Danfoss AK-SM 720 User guide

User Guide
Network control
AK-SM 720
ADAP-KOOL® Refrigeration control systems
www.danfoss.com
User Guide | Network control AK-SM 720
Contents
1. Introduction
Principles ..................................................................................................... 4
2. Design of a controller
Module survey .................................................................................................... 7
Common data for modules ............................................................................9
Dimensions ........................................................................................................10
System manager AK-SM.......................................................................11
Extension module AK-XM 101A ........................................................13
Extension module AK-XM 102A / AK-XM 102B ............................15
Extension module AK-XM 204A / AK-XM 204B ............................17
Extension module AK-XM 205A / AK-XM 205B ............................19
Extension module AK-XM 107A .......................................................21
Extension module AK-OB 110 ............................................................23
Power supply module AK-PS 075 / 150 ..........................................24
Preface to design .............................................................................................25
Functions ...................................................................................................25
Connections .............................................................................................26
Limitations ................................................................................................26
Design of a System manager ......................................................................27
Ordering .............................................................................................................35
3. Mounting and wiring
Mounting............................................................................................................36
Wiring ..................................................................................................................37
4. Configuration and operation
Installation in network...................................................................................39
Configuration ....................................................................................................41
Connect PC ...............................................................................................41
Unlock the configuration of the controllers .................................43
Clock function .........................................................................................44
Quick setup...............................................................................................45
Plants main data .....................................................................................46
Alarm relay on plant ..............................................................................47
Destinations to be communicated with ........................................48
Routing of alarms ...................................................................................49
Alarms from controllers .......................................................................51
Modem and IP settings ........................................................................52
Design some functions yourself .......................................................53
Alarms for boolean functions ............................................................54
AKC controllers on DANBUSS.............................................................55
Configuration of inputs and outputs ..............................................57
Set alarm priorities .................................................................................58
Lock configuration .................................................................................59
Check configuration ..............................................................................60
Check of connections ....................................................................................61
Find the controllers on the network .........................................................62
Setup of controllers ........................................................................................63
Setup functions ................................................................................................64
Logs ......................................................................................................................65
Plant operations ...............................................................................................67
First start of system manager ......................................................................81
Check alarms ............................................................................................81
Lock configuration of connections ..................................................82
Check level for safety ............................................................................83
Conclusion ................................................................................................83
5. Regulating function
Local data communication ..........................................................................85
Extern data communication ........................................................................86
Alarm handling ................................................................................................88
Plant controls ....................................................................................................90
Logs ......................................................................................................................94
Operation ...........................................................................................................96
Clock.....................................................................................................................97
2 | BC041586425769en-000602 © Danfoss | DCS (vt) | 2020.01
User Guide | Network control AK-SM 720
1. Introduction
Application
AK-SM 720 is a complete system manager to control data commu­nication to ADAP-KOOL® Refrigeration Control Systems. The system unit makes it possible to transmit alarms and system functions to external receivers.
The main function of the system manager is to transmit alarms. It also contains the primary functions that the refrigeration sys­tem’s controllers can use to sub-optimise the individual refrigera­tion sites.
To mention some of the various functions briefly:
• Alarm receiver
• Forward alarms
• Collect logs
• Schedules
• Defrost groups
• Light functions
• Energy-saving functions
• Design of Boolean functions
Examples
Here are a couple of examples where the system manager takes care of communication to other units.
Receive alarms and logs from the controllers in the application
Modem connection to the service company
Local data communication can be:
• LON RS 485
• MODBUS
• DANBUSS (this does, however, also require a protocol interface type AK-PI 200. Literature no. RS8EX)
• There is a maximum of 200 controllers on the data communica­tion. A maximum of 120 units of the EKC incl. SLV, where there must be a maximum of 15 different types and software versions.
• TCP/IP
External data communication can be:
• TCP/IP
• Modem
Operation must take place using:
• Service tool type AK-ST
The system unit can transmit alarms and logs to:
• System software type AKM
© Danfoss | DCS (vt) | 2020.01 BC041586425769en-000602 | 3
Retrieve functions from some controllers and forward them to others
User Guide | Network control AK-SM 720
Principles
The great advantage of this series of controllers is that it can be extended as the size of the plant is increased. It has been developed for refrigeration control systems, but not for any specific application – variation is created through the read-in software and the way you choose to define the connections. It is the same modules that are used for each regulation and the composition can be changed, as required. With these modules (building blocks) it is possible to create a multitude of various kinds of regulations. But it is you who must help adjusting the regulation to the actual needs – these instructions will assist you to find your way through all the questions so that the regulation can be defined and the connections made.
