OFF position, the actuator is working in sequential range 0(2)-5 (6) V or 0(4)-10 (12) mA. If set to ON position, the actuator is working in sequential range; 5(6)-10 V or 10(12)-20 mA
SW6: Proportional/Floating point
If set to ON position, the actuator can operate as Floating point actuator. Power supply should be connected on SN and SP ports. On port 1 or 3 24 VAC signal is connected for rising or lowering of actuator. Return signal X indicates the correct position.
If set to OFF position, the actuator operates on modulating input signal.
NOTE:
if 3 point function is selected actuator does not respond to any control signal on port Y. It only rises and lowers spindle if power is supplied on port 1 or 3.
SW7: LIN/LOG - Linear or equal percentage flow through valve selector
If set to ON position, the flow through the valve is equal percentage to the control signal. If set to OFF position, the valve position is linear acc. to the control signal.
SW8:
Set to ON for valve bodies 1/2” to 1-1/4” HF. The actuator will modulate on max stem travel of
4.5mm. Set to OFF for valve body 1/2” Low flow. The actuator will modulate on max stem travel of
2.5mm.
SW9: Reset
Toggling the switch will cause the actuator to go through an auto-calibration cycle.
Function test
The indicator light shows whether the positioner is in operation or not. Moreover, the indicator shows the control status and faults. Constant light
- normal operation
No light
- no operation or no power supply
Intermittent light (1 Hz)
- self adjusting-mode
Intermittent light (3 Hz):
- power supply too low
- insufficient valve stroke (<20 s)
- end-position cannot be reached.
73694760 / AQ283757724898en-0003014 | © Danfoss | DHS-SMDBT/SI | 2020.03
Loading...