Danfoss AK-XM 103A Data sheet

Technical Brochure
Extension module 4AI + 4AO
AK-XM 103A
ADAP-KOOL® Refrigeration control systems
Introduction
The extension module should be used with a controller in the same serial connection if there is not enough connections on the controller itself.
Function
The module contains:
• 4 analog inputs for temperature sensors, pressure transmitters, voltage signals and contact signals.
• Four analogue outputs (0-10 V) for speed control of e.g. frequen­cy converters
Installation
• The module is connected to the plug from the previous module in the sequence.
Supply voltage
The supply voltage to the module comes from the previous mod­ule in the row. Supply voltage to a pressure transmitter can be taken from either the 5 V output or the 12 V output depending on transmitter type.
Light-emitting diodes
Only the two top LED’s are used. They indicate the following:
• Voltage supply to the module
• Communication with the controller is active (red = error)
Galvanic isolation
There are three groups, and the signals should not be mixed up:
• Inputs and 5V and 12V supplies for the signals connected to the
inputs.
• Output 1 and 2
• Output 3 and 4
Connections
Max. 10 V
Max. 2.5 mA / AO
2 Technical brochure RD8BS202 © Danfoss 2018-11 AK-XM 103A