Controller
Top part
Bottom part
The controller is the cornerstone of the regulation. The module has inputs and outputs capable of handling small systems.
• The bottom part – and hence the terminals – are the same for all controller types.
• The top part contains the intelligence with software. This unit will vary according to controller type. But it will always be supplied together with the bottom part.
• In addition to the software the top part is provided with connections for data communication and address setting.
Advantages
• The controller’s size can “grow” as systems grow
• The software can be set for one or more regulations
• Several regulations with the same components
• Extension-friendly when systems requirements are changed
• Flexible concept:
- Controller series with common construction
- One principle – many regulation uses
- modules are selected for the actual connection requirements
- The same modules are used from regulation to regulation
Extension modules
If the system grows and more functions have to be controlled, the regulation can be extended. With extra modules more signals can be received and more relays cut in and out – how many of them – and which – is determined by the relevant application.
Examples
A regulation with few connections can be performed with the controller module alone
If there are many connections one or more extension modules have to be mounted
4 | BC041586425769en-000602 © Danfoss | DCS (vt) | 2020.01
User Guide | Network control AK-SM 720
Direct connection
Setup and operation of an AK controller must be accomplished via the “AK-Service Tool” software program.
The programme is installed on a PC, and setup and operation of the various functions are carried out via the controller’s menu displays.
Displays
The menu displays are dynamic, so that different settings in one menu will result in different setting possibilities in other menus.
A simple application with few connections will give a setup with few settings. A corresponding application with many connections will give a setup with many settings. From the overview display there is access to further displays for the compressor regulation and the condenser regulation. At the bottom of the display there is access to a number of general functions, such as "network overview", “time table”, “log function”, “alarms”, "plant control" and “service” (configuration).
Data communication
The controller forwards the data communication to all of the connected controllers. It receives measurements from selected functions. The measurements are sent to other controllers, which use the value in the control function. The controller receives alarms from all connected controllers and forwards them to the defined receivers.
Users
All users must be assigned a user profile which either gives access to full operation or gradually limits the operation to the lowest level that only allows you “to see”.
Users are added and defined in the menu item “Configuration”/ ”Authorisation”.
© Danfoss | DCS (vt) | 2020.01 BC041586425769en-000602 | 5
User Guide | Network control AK-SM 720
Light-emitting diodes
A number of light-emitting diodes makes it possible to follow the signals that are received and transmitted by the controller.
Log
From the log function you can define the measurements you wish to be shown. The collected values can be printed, or you may export them to a file. You can open the file in Excel.
If you are in a service situation you can show measurements in a trend function. The measurements are then made realtime and displayed instantly.
n Power n Comm n DO1 n Status n DO2 n Alarm n DO3 n Service Tool n DO4 n LON n DO5 n RS485 n DO6 n LAN n DO7 n DO8 n Service Pin
Slow flash = OK Quick flash = answer from master in 10 min. after network installation Constantly ON = error Constantly OFF = error
Flash = Active alarm / not cancelled Constant On = Aktive alarm / cancelled
External communication
Network installation
Alarm
The display gives you an overview of all active alarms. If you wish to confirm that you have seen the alarm you can cross it off in the acknowledge field. If you want to know more about a current alarm you can click on it and obtain an information display on the screen.
A corresponding display exists for all earlier alarms. Here you can upload information if you need further details about the alarm history.
6 | BC041586425769en-000602 © Danfoss | DCS (vt) | 2020.01
User Guide | Network control AK-SM 720
2. Design of a controller
This section describes how the controller is designed.
The controller in the system is based on a uniform connection platform where any deviations from regulation to regulation is determined by the used top part with a specific software and by which input and output signals the relevant application will
Module survey
• Controller module – capable of handling minor plant require­ments.
• Extension modules. When the complexity becomes greater and additional inputs or outputs are required, modules can be at­tached to the controller. A plug on the side of the module will transmit the supply voltage and data communication between the modules.
• Top part The upper part of the controller module contains the intelligence. This is the unit where the regulation is defined and where data communication is connected to other controllers in a bigger network.
