Danfoss Akva Lux II VX H2WP Fact sheet

Fact Sheet

Akva Lux II VX H2WP

District heating substation for single-family, semi-detached and terraced houses

FEATURES AND BENEFITS

•• Substation for large single-family houses

•• Indirect heating, DHW heating based on flow principle

•• Electronic control of heating (HE) temperature

•• Innovative, energy-saving controller PTC2+P in combination with high performance heat exchanger for on-demand water heating without no-load losses

•• Capacity: 20-30 kW HE/ 41-53 kW DHW

•• Pipes connection in top or bottom of substation = Savings in installations costs

•• Pipes and plate heat exchanger made of stainless steel

•• Minimized risk of lime scale and bacteria formation

Application

The Akva Lux II VX H2WP is a substation featuring high performance and simple operation. The Akva Lux II VX H2WP is especially suitable for two-pipe systems and systems with floor heating. The substation is available in several capacity variants.

District heating (DH)

The substation is prefabricated with interconnecting components such as fitting piece and sensor pockets for insertion of a heat meter, as well as strainers, ball valves, thermometers and pockets for pressure gauges.

Heating (HE)

The heating side features a pleate heat exchanger and two heating circuits. The radiator heating circuit consists of a safety valve, non-return valve, manometer, thermometers, strainer, expansion vessel, ball valves, multifunctional control valve, actuator and circulation pump, and the floor heating circuit consists of a non-return valve, thermometers, safety thermostat, strainer, ball valves, threeway valve, actuator and circulation pump. The temperature for the heating circuits is controlled by an electronic

temperature controller with an outdoor temperature sensor. Depending on substation’s application, different heat exchangers dimensioned for central or floor heating can be used.

Domestic hot water (DHW)

The domestic hot water is prepared in a heat exchanger based on the flow principle and the temperature is regulated by the selfacting controller with integrated differential pressure controller - the PTC2+P with esaveTM function. Supreme ease of operation is obtained via the combined hydraulic and thermostatic regulation of the PTC2+P controller. The pressure-controlled part allows primary and secondary side flow through the heat exchanger, only when hot water is tapped and blocks the flow immediately after completion of the tapping process. The thermostatic part controls the domestic hot water temperature. Thanks to the quickacting hydraulic control of the heat exchanger, it is largely protected from the formation of lime scale and growth of bacteria. The PTC2+P controller with integrated differential pressure controller compensates for variations in supply tem-

perature and varying differential pressure and thereby ensures a constant domestic hot water temperature at all times. A thermostatic bypass enables tapping of hot water without any delay,

– ensuring the best possible efficiency and economy. The cold water connection includes a combined ball valve/ non-return valve and safety valve.

Domestic hot water recirculation

The Akva Lux II VX H2WP is equipped with bypass function as a standard, but it is prepared for DHW recirculation. Switching to DHW recirculation is possible from a constructional point of view, requiring only mounting of a separate circulation set (see options). Equipment for DHW recirculation is optional and must be ordered separately.

Construction

All pipes are made of stainless steel. The connections are made by nuts and gaskets. The substation offers variable connection possibilities, as connection of pipes can be established both in the top or in the bottom of the substation. The Akva Lux II VX H2WP can be delivered with white-lacquered steel cover, with door.

heating.danfoss.com

Danfoss Akva Lux II VX H2WP Fact sheet

CIRCUIT DIAGRAM – EXAMPLE

 

 

 

1

Plate heat exchanger HE

10

Circulation pump FH

2

Plate heat exchanger DHW

11

Safety valve HE

5

Strainer

12

Safety valve DHW

6

Non-return valve

13

Thermometer

7

Ball valve

14

Pocket for pressure gauge

8

Circulation pump HE

15

Manometer

 

 

16

Expansion vessel

 

 

23

Sensor pocket for heat meter

DHW

FH

24

Fitting piece for heat meter

 

Supply

 

3/4” x 110 mm

 

 

25

Controller Danfoss ECL210/A260

 

FH

26

Outdoor sensor, ESMT

 

27

Sensor Danfoss, ESMC

 

Return

DCW

29

Actuator HE, AMV 13

 

 

30

Multifunctional control valve

(Option: Circ.)

