Danfoss AK-XM 103A Data sheet

Technical Brochure
Extension module 4AI + 4AO
AK-XM 103A
ADAP-KOOL® Refrigeration control systems
Introduction
The extension module should be used with a controller in the same serial connection if there is not enough connections on the controller itself.
Function
The module contains:
• 4 analog inputs for temperature sensors, pressure transmitters, voltage signals and contact signals.
• Four analogue outputs (0-10 V) for speed control of e.g. frequen­cy converters
Installation
• The module is connected to the plug from the previous module in the sequence.
Supply voltage
The supply voltage to the module comes from the previous mod­ule in the row. Supply voltage to a pressure transmitter can be taken from either the 5 V output or the 12 V output depending on transmitter type.
Light-emitting diodes
Only the two top LED’s are used. They indicate the following:
• Voltage supply to the module
• Communication with the controller is active (red = error)
Galvanic isolation
There are three groups, and the signals should not be mixed up:
• Inputs and 5V and 12V supplies for the signals connected to the
inputs.
• Output 1 and 2
• Output 3 and 4
Connections
Max. 10 V
Max. 2.5 mA / AO
2 Technical brochure RD8BS202 © Danfoss 2018-11 AK-XM 103A
Data
Supply voltage Received from the AK controller, which the extension module is connected to
Power consumption 2 VA
Analog inputs Pt 1000 ohm /0°C Resolution: 0,1°C
Pressure transmitter type AKS 32R / AKS 32 (1-5 V)
Voltage signal 0-10 V
Contact function (On/Off ) On at R < 20 ohm
Analog outputs Voltage signal 0-10 V
Max. load I < 2.5 mA
Supply for pressure transmitters 5 V
12 V
Galvanic isolation 3 groups AI 1-4
Environment During transport -40 to 70°C
During operation -20 to 55°C ,
Enclosure Material PC / ABS
Density IP10 , VBG 4
Accuracy: +/- 0,5°C
Resolution 1 mV Accuracy +/- 20 mV
Off at R > 2K ohm (Gold -plated contacts not necessary)
R > 4 Kohm
Max. 25 mA Max. 100 mA
AO 1-2 AO 3-4
0 to 95% RH (non condensing) No shock influences / vibrations
Mounting For mounting on panel wall or DIN rail
Weight with screw terminals Ca. 200 g
Approvals EU low voltage directive and EMC require-
ments are complied with
UL 916,
Dimensions
LVD tested according to EN 60730 EMC tested Immunity according to EN 61000-6-2 Emission according to EN 61000-6-3
UL file number: E357029
Ordering
Type Application Function Code no.
AK-XM 103A Extension module for control-
ler in the AK-series
4 Analog inputs.
For sensors, pressure transmitters etc.
4 Analog outputs
0 -10 V d.c.
080Z0032
AK-XM 103A Technical brochure RD8BS202 © Danfoss 2018-11 3
Point
Terminal 9: 12 V Terminal 10: 5 V
Terminal 11, 12:
Terminal 2, 4, 6, 8: GND-AI 1-4 Terminal 17, 19: GND-AO 1+2 Terminal 21, 23: GND-AO 3+4
Galvanic isolation: AI 1-4 ≠ AO 1-2 ≠ AO 3-4
Signal Signal
AI
S (sensor)
Pt 1000 ohm/0°C
S1 S2 Saux1 Saux2 SSA SdA
P (pressure)
AKS 32R
P0A P0B PcA
AKS 32
PcB
U (voltage)
...
On/Off Ext.
Main switch
Day/ Night
Door
type
Pt 1000
AKS 32R AKS 2050 MBS 8250
-1 - xx bar
AKS 32
-1 - zz bar
0 - 5 V 0 - 10 V
Active
at:
Closed
/
Open
Address
(Communication module)
Signal Signal type /
Active at
(Controller)
Module Point Terminals
1 (AI 1) 1 - 2
2 (AI 2) 3 - 4
3 (AI 3) 5 - 6
4 (AI 4) 7 - 8
5 (AO 1) 17 - 18
6 (AO 2) 19 - 20
7 (AO 3) 21 - 22
8 (AO 4) 23 - 24
AO
0-10 V
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
4 Technical brochure RD8BS202 © Danfoss 2018-11 AK-XM 103A