• Connection types There are various types of inputs and outputs. One type may, for example, receive signals from sensors and switches, another may receive a voltage signal, and a third type may be outputs with relays etc. The individual types are shown in the table below.
require. If it is an application with few connections, the controller module (top part with belonging bottom part) may be sufficient. If it is an application with many connections it will be necessary to use the controller module plus one or more extension modules. This section will give you a survey of possible connections plus assistance in selecting the modules required by your actual application.
• Optional connection When a regulation is planned (set up) it will generate a need for a number of connections distributed on the mentioned types. This connection must then be made on either the controller module or an extension module. The only thing to be observed is that the types must not be mixed (an analog input signal must for instance not be connected to a digital input).
• Programming of connections The controller must know where you connect the individual input and output signals. This takes place in a later configura­tion where each individual connection is defined based on the following principle:
- to which module
- at which point (”terminals”)
- what is connected (e.g. pressure transmitter/type/ pressure range)
Extension module with additional analog inputs
Controller with analog inputs and relay outputs.
Top part
Extension module with additional relay outputs and additional analog inputs.
The module with additional relay outputs is also available in a version where the top part is provided with change-over switches so that the relays can be overridden.
Extension module with analog output signals
© Danfoss | DCS (vt) | 2020.01 BC041586425769en-000602 | 7
User Guide | Network control AK-SM 720
1. Controller
Type Function Application
AK-SM 720 System manager Control data communication
2. Extension modules and survey of inputs and outputs
Type Analog
inputs
For sensors, pressure trans­mitters etc.
System manager 11 4 4 - - - - -
Extension modules
AK-XM 101A 8
AK-XM 102A 8
AK-XM 102B 8
AK-XM 204A 8
AK-XM 204B 8 x
AK-XM 205A 8 8
AK-XM 205B 8 8 x
AK-XM 107A 8
The following extension module can be placed on the PC board in the controller module. There is only room for one module.
AK-OB 110 2
On/Off outputs On/off supply voltage
Relay (SPDT)
Solid state Low voltage
(DI signal)
(max. 80 V)
High voltage (max. 260 V)
Pulse counter Low voltage (max 30 V)
Analog outputs
0 – 10 V DC For override of
Module with switches
relay outputs
3. AK operation and accessories
Type Function Application
Operation
AK-ST 500 Software for operation of AK controllers AK-operation
- Cable between PC and AK controller AK - Com port
- Cable between zero modem cable and AK controller AK - RS 232
Accessories Power supply modul 230 V / 115 V to 24 V DC
AK-PS 075 18 VA DC AK-PS 150 36 VA DC
Supply for controller
On the following pages there is data specific to each module.
8 | BC041586425769en-000602 © Danfoss | DCS (vt) | 2020.01
User Guide | Network control AK-SM 720
Common data for modules
Supply voltage 24 V DC/AC +/- 20%
Power consumption AK-SM 720 8 VA
AK-XM 101, 102, 107 2 VA
AK-XM 204, 205 5 VA
Analog inputs Pt 1000 ohm /0 °C Resolution: 0.1 °C
Pressure transmitter type AKS 32R / AKS 32 (1 – 5 V)
Voltage signal 0 – 10 V
Contact function (On/Off) On at R < 20 ohm
On/off supply voltage inputs Low voltage
Relay outputs SPDT
Solid state outputs Can be used for loads that are cut in and
0 / 80 V AC/DC
High voltage 0 / 260 V AC
AC-1 (ohmic) 4 A
AC-15 (inductive) 3 A
U Min. 24 V
out frequently, e.g. : rail heat, fans and AKV valve
Accuracy: +/- 0.5 °C
Resolution: 1 mV Accuracy +/- 10 mV Max. connection of 5 pressure transmitters on one module
Off at R > 2K ohm (Gold -plated contacts not necessary)
Off: U < 2 V On: U > 10 V
Off: U < 24 V On: U > 80 V
Max. 230 V Low and high voltage must not be connected to the same output group
Max. 240 V AC , Min. 48 V AC Max. 0.5 A, Leak < 1 mA Max. 1 AKV
Ambient temperature During transport -40 – 70 °C
During operation -20 – 55 °C ,
0 – 95% RH (non condensing) No shock influences / vibrations
Enclosure Material PC / ABS
Density IP10 , VBG 4
Mounting For mounting on panel wall or DIN rail
Weight with screw terminals Modules in100- / 200- / controller-series Ca. 200 g / 500 g / 600 g
Approvals EU low voltage directive and EMC require-
ments are complied with
The mentioned data applies to all modules. If data is specific, this is mentioned together with the module in question.
