Danfoss AME 11 Data sheet

Data sheet
Modulating controlled actuator AME 11
Description
Technical data
In addition to basic function such as manual control and position indication, the actuators are also equipped with force sensitive switch-off to ensure that actuators and valves are not exposed to overloading.
Main data:
• Nominal voltage: 24 Vac
• Force: 300 N
• Speed: 7 s/mm
• Max. medium temperature: 130 °C + adapter (150 °C)
• End-position signals
The actuator is available for the modulating controllers with the control Y signal. It is used with VS2, VM2, VB2, VMV and AVQM valves.
Actuators
Typ e Supply voltage Code No.
AME 11
Power supply Vac 24; +10 to –15 %
Power consumption VA 4.4
Frequency Hz 50/60
Control input Y
Output signal X Vdc 0 -10 (2-10)
Closing force N 300
Max. stroke mm 7
Speed s/mm 7
Max. medium temperature
Ambient temperature 0 … 55
Storage and transport temperature –40 … 70
Ambient humidity 5-95 % r.h., non-condensing
Protection Class II
Grade of enclosure IP 54
Weight kg 0.6
- marking in accordance with standards
24 V
082G3034
Vdc 0-10 (2-10) Ri = 24 kΩ
mA 0-20 (4-20) Ri = 500 Ω
°C
Low Voltage Directive (LVD) 2014/35/EU: EN 60730-1, EN 60730-2-14 Electromagnetic Compatibility Directive (EMC) 2014/30/EU: EN 61000-6-2,EN 61000-6-3
Note:
The use of AME ac tuators together with V S2 DN 15 is not recommenda ble. Linear character istics as in VS2 DN 15 valves is not recommendable in DHW production.
Accessories
Typ e Code No.
High temperature adapter (150°C) 065Z 7547
130 ( 150 with adapter)
© Danfoss | 2018.12 VD.AB.K6.02 | 1
Data sheet AME 11
Installation
Disposal The actuator must be dismantled and the
elements sorted into various material groups before disposal.
Mechanical
The actuator should be mounted with the valve stem in either horizontal position or pointing upwards.
The actuator is fixed to the valve body by means of a mounting ring, which requires no tools for mounting. The ring should be tightened by hand.
Electrical
Important: It is strongly recommended that the mechanical installation is completed before the electrical installation.
Note: Two cable entries are provided for M 16×1.5 cable glands. One entry is provided with a rubber grommet. Note that in order to maintain the enclosure’s IP rating, appropriate cable glands must be used.
Commissioning
Complete the mechanical and electrical installation and perform the necessary checks and tests:
• Isolate control medium. (e.g. self-adjusting in a steam application without suitable mechanical isolation could cause a hazard).
• Apply the power. Note that the actuator will now perform the self-adjusting function.
• Apply the appropriate control signal and check the valve stem direction is correct for the application.
• Ensure that the actuator drives the valve over its full stroke, by applying the appropriate control signal. This action will set the valve stroke length.
The unit is now fully commissioned.
Commissioning / testing feature
The actuator can be driven to the fully open or closed positions (depending on valve type) by connecting SN to terminals 1 or 3.
2 | VD.AB.K6.02 © Danfoss | 2018.12
Data sheet AME 11
Manual Override
The manual override is achieved by turning the manual knob to the required position. Observe the direction of rotation symbol.
If manual override has been used then X and Y signal are not correct until the actuator reaches its end position. If this is not accepted reset the actuator.
• Disconnect power supply
• Adjust valve position using control knob
• Set valve to closed position
• Restore power supply
CLOSE OPEN
A
OPEN CLOSE
B
VD.AB.K6.02 | 3© Danfoss | 2018.12
Data sheet AME 11
DIP switch setting
I
0 …--- V
Inverse
Sequential
5(6) … 10 V
U
- - -
Direct
2 …--- V
0(2) … 5(6) V
3 point/RL
Proportional
Reset
LIN fl ow
Red . Kvs
Reset
LOG f low
100 % Kvs
The actuator has a selection of DIP switches under the removable cover. The switch provides the following functions:
DIP1: U/I - Input signal type selector:
If set to OFF position, input signal Y is set to
voltage (Y).
If set to ON position, input signal Y is set to be
current (mA).
DIP2: 0/2 - Input signal range selector:
If set to OFF position, the input signal is in the
range from 2 V to 10 V (voltage input) or from 4 mA to 20 mA (current input). If set to ON position, the input signal is in the range from 0 V to 10 V (voltage input) or from 0 mA to 20 mA (current input).
DIP3: D/I - Direct or inverse acting selector:
If set to OFF position, the actuator is direct
acting (actuator’s stem extends by voltage increase). If actuator is set to ON position the actuator is inverse acting (actuator’s stem retracts by voltage increase).
DIP4: —/Seq - Normal or sequential mode
selector:
Two actuators can be set to work parallel with
one control signal. If the SEQUENTIAL is set than an actuator responds to split control signal (see 0(2) V … 5(6 V) / 5(6) V … 10 V).
