4.0 Enduser instructions, General ............................................................................................................................................................................................8
5.0 Enduser instructions, Initial adjustment and Setting ................................................................................................................................................9
6.0 Enduser instructions, Safety and Handling ................................................................................................................................................................ 11
7.0 Installation instructions - Getting started .................................................................................................................................................................. 12
8.0 Installation instructions, general .................................................................................................................................................................................... 13
10.0 Description of the Akva Lux II VX variants ................................................................................................................................................................... 21
10.1 Akva Lux II VX (thermostatic control) - 1 HE circuit + instantaneous DHW............................................................................................. 21
10.2 Akva Lux II VX (thermostatic control, optional junction box + zone valve) - 1 HE circuit + instantaneous DHW ..................... 24
10.3 Akva Lux II VX (ECL110) - 1 HE circuit + instantaneous DHW ....................................................................................................................... 27
10.4 Akva Lux II VX HWP (ECL 210/A237) - 1 HE circuit + instantaneous DHW ............................................................................................... 30
10.5 Akva Lux II VX H2WP (ECL 210/A260) - 2 HE circuits + instantaneous DHW ..........................................................................................32
12.0 Domestic hot water (DHW) ............................................................................................................................................................................................... 39
12.1 Regulation of the domestic hot water temperature ....................................................................................................................................... 39
12.2 Bypass or circulation thermostat ........................................................................................................................................................................... 39
14.2 Troubleshooting - Domestic hot water ................................................................................................................................................................44
15.0 EU Declaration of Conformity .......................................................................................................................................................................................... 45
16 Expansion vessel 12 l
17 Air valve
23 Sensor pocket for heat meter ½“
24 Flex. tting piece for heat meter, 3/4” x 110-165 mm
30 Thermostat T°C200 / VS2-15 or AVTB
38 PTC2 + P controller
40 Danfoss thermostat for bypass/circulation
--------------------------------------------------------------61 Recirculation hose (not part of the delivery)
62 Non-return valve (not part of the delivery)
64 Circulation pump DHW recirculation. (not part of the delivery)
DH
Supply
DH
Return
Principal components
1 Plate heat exchanger HE
2 Plate heat exchanger DHW
4 Dierential pressure controller
7 Ball valve (ll valve)
8 Circulation pump, HE
11 Safety valve, HE
12 Safety valve, DHW
16 Expansion vessel
17 Air valve
24 Fitting piece for heat meter
30 Thermostat T°C 200 / VS2
38 PTC2+P controller
40 Thermostat for bypass/circulation
The substation oers variable connection possibilities, as connection of pipes can be established both in the top or in the bottom of
the substation. Please note that the ball valves are supplied loose
with the substation, - for mounting on site.
Accessories available as extra equipment (mounting on site)
Recirculation pipe set - Div.736 - Code No. 004U8404
For systems that feature domestic hot water recirculation.
Rell line - Div.770 - Code No. 004U8668
To secure a constant pressure on the secondary side.
(Applicable on some markets, if in accordance with all local regulations, please check with your heating supplier).
Recirculation pipe set
Rell line
HE
Supply
HE
Return
38
17
17
162
1
162
38
7
4
30
30
40
8
24
24
11
12
24
DHW
DH return
DH supply
Primary
2
DKDHR VI.GP.Q3.02 Danfoss District Energy
HE return
HE supply
SecondaryDHW
DCW
Instructions for installation and use Akva Lux II VX substations
2.2 Akva Lux II VX (thermostatic control and optional junction box + zone valve) - 1 HE circuit and instantaneous DHW heater
1 Plate heat exchanger HE
2 Plate heat exchanger DHW
4 Dierential pressure controller
8 Circulation pump, HE
11 Safety valve HE
12 Safety valve DHW
16 Expansion vessel
17 Air valve
24 Fitting piece for heat meter
30 Thermostat T°C 200 / VS2
38 PTC2+P controller
40 Thermostat for bypass/circulation
70 Zone valve (Option)
71 Junction box (Option)
The substation oers variable connection possibilities, as connection of pipes can be established both in the top or in the
bottom of the substation. Please note that the ball valves are
supplied loose with the substation, - for mounting on site.