LVD tested according to EN 60730 EMC tested Immunity according to EN 61000-6-2 Emission according to EN 61000-6-3
© Danfoss | DCS (vt) | 2020.01 BC041586425769en-000602 | 9
User Guide | Network control AK-SM 720
Dimensions
The module dimension is 72 mm. Modules in the 100-series consist of one module Modules in the 200-series consist of two modules Controllers consist of three modules The length of an aggregate unit = n x 72 + 8
A power supply module is either 36 mm or 54 mm If there is space on the DIN rail, the power sup­ply module can be positioned to the left of the system manager.
10 | BC041586425769en-000602 © Danfoss | DCS (vt) | 2020.01
User Guide | Network control AK-SM 720
System manager AK-SM
Function
There are several controllers in the series. The function is determined by the programmed software, but outwardly the controllers are identical – they all have the same connection possibilities: 11 analog inputs for sensors, pressure transmitters, voltage signals
and contact signals.
8 digital outputs, with 4 Solid state outputs and 4 relay outputs
Supply voltage
24 V AC or DC to be connected to the controller. The 24 V must not be retransmitted and used by other controllers as it is not galvanically separated from inputs and outputs. In other words, you must use a transformer for each controller. Class II is required. The terminals must not be earthed. The supply voltage to any extension modules is transmitted via the plug on the right-hand side. The size of the transformer is determined by the power requirement of the total number of modules.
The supply voltage to a pressure transmitter can be taken either from the 5 V output or from the 12 V output depending on transmitter type.
PIN
Data communication
The installation has to be made as mentioned in the separate instructions.
Address setting
When the system manager is configured, the address must be set in the range 1 to 10. 1 must always be used. If there are more than one, the rest must be set with addresses 2 to 10.
Service PIN When the address has been set, the software must know the set­ting. This is done by pressing the Service PIN button. The “Status” LED will flash when acceptance is received.
Operation
The configuration operation of the controller must take place from the software programme “Service Tool”. The program must be installed on a PC, and the PC must be connected to the controller via the network plug on the front of the unit.
Light-emitting diodes
There are two rows with LED’s. They mean: Left row:
• Voltage supply to the controller
• Communication active with the bottom PC board (red = error)
• Status of outputs DO1 to DO8
Right row:
• Software status
• Alarm when LED flashes. Alarm acknowledged = constant light
• Communication with Service Tool
• Communication on LON
• Communication on MODBUS
• Communication on TCP/IP
• “Service Pin” switch has been activated
Address
Internal communication between the moduls: Quick flash = error Constantly On = error
n Power n Comm n DO1 n Status n DO2 n Alarm n DO3 n Service Tool n DO4 n LON n DO5 n MODBUS n DO6 n LAN n DO7 n DO8 n Service Pin
Status on output 1-8
Slow flash = OK Quick flash = answer from master in 10 min. after network installation Constantly ON = error Constantly OFF = error
Flash = Active alarm / not cancelled Constant On = Active alarm / cancelled
External communication
Network installation
Keep the safety distance!
Low and high voltage must not be connected to the same output group
A small module (option board) can be placed on the bottom part of the controller. The module is described later in the document.
© Danfoss | DCS (vt) | 2020.01 BC041586425769en-000602 | 11
User Guide | Network control AK-SM 720
Point
Analog inputs on 1 - 11
Solid state outputs on 12 - 15
Relay or AKV coil fx 230 V AC
S
Pt 1000 ohm/0°C
Point 1 2 3 4 5 6 7 8 9 10 11
Type AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8 AI9 AI10 AI11
Signal Signal
type
S1 S2 Saux1
Pt 1000 Saux2 SSA SdA
24 and 25 used only when "Op­tion board fitted"
Terminal 15 & 27: 12 V max. 100 mA in total.
Terminal 16 & 28: 5 V max 100 mA in total.
Terminal 17, 18, 29, 30: (Cable screen)
Relay outputs on 16 - 19
Point 12 13 14 15 16 17 18 19
Type DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8
P
AKS 32R
3: Brown
2: Blue
1: Black
P0A P0B PcA PcB
AKS 32
3: Brown
2: Black
1: Red
U
...
On/Off Ext.
Main switch
Day/ Night
Door
DO
AKV
AKV
Comp 1 Comp 2 Fan 1 Alarm Light Rail heat Defrost
Option Board
Please see the signal on the page with the module.
