AMD 610, 610 AS, AMD 620, 620 AS
AMD 710, 710 AS, AMD 720, 720 AS
AMD 810, 810 AS, AMD 820, 820 AS
Description
AMD actuators are used for the regulation of
air dampers of 90° angle of rotation to be used
in heating, ventilation and air conditioning
applications (HVAC).
Features:
• Manual operation
• Rotation direction selection by switch
• Adjustable angle of rotation by mechanical
end stop.
• Position indication
• Overload protection
• Direct mounting with universal spindle clamp
• Anti-rotation strap for preventing actuator
from rotating
• Maintenance free
Main Data:
• Nominal voltage (AC or DC)
- 230 V, 50/60 Hz
- 24 V, 50/60 Hz
• Control Input signal: modulating or 2/3 point
(depend on wiring)
Data sheet Actuators for dampers AMD 610(AS),620(AS), 710(AS), 720(AS), 810(AS), 820(AS)
Technical data
Note:
* depend on wiring
** at distance 1m
Operating mode
Typ e
Power supplyV24 AC/DC or 230 AC/DC ± 20%
Power consumption in motion
Power consumption in Stand by
(end p osition)
FrequencyHz50/60
Control Input
Operating torqueNm203040203040
Rotation angle0...max 95°
Ambient temperature
Ambient humidity: 5...95% r.F., non- condensating (EN 60730 -1)
Storage and transport temperature−30 … 80
Protection ClassIII (24V) / II (230V)
Rated impulse voltage: kV
Grade of enclosure / Degree of protection
Sound power level motor: **
Weightkg1,7
marking in accordance with standards
610/610 AS
(24V/ 230V)
W
V
mA0-20 (4-20) Ri = 500Ω
°C
dB(A)
Low voltage directive (LVD) 2006/95/EC: EN 60730-1, EN 60730-2-14
EMC Directive 2004/108/EC: EN 61000-6 -2, EN 61000-6-3 RoHS CE (2011/65/EU)
Valid for: AMD 610, 610AS, 710, 710AS, 810, 810AS
2- point.
Through connecting the power supply to BU+BN
(1+2) and the direction of rotation switch on
position “R” moves the actuator to position 1. Is
also BK (1+2+3) connected to the power supply
the actuator is moving to position 0.
710/710AS
(24V/ 230V)
3
4,5 (24V)
4 (230V)
2/3 point *modulating
24V 0,8 (EN 60730-1)
230V 4 (EN 60730-1)
810/810A S
(24V/ 230V)
/
620/620AS
(24V)
5,534,57
1,52
−30 … 50
IP 54
< 45
Valid for: AMD 620, 620AS, 720, 720AS, 820, 820AS
Through connecting the power supply to
BU+BN (1+2) and a reference signal Y to BK (3) of
0(2)…10VDC, moves the actuator to its specied
position. The actual damper position 0…100%
is a feedback signal U for example to share the
signal with other actuators.
720/720AS
(24V)
0-10 (2-10) Ri = 100 kΩ
0,8 (EN 60730-1)
820/820AS
(24V)
3- point.
Through connecting the power supply to BU+BN
(1+2) and the direction of rotation switch on
position “R” moves the actuator to position 1.
If the power supply is interrupted the actuator
maintains its current position. Is also BU+BK (1+3)
connected to the power supply the actuator is
moving in direction 0.
The actuator is overload-proof, requires no limit
switches and automatically stops when the end
stop is reached.
Direct mountingSimple direct mounting on the damper spindle
with a universal spindle clamp, supplied with an
anti-rotation strap to prevent the actuator from
rotating.
Manual operation
Manual operation is possible with the selfresetting pushbutton (the gearing latch remains
disengaged as long as the pushbutton is pressed)
Rotary direction switch
Valid for AMD:
(610, 610AS, 710, 710AS, 810, 810AS)
The actuator is overload-proof, requires no limit
switches and automatically stops when the end
stop is reached.
Anschlussschema/ connection scheme/ schema de connexion/ schema di collegamento/ es
quema de conexiones:
1
2
3
Mode- switch
Valid for AMD:
(620, 620AS, 720, 720AS, 820, 820A S)
Adaption drive (Adp)
Valid for AMD:
(620, 620AS, 720, 720AS, 820, 820A S)
Auxiliary switches
Valid for AMD:
(610AS, 620AS, 710AS, 720AS, 810AS, 820AS)
DIP-Switch under the case cover
-Adaption on angle of rotation < 90°
-Actuator power-o
-Setting the mechanical end stops
-Actuator power-on
-Adaption to enable
-Actuator adaption on angular range
-Adaption to disable
-“Y” refers to the measured angular range
Installation
Dimensions
DEN-SMT/SI
The actuators should be mounted in a dry
anvironment, absolutely free from acrid fumes.
In case of outdoor installation, the actuator has
to be protected against climatic inuences by
suitable measures.