 

 

 

AHQM

DH

HE

33

Actuator HE, AMV 150

Supply

Supply

34

Three-way valve VMV

Bypass

 

38

PT°C 2 controller

DH

HE

40

Thermostat for bypass/circ.

-----------------------------------------------

Return

Return

Options:

 

 

57

Safety thermostat monitor

Design specifications:

Connections:

 

 

Nominal pressure (prim./sec.):

PN 16 / PN3

 

1. District heating (DH) supply

Max supply temperature:

120 °C (design temperature)

 

2. District heating (DH) return

Min. ∆P:

See capacity examples

 

3. Heating (HE) return

Brazing material (HEX):

Copper

 

4. Heating (HE) supply

Weight incl. cover:

Max. 60 kg (incl. packing)

 

5. Floor heating (FH) supply

 

6. Floor heating (FH) return

 

 

<![if ! IE]>

<![endif]>861

Cover:

White-lacquered steel

7. Domestic hot water (DHW)

Electrical supply:

230 V AC

 

8. Domestic cold water (DCW)

 

Options:

Dimensions (mm):

 

 

 

 

• Cover, white-lacquered steel, with door

Without cover:

H 860 x W 650 x D 365

 

 

• Electronic controller Danfoss ECL310

With cover:

H 860 x W 700 x D 380

 

• Circulation set for DHW recirculation

Connections sizes:

 

 

• Connection of pipes can be established in the top or in

 

 

the bottom of the substation

DH:

G ¾”(ext. thread)

 

 

• Pipe insulation

DCW + DHW + HE + FH:

G ¾”(int. thread)

 

• Mounting of heat meter (supplied by customer)

Circulation:

G ¾” (ext. thread)

Wall

• Supplementary fitting set for change of fitting piece size

 

 

¾ x 110 mm to fitting piece size 1“ x 190 mm

 

 

 

 

 

 

Recirculation:

 

top view

 

Remember to order circulation set for systems that

 

 

feature DHW recirculation.

DHW: CAPACITY EXAMPLES, 10°C / 45°C

Capacity

Plate heat

Supply flow

Return flow

DHW

Pressure loss

Flow rate

primary

primary

tap load

primary

primary

[kW]

exchanger

[°C]

[°C]

[l/min]

[bar]

[l/h]

 

 

 

 

 

 

 

 

 

32,3

XB 06H-1 26

55

21,8

13,16

0,36

840

32,3

XB 06H-1 26

60

18,9

13,16

0,24

680

32,3

XB 06H-1 40

55

19,0

13,16

0,27

770

32,3

XB 06H-1 40

60z

18,9

13,16

0,24

680

41,0

XB 06H-1 26

60

20,4

16,83

0,41

890

41,0

XB 06H-1 26

70

16,8

16,83

0,23

660

53,0

XB 06H-1 40

60

19,1

21,67

0,55

1110

53,0

XB 06H-1 40

70

15,7

21,67

0,31

840

HEATING: CAPACITY EXAMPLES

 

TOTAL

 

 

 

Capacity

Plate heat

HE circuit

HE circuit

primary

secondary

[kW]

exchanger

[°C]

[°C]

 

 

 

 

 

 

23

26

70 / 38

33 / 60

30

40

70 / 38

33 / 60

10

40

60 / 30

33 / 60

35

26

95 / 41

38 / 70

Pressure loss

Flow

primary

Primary

(total1) [bar]

(total1) [l/h]

0,503

980

0,603

1120

0,272

880

0,384

760

1Calculated at 70% of the heating capacity + DHW capacity of 32.3 kW with heat exchanger XB06H-1 26 at a district heating supply temperature of 552 °C or 603 °C (DHW 10/45°C)