General mounting
Instructions
System Manager
AK-SM 810
sm800.danfoss.com
-10°< t
14°F < t
0 - 95% RH, non condensing
IP20
T 8
< 55°C°
amb
amb
< 130°F
RI8SD402 2019-01
T 10
Relay 2

US mounting
Panel mounting
Listed
UL file: E31024
61B5
Class 2 or LPS in accordance with NEC.
For supply connections, use 16 AWG or
larger wires rated for at least 75°C (167°F).
Use copper conducters only.
14°F < t
0 - 95% RH, non condensing
< 130°F
amb
IP20
Supply
Relay 2
T 8
Modbus, Lon-version
For safety reasons both supply
voltage and relay voltage must be
the same voltage.
2 Instructions RI8SD402 © Danfoss 2019/01 AK-SM 810

Selve installationen af datakommunikationskablet skal overholde de krav, som er nævnt i dokumentet
"Datakommunikation imellem ADAP-KOOL® Køleanlægsstyringer". Litteraturnummer = RC8AC.
The actual installation of the data communication cable must comply with the requirements mentioned in the document
"Data communication between ADAP-KOOL® Refrigeration controls". Literature sheet number = RC8AC.
Beim Verlegen des Datenkommunikationskabels sind die im Dokument „Datenkommunikation zwischen ADAP-KOOL®
Kälteanlagenregelsysteme“ enthaltenen Anforderungen einzuhalten. Literaturnummer = RC8AC.
L’installation elle-même du câble de transmission de données doit respecter les contraintes citées dans le document
«Transmission de données ADAP-KOOL® Commande d’installation frigorifiques». Référence documentaire = RC8AC.
La instalación práctica del cable de comunicación de datos debe cumplir con los requisitos mencionados en el documento "Comunicación de datos entre controles de refrigeración ADAP-KOOL®". Número de documento = RC8AC.
Terminering
Termination
Terminierung
Terminaison
Terminación
If a repeater is used, make
Modbus
LON
sure the terminators
are used (included with
repeater).
TCP/IP
Initial settings
Use the included 120 Ohm
terminator on last device.
LAN
Use shielded ethernet cable
1. Check address setting = 9 (9 = Factory IP address = 192.168.1.161)
2. Download "StoreView Desktop" (sm800.danfoss.com) to PC
3. Run "StoreView Desktop"
4. Connect to 192.168.1.161
5. Set Engineering unit preferences
6. Set Users / Password
Default: User = Supervisor / Password = 12345
7. Set Communications
8. Set address setting = 0 ( 0 = master)
9. OK and Finish (reset)
Konfiguration
Configuration
Konfiguration
Configuration
Configuración
See manual: USCO.PI.R1.E9.--