Accessories available as extra equipment (mounting on site)
Recirculation pipe set - Div.736 - Code No. 004U8404
For systems that feature domestic hot water recirculation.
Rell line - Div.770 - Code No. 004U8668
To secure a constant pressure on the secondary side.
(Applicable on some markets, if in accordance with all local regulations, please check with your heating supplier).
Recirculation pipe set
Rell line
17
16
1
16
70
38
71
40
30
2
4
12
11
8
24
24
24
DCW
DHW
DH supply
Primary
DH return
HE return
HE supply
SecondaryDHW
Danfoss District Energy VI.GP.Q3 .02 DKDHR
33
Instructions for installation and use Akva Lux II VX substations
2.3 Akva Lux II VX (ECL 110) - 1 HE circuit and instantaneous domestic hot water heater
1 Plate heat exchanger HE
2 Plate heat exchanger DHW
4 Dierential pressure controller
8 Circulation pump, HE
11 Safety valve, HE
12 Safety valve, DHW
16 Expansion vessel
24 Fitting piece for heat meter
25 Electronic controller
29 Actuator AMV 150
30 2-way valve VS2
38 PTC2+P controller
40 Thermostat for bypass/circulation
The substation oers variable connection possibilities, as connection of pipes can be established both in the top or in the
bottom of the substation. Please note that the ball valves are
supplied loose with the substation, - for mounting on site.
Accessories available as extra equipment (mounting on site)
Recirculation pipe set - Div.736 - Code No. 004U8404
For systems that feature domestic hot water recirculation.
Rell line - Div.770 - Code No. 004U8668
To secure a constant pressure on the secondary side.
(Applicable on some markets, if in accordance with all local regulations, please check with your heating supplier).
Rell lineRecirculation pipe set
38
1
2
25
29
4
40
30
16
24
8
11
12
24
DHW
DH return
DH supply
Primary
4
DKDHR VI.GP.Q3.02 Danfoss District Energy
HE return
HE supply
SecondaryDHW
DCW
Instructions for installation and use Akva Lux II VX substations
2.3 Akva Lux II VX HWP (ECL 210/A237) - 1 HE circuit and instantaneous domestic hot water heater
12 Safety valve, DHW
13 Thermometer
14 Pocket for pressure gauge ¼
15 Manometer
16 Expansion vessel
23 Sensor pocket for heat meter ½“
24 Fitting piece for heat meter, 3/4” x 110 mm
25 Electronic controller Danfoss ECL 210/A237
26 Outdoor sensor Danfoss ESMT
27 Sensor Danfoss ESMC
29 Danfoss actuator AMV 150
30 Multifunctional control valve AHQM
38 PTC2 + P controller
40 Danfoss thermostat for bypass/circulation
--------------------------------------------------------------Options.:
Recirculation set
Electronic Danfoss Controller ECL 310
DCW
Circ.
(option)
DH
Supply
Bypass
DH
Return
Principal components
1 Plate heat exchanger HE
2 Plate heat exchanger DHW
5 Strainer
8 Circulation pump, HE
11 Safety valve, HE
12 Safety valve, DHW
16 Expansion vessel
24 Fitting piece for heat meter
25 Electronic controller ECL 210/A237
29 Actuator AMV 150
30 Multifunctional control valve AHQM
38 PTC2+P controller
40 Thermostat for bypass/circulation
The substation oers variable connection possibilities, as connection of pipes can be established both in the top or in the
bottom of the substation. Please note that the ball valves are
supplied loose with the substation, - for mounting on site.
HE
Supply
HE
Return
38
25
29
1
2
40
30
16
12
8
11
Accessories available as extra equipment (mounting on site)
Recirculation pipe set - Div.736 - Code No. 004U8404
For systems that feature domestic hot water recirculation.
Rell line - Div.770 - Code No. 004U8668
To secure a constant pressure on the secondary side.
(Applicable on some markets, if in accordance with all local regulations, please check with your heating supplier).
