DH-SMT/SI VD.KG. Z1.02 © Danfoss 06/20 06 3
Data sheet Actuators for modulating control AME 130, AME 140, AME 130H, AME 140H
DIP Switch Setting
(for service purposes only)
The actuator has a function selection DIP switch
under the removable cover.
The switch provides the following functions:
• SW1:
Reset
Changing this switch position will cause the
actuator to go through a self stroking cycle.
• SW2:
0/2 - Input signal range selector
If set to OFF position, the input signal is in the
range from 2 V … 10 V (voltage input) or from
4 mA … 20 mA (current input). If set to ON
position, the input signal is in the range from
0 V … 10 V (voltage input) or from
0 mA … 20 mA (current input).
• SW3:
D/I - Direct or inverse acting selector
If set to OFF position, the actuator is direct
acting (stem lowers as voltage increases). If
the actuator is set to ON position, the actuator
is inverse acting (stem raises as voltage
increases).
• SW4:
---/Seq - Normal or sequential mode
selector:
If set to OFF position, the actuator is working
in range 0(2)..10V or 0(4)..20mA. If set to ON
position, the actuator is working in sequential
range; 0(2)..5 (6)V or (0(4)..10 (12)mA) or
(5(6)..10V) or (10(12)..20mA).
• SW5:
0 … 5 V/5 … 10 V - Input signal range in
sequential mode:
If set to OFF position, the actuator is working
in sequential range 0(2)..5 (6)V or 0(4)..10 (12)mA.
If set to ON position, the actuator is working
in sequential range; 5(6)..10V or 10(12)..20mA.
• SW6:
U/I - Input signal type selector
If set to OFF position, voltage input is
selected. If set to ON position, current input is
selected.
Manual override
(for service purposes only)
AME 130, AME 140
1 Remove the cover.
2 Insert the Allen key 6 into the spindle.
3 Press and hold the button (on the bottom
side of the actuator) during manual override.
4 Pull out the tool.
5 Place cover back on the actuator.
Caution:
Do not manually operate the
drive under power!
Remark:
A ”click” sound after energizing the actuator
means that the gear wheel has jumped into
normal position.
If manual override has been used, then Y
signal is not correct until the actuator reaches
it’s end position. If this is not accepted, reset
the actuator.
push