AKS 32R
-1 - xx bar
AKS 32
-1 - zz bar
0 – 5 V
0 – 10 V
Active at:
Closed
/
Open
Active at:
On
/
Off
Signal Module Point Terminal Signal type / Active at
1 (AI 1) 1 - 2
2 (AI 2) 3 - 4
3 (AI 3) 5 - 6
4 (AI 4) 7 - 8
5 (AI 5) 9 - 10
6 (AI 6) 11 - 12
7 (AI 7) 13 - 14
8 (AI 8) 19 - 20
9 (AI 9) 21 - 22
10 (AI 10) 23 - 24
11 (AI 11) 25 - 26
1
12 (DO 1) 31 - 32
13 (DO 2) 33 - 34
14 (DO 3) 35 - 36
15 (DO 4) 37 - 38
16 (DO 5) 39 - 41
17 (DO6) 42 - 44
18 (DO7) 45 - 47
19 (DO8) 48 - 50
24 -
25 -
12 | BC041586425769en-000602 © Danfoss | DCS (vt) | 2020.01
User Guide | Network control AK-SM 720
Extension module AK-XM 101A
Function
The module contains 8 analog inputs for sensors, pressure transmitters, voltage signals and contact signals.
Supply voltage
The supply voltage to the module comes from the previous module in the row.
Supply voltage to a pressure transmitter can be taken from either the 5 V output or the 12 V output depending on transmitter type.
Light-emitting diodes
Only the two top LED’s are used. They indicate the following:
• Voltage supply to the module
• Communication with the controller is active (red = error)
© Danfoss | DCS (vt) | 2020.01 BC041586425769en-000602 | 13
User Guide | Network control AK-SM 720
Point
S
Pt 1000 ohm/0°C
At the top the signal input is the left of the two terminals.
At the bottom the signal input is the right of the two terminals.
Signal Signal
S1 S2 Saux1 Saux2 SSA SdA
type
Pt 1000
Point 1 2 3 4
Type AI1 AI2 AI3 AI4
Point 5 6 7 8
Type AI5 AI6 AI7 AI8
Terminal 9 & 16: 12 V max. 100 mA in total.
Terminal 10 & 15: 5 V max 100 mA in total.
Terminal
11, 12, 13, 14:
(Cable screen)
P
AKS 32R
AKS 32
3: Brown
2: Blue
1: Black
3: Brown
2: Black
1: Red
P0A P0B PcA PcB
U
...
On/Off Ext.
Main switch
Day/ Night
Door
AKS 32R
-1 - xx bar
AKS 32
-1 - zz bar
0 – 5 V 0 – 10 V
Active at:
Closed
/
Open
Signal Module Point
1 (AI 1) 1 - 2
2 (AI 2) 3 - 4
3 (AI 3) 5 - 6
4 (AI 4) 7 - 8
5 (AI 5) 17 - 18
6 (AI 6) 19 - 20
7 (AI 7) 21 - 22
8 (AI 8) 23 - 24
Terminal
Signal type /
Active at
14 | BC041586425769en-000602 © Danfoss | DCS (vt) | 2020.01
User Guide | Network control AK-SM 720
Extension module AK-XM 102A / AK-XM 102B
Function
The module contains 8 inputs for on/off voltage signals.
Signal
AK-XM 102A is for low voltage signals. AK-XM 102B is for high voltage signals.
Supply voltage
The supply voltage to the module comes from the previous module in the row.
Light-emitting diodes
They indicate:
• Voltage supply to the module
• Communication with the controller is active (red = error)
• Status of the individual inputs 1 to 8 (when lit = voltage)
AK-XM 102A
Max. 24 V
On/Off: On: DI > 10 V AC Off: DI < 2 V AC
AK-XM 102B
Max. 230 V
On/Off: On: DI > 80 V AC Off: DI < 24 V AC
© Danfoss | DCS (vt) | 2020.01 BC041586425769en-000602 | 15
User Guide | Network control AK-SM 720
Point
DI
AK-XM 102A: Max. 24 V AK-XM 102B: Max. 230 V
Signal Active at
Ext. Main switch
Day/ Night
Comp. safety 1
Comp. safety 2
Closed
(voltage on)
/
Open
(voltage off)
Point 1 2 3 4
Type DI1 DI2 DI3 DI4
Point 5 6 7 8
Type DI5 DI6 DI7 DI8
Signal Module Point Terminal Active at
1 (DI 1) 1 - 2
2 (DI 2) 3 - 4
3 (DI 3) 5 - 6
4 (DI 4) 7 - 8
5 (DI 5) 9 - 10
6 (DI 6) 11 - 12
7 (DI 7) 13 - 14
8 (DI 8) 15 - 16
16 | BC041586425769en-000602 © Danfoss | DCS (vt) | 2020.01
User Guide | Network control AK-SM 720
Extension module AK-XM 204A / AK-XM 204B
Function
The module contains 8 relay outputs.
