Danfoss AKVH 10-n Installation guide [da]

Installation Guide
Electrically Operated Expansion Valve Types AKVH 10-n (n= 0 – 6)
068R9820
068R9820
A
B
(en-gb) In solder
(da) Ind lodde
(de) Eintritt / L öt
A
(fr) Raccord d ’entrée à braser
(es) Conector d e Entrada
(en-gb) Out solder
(da) Ud lodde
(de) Austrit t / Löt
B
(fr) Raccord de s ortie à braser
(es) Conector de Salida
3
/8 in.
(10 mm)
1
/2 in.
(12 m m)
AKVH 10 –
c 75
d 67
AKVH 10-2 , AKVH 10-3, AKVH 10- 4, AKVH 10-5 ,
AKV H 10-6
max. 150 °C (300 °F)
© Danfoss A/S (AC-MCI / jmn), 2012-12 DKRCC.PI.VA1.G4.53 / 520H7238 1
Ambient temperature range:
-50 °C < t
-58 °F < t
< 50 °C
amb
< 120 °F
amb
Media temperature range
-50 °C < t
-58 °F < t
< 60 °C
media
< 140 °F
media
(en-gb) Do not insulate (da) Må ikke isoleres (de) Nicht isolieren (fr) Ne pas isoler (es) No encerrar para evitar condensación
Note: If operated consistently at or near MOPD,
the service interval will decrease.
Clip-on coil
Refrigerants
Max. working pressure
Max. test pressure PT = 129 barg / 1870 psig
Max. dierential pressure
A B
R744, R22/R4 07C , R404A/R507, R410A, R13 4a, R407A, R23. For other refrigerants, please contact Danfoss.
AKVH 10-0
AK VH 10 -1
AKV H 10-2
AKV H 10-3
AKV H 10-4
AKV H 10-5
AKV H 10-6
PS = 90 barg / MWP = 1305 psig
MOPD = P
= 35 bar / 505 psi
- P
1
2
45 Nm
75 Nm
Warning
Never switch on power to the coil when the coil is dismounted from the valve. Otherwise the coil may be damaged and there is risk of injuries and burns.
en-gb da de fr es
The gasket must be exchanged, if the valve is dismantled
New A: Ny A: Neu A: Neuf A: Nueva
A:
Pakningen skal skiftes, hvis ventilen adskilles
Bei Zerlegung des Ventils muß die Dichtung usge wechselt werden.
Changer le joint chaque fois que la vanne est démontée
Es preciso cambiar la junta si se desmonta la válvula
B: Used B: Brugt B: Gebraucht B: Usagé B: Usado
2 DKRCC.PI.VA1.G4.53 / 520H7238 © Danfoss A/S (AC-MCI / jmn), 2012-12
Loading...