Rell lineRecirculation pipe set
Danfoss District Energy VI.GP.Q3 .02 DKDHR
5
DH supply
Primary
24
DH return
5
HE return
HE supply
SecondaryDHW
DHW
DCW
55
Instructions for installation and use Akva Lux II VX substations
2.4 Akva Lux II VX H2WP (ECL 210/A260) - 2 HE circuits and instantaneous domestic hot water heater
14 Pocket for pressure gauge ¼
15 Manometer
16 Expansion vessel
23 Sensor pocket for heat meter ½“
24 Fitting piece for heat meter, 3/4” x 110 mm
25 Electronic controller Danfoss ECL 210/A260
26 Outdoor sensor Danfoss ESMT
27 Sensor Danfoss ESMC
28 Immersion sensor ESMB
DHW
DCW
Circ.
(option)
DH
Supply
Bypass
DH
Return
Principal components
1 Plate heat exchanger HE
2 Plate heat exchanger DHW
5 Dirt strainer
8 Circulation pump, HE
10 Circulation pump, FH
11 Safety valve, HE
12 Safety valve, DHW
16 Expansion vessel
24 Fitting piece for heat meter
25 Electronic controller
29 Actuator AMV 13
30 Multifunctional control valve AHQM
33 Actuator AMV 150
34 3-way valve VMV
38 PTC2+P controller
40 Thermostat for bypass/circulation
57 Safety thermostat
The substation oers variable connection possibilities, as connection of pipes can be established both in the top or in the
bottom of the substation. Please note that the ball valves are
supplied loose with the substation, - for mounting on site.
Accessories available as extra equipment (mounting on site)
Recirculation pipe set - Div.736 - Code No. 004U8404
For systems that feature domestic hot water recirculation.
Rell line - Div.770 - Code No. 004U8668
To secure a constant pressure on the secondary side.
(Applicable on some markets, if in accordance with all local regulations, please check with your heating supplier).
Rell lineRecirculation pipe set
29 Danfoss actuator AMV
30 Multifunctional control valve AHQM
33 Danfoss actuator AMV
34 Three-way valve VMV
38 PTC2 + P controller
40 Danfoss thermostat for bypass/circulation
29 Danfoss actuator AMV, HE
57 Safety thermostat
Supply limit
HE
Supply
HE
Return
57
25
1
3433
29
38
2
40
30
10
16
8
11
5
24
5
12
DHW
DH return
DH supply
Primary
6
DKDHR VI.GP.Q3.02 Danfoss District Energy
HE return
HE supply
SecondaryDHW
FH supply
FH return
DCW
Instructions for installation and use Akva Lux II VX substations
3.0 Dimensional sketches / connections
Dimensions mm:
Without cover:
H 860 x W min. 510 / max. 553* x D 365
With cover:
H 861 x W 550 x D 365
H 861 x W 600 ** x D 381
* Units with insulated plate heat exchanger type XB06H-1 40
for both HE and DHW circuits.
** Width of cover for units with insulated plate heat exchanger
type XB06H-1 40 for both HE and DHW circuits
.
Connections sizes:
Akva Lux II VX (thermostatic control)
DH + DCW + DHW + HE: G ¾” (int. thread)
Connections, Circ.: R ½” (int. thread)
*
Substations with XB 0 6L-24 heat exchanger for o or heating are
supplied with connection pipes for radiators for direct connection.
Akva Lux II VX (thermostatic control and optional
junction box + zone valve) +
Akva Lux II VX (electronic control)
Akva Lux II VX - 1 HE circuit + domestic hot water
Wall
ADBFEC
H
G
top view
Connections:
Order:
A. District heating (DH) supply
B. District heating (DH) return
C. Heating (HE) return
D. Heating (HE) supply
E. Domestic hot water (DHW
F. Domestic cold water (DCW)
G. Connection return
H. Connection supply *
*
Wall
ADBFEC
top view
Connections:
Order:
A District heating (DH) supply
B District heating (DH) return
C Heating (HE) return
D Heating (HE) supply
E DHW
F DCW
Akva Lux II VX - 2 HE circuits + domestic hot water
Zirk.
Wall
top view
Danfoss District Energy VI.GP.Q3 .02 DKDHR
77
Instructions for installation and use Akva Lux II VX substations
4.0 Enduser instructions, General
Instructions
Please read these instructions carefully before installing and commissioning this substation. The manufacturer accepts no liability for loss
or damage resulting from failure to comply with these instructions
for use. Read and follow these instructions carefully to prevent the
risk of physical injury and/or damage to property. Exceeding the
recommended operating parameters appreciably increases the risk
of personal injury and/or damage to property.
