-20°< t
-0°F < t
0 - 95% RH, non condensing
IP10 / VBG4
UL: E166834
amb
amb
< 55°C
< 130°F
Instructions
System manager
AK-SM 720
AK-SM 720
See manual: RS8EC
Data communication
See literature : RC8AC
AI x 11
DO x 8
Supply voltage:
Transformer
Class II
The 24V must not be
shared by other
controllers or units
The 24 V input must not
have earth connection
Max. 10 V
Max. 230 V
Keep the safety distance
Low and high voltage must
not be connected to the
same output group
RI8LL102 03-2007
U
min
I
max
: 48 V a.c.
.: 0.5 A
SPDT:
AC-1: 4A (ohmic)
AC-15: 3A (Inductive)
Point
Relay or
AKV coil
110/230 V
Terminal 15: 12 V
Terminal 16: 5 V
Terminal 27: 12 V
Terminal 28: 5 V
Terminal
17, 18, 29, 30:
S (sensor)
Pt 1000 ohm/0°C
P (pressure)
AKS 32R
AKS 32
U (voltage)
On/O
DO
AO
The Product contains electrical components
And may not be disposed together with domestic waste.
Equipment must be separate collected with Electrical and Electronic waste. According to Local and currently valid legislation.
Signal
Signal
type
Address
S1
S2...
Saux1
Pt 1000
Saux2
SSA
SdA
(System manager)
P0A
P0B
PcA
PcB
AKS 32R
-1 - xx bar
AKS 32
-1 - zz bar
Signal Signal type /
Active at
Module Point Terminals
1 (AI 1) 1 - 2
2 (AI 2) 3 - 4
3 (AI 3) 5 - 6
4 (AI 4) 7 - 8
5 (AI 5) 9 - 10
...
0 - 10 V
0 - 5 V
6 (AI 6) 11 - 12
7 (AI 7) 13 - 14
8 (AI 8) 19 - 20
Ext.
Main
switch
Day/
Night
Door
Comp 1
AKV
Comp 2
Fan 1
Alarm
Active at:
Closed
/
Open
Active at:
ON
/
OFF
9 (AI 9) 21 - 22
10 (AI 10) 23 - 24
11 (AI 11) 25 - 26
1
12 (DO 1) 31 - 32
13 (DO 2) 33 - 34
14 (DO 3) 35 - 36
15 (DO 4) 37 - 38
16 (DO 5) 39 - 41
17 (DO6) 42 - 44
18 (DO7) 45 - 47
19 (DO8) 48 - 50
AO
0-10 V
24 (AO1) -
25 (AO2) -
DE-BD
2 Instructions RI8LL102 © Danfoss 03/2007 AK-SM 720 System manager