Danfoss AK-SM 810 Installation guide

General mounting
Instructions
System Manager AK-SM 810
sm800.danfoss.com
-10°< t 14°F < t 0 - 95% RH, non condensing IP20
T 8
< 55°C°
amb
amb
RI8SD402 2019-01
T 10
Relay 2
US mounting
Panel mounting
Listed
UL file: E31024 61B5 Class 2 or LPS in accordance with NEC. For supply connections, use 16 AWG or larger wires rated for at least 75°C (167°F). Use copper conducters only. 14°F < t 0 - 95% RH, non condensing
amb
IP20
Supply
Relay 2
T 8
Modbus, Lon-version
For safety reasons both supply voltage and relay voltage must be the same voltage.
2 Instructions RI8SD402 © Danfoss 2019/01 AK-SM 810
Selve installationen af datakommunikationskablet skal overholde de krav, som er nævnt i dokumentet "Datakommunikation imellem ADAP-KOOL® Køleanlægsstyringer". Litteraturnummer = RC8AC.
The actual installation of the data communication cable must comply with the requirements mentioned in the document "Data communication between ADAP-KOOL® Refrigeration controls". Literature sheet number = RC8AC.
Beim Verlegen des Datenkommunikationskabels sind die im Dokument „Datenkommunikation zwischen ADAP-KOOL® Kälteanlagenregelsysteme“ enthaltenen Anforderungen einzuhalten. Literaturnummer = RC8AC.
L’installation elle-même du câble de transmission de données doit respecter les contraintes citées dans le document «Transmission de données ADAP-KOOL® Commande d’installation frigorifiques». Référence documentaire = RC8AC.
La instalación práctica del cable de comunicación de datos debe cumplir con los requisitos mencionados en el documen­to "Comunicación de datos entre controles de refrigeración ADAP-KOOL®". Número de documento = RC8AC.
Terminering Termination Terminierung Terminaison Terminación
If a repeater is used, make
Modbus
LON
sure the terminators are used (included with repeater).
TCP/IP
Initial settings
Use the included 120 Ohm terminator on last device.
LAN Use shielded ethernet cable
1. Check address setting = 9 (9 = Factory IP address = 192.168.1.161)
2. Download "StoreView Desktop" (sm800.danfoss.com) to PC
3. Run "StoreView Desktop"
4. Connect to 192.168.1.161
5. Set Engineering unit preferences
6. Set Users / Password
Default: User = Supervisor / Password = 12345
7. Set Communications
8. Set address setting = 0 ( 0 = master)
9. OK and Finish (reset)
Konfiguration Configuration Konfiguration Configuration Configuración
See manual: USCO.PI.R1.E9.--
AK-SM 810 Instructions RI8SD402 © Danfoss 2018/01 3