Installation, commissioning and maintenance must be carried out
by qualied and authorised personnel (both plumbing and electrical work).
Once the station has been installed and is operating, there is nor-mally no need to alter the settings or other functions. The district
heating substation is very reliable and easy to operate.
If necessary, you can change the temperature settings as described
on page 10. For more detailed information about the substation,
see the sections concerning installation and commissioning.
Description
These instructions apply to substation types Akva Lux II VX, which
are district heating substations for indirect heating for single-family
houses, semi-detatched and terraced houses as well as ats. With
one or two heating circuits for radiator and/or oor heating and with
instantaneous water heater for domestic hot water heating. For wallmounting and with variable connection possibilities.
The HE supply temperature is controlled either by a self-acting thermostat T°C 200 or AVTB or by a Danfoss ECL controller in combination
with an electronic actuator. The ECL controller acts as the brain of
the heating system. It lets you easily control and optimize system
performance and operation.
Warning! Hot surfaces
Parts of the substation may be very hot and can cause burn injuries. Be very careful when you are in the immediate vicinity of
the unit.
Warnings about high pressure and high temperature
The maximum supply temperature in the district heating network can be up to 120°C (130° C*) and the operating pressure can
be up to 16 bar. This may result in a risk of scalding from touching
the substation and from outow of the medium (water/steam).
Exceeding the substation design data and operating parameters
for pressure and temperature carries an appreciable risk of personal injury and/or damage to property.
Emergencies
In the event of re, leaks or other hazards, immediately shut o
all sources of energy to the substation, if possible, and call for
appropriate assistance.
If the domestic hot water is discoloured or malodorous, shut o
all ball valves on the substation notify all users and call for professional assistance without delay.
*
the substations can work temporarily at 130° C
We recommend regular inspections of the substation - ideally in
connection with readings of the district heating meter.
Pay special attention to any leaks and an excessively high return
temperature in the district heating circuit (poor cooling of the district
heating water). Cooling – i.e. the dierence between the supply and
return temperature of the district heating water – has a signicant effect on the overall energy economy. Therefore, it is important to focus
on the supply and return temperature in the heating system.
The dierence should typically be 30–35°C in systems that operate
with radiators. In systems that feature oor heating, the dierence
is typically 5–10°C. In oor heating systems, the supply temperature
should not exceed 35°C.
Cooling from the water heater alone:
During tapping, the level of cooling will typically be 30–35°C. When
domestic hot water is not being tapped, it is completely normal for the
return temperature from the water heater to rise slightly. In this situation, the district heating meter will register very modest consumption
as the volume of water is very small.
On substations with recirculation, the calorie meter registers the heat
loss in the recirculation pipe.
Irregularities
When reading the meters, check all joints and connections for leaks.
If you identify any irregularities/leaks, contact your professional
provider for assistance.
Check the troubleshooting section before contacting your
professional provider.
8
DKDHR VI.GP.Q3.02 Danfoss District Energy
Instructions for installation and use Akva Lux II VX substations
5.0 Enduser instructions, Initial adjustment and Setting
Domestic hot water control
Danfoss PTC2+P controller (Fig. 1) for domestic hot water. Set the DHW
temperature by moving the adjuster lever towards “+” (hotter) or “-”
(colder).
Start by turning the lever clockwise – until it stops/until you cannot turn it
any further. Then turn the lever counter-clockwise until the temperature
of the tap water is approx. 48°C during normal tapping ow (7–8 litres
per min.). The temperature must never exceed 55°C to prevent limescale
deposits building up in the water heater.
Fig. 1
Option: Alternatively the VX substations may be tted with a Danfoss
PM2+P controller (Fig. 2) for domestic hot water. Set the DHW temperature
by turning the adjuster lever towards red (hotter) or blue (colder). Start
by turning the lever clockwise – until the pin is opposite the blue dot.
Then turn the lever counter-clockwise until the temperature of the tap
water is approx. 48°C during normal tapping ow (7–8 litres per min.).
The temperature must never exceed 55°C to prevent limescale deposits
building up in the water heater.
