Danfoss AK-XM 205B Installation guide

Danfoss AK-XM 205B Installation guide

Instructions

AK-XM 205B

080Z0017

AK-XM 205B

-20°< tamb < 55°C17

-0°F < tamb < 130°F

0 - 95% RH, non condensing IP10 / VBG4

UL: E357029

AI x 8

max. 10 V

DO x 8

 

Keep the safety distance Low and high voltage must not be connected to the same output group

Max. 230 V

AC-1: max. 4 A (ohmic)

AC-15: max. 3 A (Inductive)

RI8HM602    09-2018

Point

 

 

Override (off / Auto / on)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminal 9:

12 V

Terminal10:

5 V

Terminal 21:

12 V

Terminal 22:

5 V

Terminal 11, 12, 23, 24 :

 

Signal

Signal

 

 

 

 

 

 

type

Address

 

 

 

 

 

 

 

 

 

S (sensor)

S1

 

 

 

 

 

 

 

 

 

 

 

Pt 1000 ohm/0°C

S2

Pt 1000

 

 

 

 

 

Saux1

 

 

 

 

 

Saux2

 

 

 

 

 

 

SSA

 

(Communication module)

 

 

 

SdA

 

 

 

 

 

P (pressure)

 

 

 

 

 

 

AKS 32R

 

 

 

 

 

 

AKS 2050

 

AKS 32R

 

 

 

 

 

 

 

 

 

 

 

P0A

AKS 2050

 

 

 

 

 

P0B

MBS 8250

 

 

 

 

 

PcA

-1 - xx bar

(Controller)

 

 

 

 

PcB

 

 

 

 

 

 

 

 

 

 

AKS 32

Paux

AKS 32

 

 

 

 

 

 

-1 - zz bar

 

 

 

 

 

 

Signal

Signal type /

Module

Point

Terminal

 

 

 

Active at

 

 

 

U (voltage)

 

 

 

 

1 (AI 1)

1 - 2

 

 

 

 

2 (AI 2)

3 - 4

 

 

 

 

 

 

 

0 - 5 V

 

 

3 (AI 3)

5 - 6

 

...

0 - 10 V

 

 

 

 

 

4 (AI 4)

7 - 8

 

 

 

 

 

 

 

 

 

 

5 (AI 5)

13 - 14

 

 

 

 

 

6 (AI 6)

15 - 16

On/Off

Ext.

Active at:

 

 

7 (AI 7)

17 - 18

 

Main

 

 

8 (AI 8)

19 - 20

 

 

 

 

 

switch

 

 

 

 

Closed

 

 

9 (DO 1)

25-26-27

 

 

 

 

 

 

/

 

 

 

Day/

 

 

10 (DO 2)

28-29-30

 

Open

 

 

 

Night

 

 

 

11 (DO 3)

31-32-33

 

 

 

 

 

 

Door

 

 

 

12 (DO 4)

34-35-36

 

 

 

 

 

13 (DO 5)

37-38-39

DO

Comp 1

Active at:

 

 

14 (DO6)

40-41-42

 

Comp 2

ON

 

 

15 (DO7)

43-44-45

 

 

 

16 (DO8)

46-47-48

 

 

/

 

 

 

Fan 1

OFF

 

 

 

 

 

Alarm

 

 

 

 

 

 

 

 

 

The Product contains electrical components

 

 

 

 

And may not be disposed together with domestic waste.

 

 

 

 

Equipment must be separate collected with Electrical and Elec-

 

 

 

 

tronic waste. According to Local and currently valid legislation.

2

Instructions  RI8HM602  ©  Danfoss  09/2018