Installation guide
Electric expansion valve
Types AKVO 10 – 1 to AKVO 10 – 6
<![if ! IE]> <![endif]>068R9806 |
Refrigerants |
|
|
|
Max. working pressure: |
Max. test pressure: |
|
|
|
|
|
||||
|
R744, R22/R407C, R404A/R507, R410A, R134a, R407A, R23. |
|
PS/MWP = 28 barg (410 psig) |
Pe = 42 barg (610 psig) |
|||
|
For other refrigerants, please contact Danfoss. |
|
|
|
|
||
|
|
|
|
|
|
||
|
Max. differential pressure: |
Media temperatur range: |
Ambient temperatur range: |
||||
|
MOPD = 18 bar (260 psi) |
-50 |
°C < t media < 60 °C |
-50 |
°C < tamb < 50 °C |
|
|
|
|
-58 |
°F < t media < 140 °F |
-58 |
°F < t amb < 120 °F |
|
|
|
|
|
|
|
|
|
|
10 mm (3/8 in.)
64 mm (2 1/2 in.)
12 mm (1/2 in.)
64 mm (2 1/2 in.)
max. 150 °C (300 °F)
Min. 5% Ag
<![endif]>068R9806
© Danfoss A/S (AC-MCI / sw), 2013-12 |
DKRCC.PI.VA1.E4.53 / 520H8345 |
1 |
UL approved Coil
(en-gb) Do not insulate
(da) |
Må ikke isoleres |
(de) |
Nicht isolieren |
(fr) |
Ne pas isoler |
(es) |
No encerrar para |
|
evitar condensación |
<![endif]>Danfoss 68F748.10
Standard Coil
<![if ! IE]><![endif]>Danfoss 68F610.10
O-ring must be in place
Warning
Never switch on power to the coil when the coil is dismounted from the valve. Otherwise the coil may be damaged and there is risk of injuries and burns.
2 |
DKRCC.PI.VA1.E4.53 / 520H8345 |
© Danfoss A/S (AC-MCI / sw), 2013-12 |