Bypass or circulation thermostat
Thermostat (Fig. 3) that keeps the branch pipe warm in the summer
or regulates the circulation temperature if domestic hot water recirculation has been established in the hot water system (see pages 20-21
and page 37 for more information).
The thermostat should initially be set to position 3.
Heating circuit, Dierential Pressure Controller
The dierential pressure controller (Fig. 1) reduces the high, uctuating
pressure in the district heating network to a constant operating pressure.
The AVPL dierential pressure controller is initially set by the plumber in
connection with the commissioning of the substation. If disruptions to
the operation occur: noise in the radiator thermostats or poor regulation
capacity, it may be necessary to reset the dierential pressure controller
to a lower or higher operating pressure. We suggest that you contact
your local plumber for assistance.
The TD200 dierential pressure controller is preset from factory and
should not be adjusted afterwards.
Heating circuit, Temperature control
Thermostatic control
The supply temperature to the substation can be set by adjusting the thermostat TC (Fig. 5), which controls the temperature for the heating circuit.
The thermostat will be set by the installer in connection with the com
missioning, but it may be necessary to adjust it subsequently depending
on the outdoor temperature.
Approximate thermostat scale settings:
Pos. 2 = 30°C
3 = 40°C for range 25-70° C
4 = 50°C
5 = 60°C
or
Pos. 2 = 45°C
3 = 55°C for range 35-85° C
4 = 65°C
5 = 75°C
Please note that a label on the TC thermostat will indicate the temperature
range (g. 6).
The setting values may vary depending on the operating conditions. It is
important to set the supply temperature to the radiators as low as possible. Use the radiator thermostats to regulate the room temperature.
NB! For houses that are heated exclusively with oor heating.
The supply temperature should typically be set to approx. 30–35°C.
ALWAYS refer to the instructions from the oor supplier.
Fig. 2
pin
Fig. 3
Fig. 4
or
TD200AVPL
Fig. 5A
-
Fig. 6
or
Range 35-85° CRange 25-70° C
Danfoss District Energy VI.GP.Q3 .02 DKDHR
99
Instructions for installation and use Akva Lux II VX substations
Alternatively the HE temperature is controlled by a self-acting temperature controller Danfoss AVTB (Fig. 5B). The controller has a control
valve, thermostatic actuator and handle for temperature setting. The
thermostat will be set by the installer in connection with the commissioning, but it may be necessary to adjust it subsequently depending
on the outdoor temperature.
Approximate thermostat scale settings:
1.0 = 35 °C
1.5 = 45 °C
2.0 = 55 °C
2.5 = 65 °C
3.0 = 75 °C
Other variations with other types of thermostatic valves for control
of the heating circuit may occur.
Electronic control
The temperature for the heating circuit can be controlled electronically by a Danfoss ECL 110, a Danfoss ECL 210 or a Danfoss ECL 310
controller (Fig. 6). The supply temperature ist calculated by the controller on basis of the outdoor temperature.
See the enclosed documentation for same.
Pump.
Akva Lux II VX substations are factory tted with a pump (Fig. 7). The
pump setting is established in connection with the commissioning. Generally speaking, this setting is not to be altered. If it should nevertheless
be necessary to change the pump setting, see the section concerning
pumps in the installation and commissioning sections regarding the
individual products.
In the summer, you can switch o the power to the pump at the mains
if you want to save electricity by not heating your home.
Start-up and venting – see the installation and commissioning sections,
if necessary.
Fig. 5B
AVTB
Fig. 6
or
ECL 210 / ECL 310ECL 110
Fig. 7
UPM3 AUTOUPM3 AUTO L
10
DKDHR VI.GP.Q3.02 Danfoss District Energy
Instructions for installation and use Akva Lux II VX substations
6.0 Installation instructions, Safety and Handling
Instructions
Please read these instructions carefully before installing and comissioning this substation. The manufacturer accepts no liability for loss or
damage resulting from failure to comply with these instructions for use.
Read and follow these instructions carefully to prevent the risk of physical injury and/or damage to peroperty. Exceeding the recommended
operating parameters considerably increases the risk of personal injury
and/or damage to property.
Installation, commissioning and maintenance must be carried out by
qualied and authorized personnel in compliance with the local safety
regulations.
