Danfoss AMD 413, AMD 413 AS, AMD 423, AMD 423 AS Data sheet

Data sheet
Actuators for dampers (with spring return)
AMD 413, 413 AS, AMD 423, 423 AS
Description AMD actuators are used for the regulation of
air dampers of 90° angle of rotation to be used in heating, ventilation and air conditioning applications (HVAC).
Features:
• Spring return function
• Manual operation
• Rotation direction selection by switch
• Adjustable rotation angle by mechanical end stop min 35°.
• Position indication
• Overload protection
• Direct mounting with universal spindle clamp
• Anti-rotation strap for preventing actuator from rotating
• Maintenance free
Ordering
Note:
* Actuator with built-in auxiliary switches
** D amper size:
damper size:
a
b
S=a×b
S=π×r
r
2
Working cycles
Main Data:
• Nominal voltage (AC or DC):
230 V, 50/60 Hz 24 V, 50/60 Hz
• Control Input signal: modulating or 2 point (depend on wiring)
• Torque: 10 Nm
• Rotation angle: 0- max. 95°
• Running time motor 75…150 s /90°
• Running time spring 20 s /90°
Typ e
AM D 413
AMD 413 AS 24 VAC /DC 2 aux. Switches * 08 2H11 49
AM D 413 230 VAC/ DC - 08 2H11 50
AMD 413 AS 230 VAC/ DC 2 aux. Switches * 08 2H115 1
AMD 42 3
AMD 423 AS 24 VAC/DC 2 aux. Switches * 0 82H 1153
2-point >60.000 cycles (0°-95°-0°)
modulating
Torque
(Nm) (s/90°) (V)
Control
signal
2-point
10
modulating
>60.000 cycles (0°-95°-0°)
>1.000.000 partial cycles (±5°)
Speed Supply voltage
24 VAC /DC -
75 s motor /
20 s spring
150 s motor /
20 s spring
24 VAC /DC - 08 2H115 2
Auxiliary
switch
Max. da mper size
(m2)
2 **
Code No.
08 2H11 48
DEN-SMT/SI
VD.IR.D2.02 © Danfoss 03/2015
1
Data sheet Actuators for dampers AMD 413(AS),423(AS)
Technical data
Note:
* at distance 1m
Operating mode Valid for: AMD 413, 413AS
Typ e
Power supply V 24 AC/DC or 230 AC/DC ± 20%
Power consumption in motion
Power consumption in Stand by (end p osition)
Frequency Hz 50/60
Control Input
Operating torque Nm 10
Rotation angle 0...max 95°
Ambient temperature
Ambient humidity: 5...95% r.F., non- condensating (EN 60730 -1)
Storage and transport temperature −30 … 80
Protection Class III (24V) / II (230V)
Rated impulse voltage: kV 0,8 (EN 60730-1) 4 (EN 60730-1) 0,8 (EN 60730-1)
Grade of enclosure / Degree of protection
Sound power level motor: * dB(A) < 45 motor / < 65 spring < 35 motor / < 65 spring
Weight kg 1,8
marking in accordance with standards
W
- 2 point modulating
V
mA 0-20 (4-20) Ri = 500Ω
°C
Valid for: AMD 423, 423AS
Through connecting the power supply to BU+BN (1+2) and a reference signal Y to BK (3) of 0(2)…10VDC, moves the actuator to its specied position. The actual damper position 0…100% is a feedback signal U for example to share the signal with other actuators. If the power supply is interrupted the actuator is moving to position 0
413/413AS
(24V)
5 5,5 5
2 1,5 2
Low voltage directive (LVD) 2006/95/EC: EN 60730-1, EN 60730-2-14 EMC Directive 2004/108/EC: EN 61000-6 -2, EN 61000-6-3 RoHS CE (2011/65/EU)
413/413AS
(230V)
/
−30 … 50
IP 54
Through connecting the power supply to BU+BN (1+2), the actuator moves to position 1 while the pre-tensioned spring is wound up the same time. If the power supply is interrupted the actuator is moving back to position 0 by the spring power. The actuator is still maintaining the minimum
torque at the damper spindle. by spring power. The actuator is still maintaining the minimum torque at the damper spindle
The actuator is overload-proof and requires no
end switches. It automatically stops when the The actuator is overload-proof and requires no
end stop is reached. end switches. It automatically stops when the end stop is reached.
423/423AS
(24V)
0-10 (2-10) Ri = 100 kΩ
Direct mounting Simple direct mounting on the damper spindle
with a universal spindle clamp, supplied with an anti-rotation strap to prevent the actuator from rotating.
Manual operation The actuator can be operated only manually
while the power supply is o. The supplied lever is to open and lock the damper position. The lock stays until the power supply is put on.
Mode- switch
Valid for AMD: (423, 423AS)
2
DIP-Switch under the case cover
VD.IR.D2.02 © Danfoss 03/2015
DEN-SMT/SI
Loading...
+ 2 hidden pages