NOTE: This combinatio n works in combination with D IP 5:
0(2)V… 5(6 V) / 5(6) V … 10 V
DIP5: 0-5 V/5-10 V - Input signal range in
sequential mode:
This function is available if switch
DIP4:---/Sequential is set. Actuator can be set to match the range of the control signal:
2 … 6 V (DIP 2: 2 V … 10) 0 … 5 V (DIP 2: 0 V … 10) 4 … 12 mA (DIP 2: 2 V … 10) 0 … 10 mA (DIP 2: 0 … 10)
OR 6 … 10 V (DIP 2: 2 V … 10) 5 … 10 V (DIP 2: 0 V … 10) 12 … 20 mA (DIP 2: 2 V … 10) 10 … 20 mA (DIP 2: 0 … 10)
DIP6: Prop./3-pnt - Modulating or 3-point
mode selector:
Actuator can operate in modulating (DIP 6
to OFF) or in “simple” 3-point mode, if the 3-point function is selected (DIP 6 to ON).
Modulating mode; DIP 6 set to OFF
(factorysetting)
After the actuator has been connected to power supply, the actuator will start the
self-adjustment procedure. The indicator LED
flashes until self-adjustment is finished.
Actuator’s stem will run to its totally extended or retracted position by bridging SN signal to terminals 1 or 3 and will remain in this positron as long as potential is present.
It is not allowed to bridge SP to terminal 1
or 3 when DIP 6 is set to OFF .
3-point mode; DIP 6 set to On Look carefully wiring diagrams as wiring is
different for controllers with triacs output (ECL) in comparison to controllers with relay output.
• Connect SN (Neutral) and power supply (24Vac) via controller to terminals 1 or 3.
Return signal X (depends on DIP 2, 3, 4 & 5) is possible if connected power supply to SP and SN.
SW7: LOG/LIN - Not in use.
SW8: 100 % KVS/Reduced KVS - Not in use.
SW9: Reset:
Changing this switch position will cause the
actuator to go through a self-adjustment procedure.
4 | VD.AB.K6.02 © Danfoss | 2018.12
Data sheet AME 11
Wiring
24 Vac only.
Actuator ne eds to perform Self- adjusting prior chang ing DIP 6 to ON. Output signa l depends on DIP 2, 3&5 setting.
DIP 6 = OFF
DIP 6 = ON
Wiring for modulating mode
SN 0 V Neutral
SP 24 Vac Power supply
Y
1
3
X 0(2)-10 Vd c Output
0(2)-10 Vac
0(4) -20 mA
SN Input
Wiring for 3-point floating mode / Controller with relay output
SN 0 V Neutral
SP 24 Vac Power supply
1
SP Input
3
Input
* Only for ac tuators with safety fu nction
*R1, *R2=2.6 k Ω (0.5W)
DIP 6 = ON
Wiring for 3-point floating mode / Controller with triacs output
Automatic self-adjustment feature
When power is first applied, the actuator will automatically adjust to the length of the valve stroke. Subsequently, the self-adjustment feature can be re-initialised by changing position of SW9.
Wiring length
0-50 m 0.75 mm
> 50 m 1.5 mm
Recommended
square of the wiring
2
2
X 0(2)-10 Vd c Output
SN 0 V Neutral
SP 24 Vac Power supply
1
SP Input
3
X 0 (2)-10 Vd c Output
Diagnostic LED
The red diagnostic LED is located on the pcb under the cover. It provides indication of three operational states:
• Actuator Healthy (Permanently ON),
• Self-adjusting (Flashes once per second),
• Error (Flashes 3 times per second - seek technical assistance).
VD.AB.K6.02 | 5© Danfoss | 2018.12
Data sheet AME 11
Dimensions
Actuator - valve combinations
121 83
55.5
107
min. 200
AME 11 + AME 11 + AME 11 + AME 11 + VS 2 (DN 15 - 25) VB 2 (DN 15 - 25) VMV (DN 15 - 40) AVQM (see AVQM data sheet) VM 2 (DN 15 - 32)
* The use of AME actuators together with VS2 DN 15 is not recommendable. Linear characteristics as in VS2 DN 15 valves is not recommendable in DHW production.
6 | VD.AB.K6.02 © Danfoss | 2018.12
Data sheet AME 11
VD.AB.K6.02 | 7© Danfoss | 2018.12
Danfos produc Al
Danfoss A/S
Heating Segment
Data sheet AME 11
s can accept no responsibility for possible errors in catalogues, brochures and o ther printed material. Danfoss reserves the right to alter its pro ducts without notice. This also applies to ts already on order provided that such alterations can be m ade without subsequential changes being necessary in specications already agreed.
l trademarks in this material are property of the r espective companies. Danfoss and all Danfoss logotypes are t rademarks of Danfoss A/S. All rights reserved.
heating.danfoss.com +45 7488 2222 E-Mail: heating@danfoss.com
© Danfoss | DHS-SRMT/SI | 2018.128 | VD.AB.K6.02
Loading...