Once the station has been installed and is operating, there is normally
no need to alter the settings or other functions. The district heating
substation is very reliable and easy to operate.
Energy source
The substation is primarily designed for connection to district heating.
Alternative energy sources can be used if the operating conditions are
equivalent to district heating at all times.
Application
The substation is designed only to operate with water or a water-glycol
mixture (up to 40%), and other heating media may not be used.
The substation is to be connected to the household piping in a frost-free
room, where the temperature does not exceed 50 °C and the relative
humidity is not higher than 80%. The substation must no be covered,
bricked in or otherwise cut o from access.
Choice of materials
Only use materials, that comply with local regulations.
Corrosion
The maximum chloride compounds of the medium must not be higher
than 300 mg/l. The risk of corrosion increases considerably if the recommended chloride content is exceeded.
Safety valve(s)
Installation of safety valve(s) must always be in compliance with local
regulations.
Noise level.
≤ 55 dB.
PTC2+P controller for domestic hot water
The controller is preset from factory and sealed with a
red sticker. This sealing must not been broken.
The warranty becomes void if the sealing is broken.
Storage
Before installation, the units must be stored in a dry, heated (i.e. frostfree) room.
(Relative humidity max. 80% and storage temperature 5-70 °C).
The units must not be stacked higher than the limit at the factory (max.
8 layers) Units supplied in cardboard packaging must be lifted using the
handles incorporated in the packaging. Units must be placed on pallets
for transport/moving across large distances.
As far as possible, do not lift the substation by the pipes. Lifting by the
pipes may cause leaks. REMEMBER to retighten.
Disposal
Dispose of the packaging in accordance with the local regulations for
disposal of used packaging materials.
The substation is made of materials that cannot be disposed of together
with household waste.
Close all energy sources and disconnect all connection pipes. Disconnect
and dismantle the product for disposal in accordance with the applicable
local regulations for the disposal of the individual components.
Danfoss District Energy VI.GP.Q3 .02 DKDHR
Connection
It must be possible to cut o all energy sources to the unit - including electrical connections - at all times.
Potential equalization/grounding
Potential equalization is an electrical equalizer connection to secure
against user contact with dangerous voltage, which may occur for
example between two piping systems. Potential equalization reduces
corrosion in heat exchangers, water heaters, district heating units and
plumbing installations. Equalization of potentials should be eected
according to local regulations.
Warning! Hot surfaces
Parts of the substation may be very hot and can cause burn injuries. Be very careful when you are in the immediate vicinity of the
substation.
Warning of high pressure and high temperature
The maximum supply temperature in the district heating network
can be up to 120°C (130°C*) and the operating pressure can be up
to 16 bar. This may result in a risk of scalding from touching the substation and from outow of the medium (water/steam). Exceeding
the substation design data and operating parameters for pressure
and temperature carries an appreciable risk of personal injury and/
or damage to property.
* the substation can work temporarily at130°C.
Emergencies
In the event of re, leaks or other hazards, immediately shut o all
sources of energy to the substation, if possible and call for appropriate assistance.
If the domestic hot water is discoloured or malodorous, shut o all
ball valves on the substation, notify all users and call for professional
assistance immediately.
Warning of damage during transport
On reception of the substation, and before installing it, check for
any evidence of damage during transport.
The substation must be handled and moved with the greatest care
and attention.
NB! - Tightening of connections
Before mounting of the substation, ALL pipe connections MUST
be retightened, as vibrations during transport may have caused
leaks. Once the substation has been put into operation ALL pipe
connections MUST be pressure tested for leaks and retightened
once more if necessary.
DO NOT OVERTIGHTEN THE PIPE CONNECTIONS – see page 14,
“Test & connections”.
Handling
We recommend that you wear suitable safety footwear while
handling and installing the substation.
1111
Instructions for installation and use Akva Lux II VX substations
7.0 Installation instructions - Getting started
Connect the substation to the household piping in accordance with
the labelling at the bottom and/or in accordance with the instructions in this manual.
If the system features DHW recirculation, a recirculation connection must be established on the substation. The circulation set
is optional equipment, which must be ordered separately and
mounted on site.
We recommend establishing recirculation BEFORE mounting the
substation on the wall.
For instructions about recirculation connection, see page 20-21.
Commissioning
Please note that from factory the substation is prepared for
connection in bottom of the substation.
1. The ball valves, which are supplied loose with the substation, can
be mounted either on the top connections or bottom connections. For connection in top, demount the plugs from the top connections and mount them on the bottom connections.
(Please see instruction on page 14 for further information)
2. For connection in TOP for DCW and DHW please note that
this includes relocation of the built-in blind plates BEFORE
mounting the substation on the wall. (Please see instruction
on page 15 for further information).
3. If the household piping system features domestic hot water
recirculation, the substation must be connected to the recirculation system. See pages 20-21 for further information about
DHW recirculation.
4. The substation is prepared for wall mounting. Mount the substation on a solid wall using two sturdy bolts, screws, expansion bolts or similar.
5. Close all shut-o valves in the substation before connecting it/
them to the household piping.
6. Mount the district heating meter (see page 16).
7. IMPORTANT! Tighten all pipe connections, as they may have
loosened during transport and handling.
8. On systems that feature a safety valve, establish a drain connection in compliance with the applicable legislation.
9. Fill the heat exchanger / the system with water according
to the instructions on pages 18 and 19 until the manometer
shows a working pressure, which corresponds to the system
height + approx. 5 m (approx. 1.2 - 1.5 bar).
12. Pressure test the entire system for leaks in accordance with
the applicable regulations.
13. Connect pump and automatic components, if any, to the electricity supply, but do not switch on the power.
14. Heat the system and vent the radiator circuit/heating side
thoroughly on the radiators and the air valve, if any.
15. For substations, which include zone valve, remember
to remove the red split on the position indicator of
the zone valve.
16. Now switch on the pump and automatic components, if any.
10. Finally open the ball valve for the DH supply and return ow
and heat up the system.
11. Check the substation and the household piping thoroughly
for leaks.
12
DKDHR VI.GP.Q3.02 Danfoss District Energy
17. Finish by adjusting the substation in accordance with the
instruction manuals.
Heating and cooling the substation may cause leaks. Therefore
it may be necessary to retighten the connections in the period
after commissioning.
Instructions for installation and use Akva Lux II VX substations
8.0 Installation instructions, general
The installation, connection and maintenance of the substation must
be performed by qualied and authorised personnel.
Installation must always be performed in accordance with the applicable legislation and in compliance with these instructions.
The substation must be installed so that it is freely accessible and can
be maintained without unnecessary disruption. Lift the substation
by its mounting plate and secure it to a solid wall using 2 sturdy
bolts, screws or expansion bolts positioned in the two keyholes in
the mounting plate.
Before commissioning, rinse all the pipes in the household piping
system thoroughly to remove any impurities, and check and clean
the dirt strainers in the substation.
Connect the substation to the household piping in accordance with
the labelling at the bottom and/or in accordance with the instructions in this manual.
Test and connections
Before lling the system with water, retighten all the pipe connections
because vibrations and shocks during transport and handling may
have caused leaks. Once the system has been lled with water, tighten
all the pipe connections once more before performing pressure test
for leaks. After heating of the system, check all the connections and
retighten if necessary.
Please note that the connections feature EPDM rubber gaskets!
Therefore, it is important that you DO NOT OVERTIGHTEN the union
nuts. Over-tightening may result in leaks. Leaks caused by overtightening or failure to retighten connections are not covered by
the warranty.
Variable connections possibilities
The Akva Lux II VX substations oer variable connection possibilities, as connections of pipes can be established in the top or in the
bottom of the substation. - Upon delivery the substation is prepared
for connction in bottom of the substation. Please note that the ball
valves are supplied loose and must be mounted on site.
For change of connection from bottom to top, demount plugs on
connection pipes in top of substation and ball valves on connection
pipes in bottom of substation, and mount plugs in connection pipes
in bottom of substation and ball valves on connection pipes in top
of substation.
These variable connection possibilities makes it possible to establish
some of the connections in the top and others in the bottom of the
substation. This may be desirable in some cases.
Danfoss District Energy VI.GP.Q3 .02 DKDHR
1313
Instructions for installation and use Akva Lux II VX substations
PLEASE NOTE!
Remember to use gaskets when establishing connection in top of
unit.
DCW
If there is a need for a domestic cold water outlet in top of the unit,
remove the blind plate in pos. A and demount the plug in top of the
unit.
For DCW inlet in top of the unit, remove the plug in top of the unit
and the blind place in pos. A. Mount the ball valve in top and use
the plug for plugging in the bottom (remember gaskets).
DHW
For DHW outlet in top of the unit, remove the blind plate and gasket
from Pos. B and relocate to Pos. C - see photos to the right.
The blind plate should be installed in Pos. C to prevent a pocket
of standing water that at worst can produce dangerous bacteria.
Therefore, it is extremely important to install the blind plate as
shown.
Also move the plug from the top connection to the DHW outlet in
the bottom of the unit and mount the ball valve in top (remember
gaskets).
DHW both up and down
The unit can be connected with piping both up and down for the domestic hot water. Remove blind plate in pos. B and plug in top of unit.
DCW
DHW
A
Demount
blind plate
Heating (HE)
The unit can be connected with piping both up and down on the
heating side. Remove the plugs in top of unit, and establish connection upwards.
Expansion vessel
The Akva Lux II VX substations are equipped with an expansion
vessel, which is factory set to 0,5 bar.
DHW
Demount
blind plate
B
Mount blind
C
plate here
14
DKDHR VI.GP.Q3.02 Danfoss District Energy
Instructions for installation and use Akva Lux II VX substations
Fitting piece(s) for heat meter(s).
The Akva Lux II VX substations are equipped with tting piece(s) for
heat meter in both DH supply and return (leak detection) or only in
DH return.
The tting piece(s) can be either exible size 3/4 x 110 - 165 mm or
xed size 3/4” x 110 mm.
Variations with other dimensions may occur.
Fitting of heat meter in substation with exible tting piece
size 3/4 x 110 - 165 mm
Fitting of heat meter in DH return - (Fig. 1)
The heat meter can easily be tted on site as follows:
- Close the ball valves on the district heating and the heating
lines.
- Loosen the union nuts at both ends of the nipple pipe 24
remove nipple pipe 24
1
and insert heat meter and tighten
1
.
- do not forget gaskets.
- For heat meters with an overall length of more than110 mm
the exible tting pipe 24
2
must be loosened and displaced,
so that it corresponds to the size of the heat meter.
- Tighten union nut/locknut.
- After mounting of heat meter remember to check and tighten
all pipe connections before commissioning the heat meter.
For tting of heat meter in DH supply (Fig. 2) please follow the above
instructions.
For tting of heat meter in both DH supply and return, please follow
the above instructions.
Fig. 1
2
1
24
24
Loosen union nut/locknut and the exible pipe 242
is adjustable from 110 to 165 mm.
Fig. 2
2
1
24
24
Loosen union nut/locknut and the exible pipe 242
is adjustable from 110 to 165 mm.
Fig. 3
Fitting of heat meter(s) in substation with xed tting piece
size 3/4 x 110 mm
Fitting of heat meter(s) - (Fig. 3)
The heat meter can easily be tted on site as follows:
- Close the ball valves on the district heating and the heating
lines.
- Loosen the union nuts at both ends of the tting piece13b and
remove it.
- Fit the heat meter, - remember to insert gaskets.
- After mounting of heat meter remember to check and tighten
all pipe connections before commissioning the heat meter.
Mounting of temperature sensor
As standard the heat meter is supplied with temperature sensors for
measuring the supply and return ow temperatures.
The Akva Lux II VX substations are prepared for mounting of temperature sensors with M10x1 connection (see photo to the right).
The supply ow sensor is mounted in the sensor pocket on DH supply (pos. A)
- demount M10 plug (pos. A)
- insert one temperature sensor in the sensor pocket
- tighten temperature sensor union nut
Mount the return ow sensor in the heat meter housing (pos. C) or
in the sensor pocket on DH return (pos. B).
13b
Fig. 4
A
B
Pipe bushing ½”/M10x1 incl. plug M10
C
Please note:
Some variant are supplied with ½” plug.
Danfoss District Energy VI.GP.Q3 .02 DKDHR
1515
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.