Supply voltage
The supply voltage to the module comes from the previous module in the row.
AK-XM 204B only Override of relay
Eight change-over switches at the front make it possible to override the relay’s function. Either to position OFF or ON. In position Auto the controller carries out the control.
Light-emitting diodes
There are two rows with LED’s. They indicate the following: Left row:
• Voltage supply to the controller
• Communication active with the bottom PC board (red = error)
• Status of outputs DO1 to DO8
Right row: (AK-XM 204B only):
• Override of relays Light ON = override Light OFF = no override
AK-XM 204A AK-XM 204B
Fuses
Behind the upper part there is a fuse for each output.
Max. 230 V
AC-1: max. 4 A (ohmic) AC-15: max. 3 A (Inductive)
AK-XM 204B Override of relay
Keep the safety distance!
Low and high voltage must not be connected to the same output group
© Danfoss | DCS (vt) | 2020.01 BC041586425769en-000602 | 17
User Guide | Network control AK-SM 720
Point
Punkt 1 2 3 4 5 6 7 8
Type DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8
DO
Signal Active at
Comp. 1
Comp. 2
Fan 1
Alarm
On
/
Off
Signal Module Point Terminal Active at
1 (DO 1) 25 - 27
2 (DO 2) 28 - 30
3 (DO 3) 31 - 33
4 (DO 4) 34 -36
5 (DO 5) 37 - 39
6 (DO 6) 40 - 42
7 (DO 7) 43 - 45
8 (DO 8) 46 - 48
18 | BC041586425769en-000602 © Danfoss | DCS (vt) | 2020.01
User Guide | Network control AK-SM 720
Extension module AK-XM 205A / AK-XM 205B
Function
The module contains: 8 analog inputs for sensors, pressure transmitters, voltage signals
and contact signals.
8 relay outputs.
Supply voltage
The supply voltage to the module comes from the previous module in the row.
AK-XM 205B only Override of relay
Eight change-over switches at the front make it possible to override the relay’s function. Either to position OFF or ON. In position Auto the controller carries out the control.
Light-emitting diodes
There are two rows with LED’s. They mean: Left row:
• Voltage supply to the controller
• Communication active with the bottom PC board (red = error)
• Status of outputs DO1 to DO8
Right row: (AK-XM 205B only):
• Override of relays ON = override OFF = no override
AK-XM 205A AK-XM 205B
max. 10 V
Fuses
Behind the upper part there is a fuse for each output.
Max. 230 V
AC-1: max. 4 A (ohmic) AC-15: max. 3 A (Inductive)
AK-XM 205B Override of relay
Keep the safety distance!
Low and high voltage must not be connected to the same output group
© Danfoss | DCS (vt) | 2020.01 BC041586425769en-000602 | 19
User Guide | Network control AK-SM 720
Point
S
Pt 1000 ohm/0°C
Signal Signal
type
S1 S2 Saux1
Pt 1000
Saux2 SSA SdA
Point 1 2 3 4 5 6 7 8
Type AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8
Terminal 9 & 21: 12 V max. 100 mA in total.
Terminal 10 & 22: 5 V max 100 mA in total.
Terminal 11, 12, 23, 24 :
(Cable screen)
Point 9 10 11 12 13 14 15 16
Type DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8
P
AKS 32R
AKS 32
U
On/Off
DO
3: Brown
2: Blue
1: Black
3: Brown
2: Black
1: Red
P0A P0B PcA PcB
...
Ext. Main switch
Day/ Night
Door
Comp 1 Comp 2 Fan 1 Alarm Light Rail heat Defrost
AKS 32R
-1 - xx bar
AKS 32
-1 - zz bar
0 – 5 V 0 – 10 V
Active at:
Closed
/
Open
Active at:
on
/
Off
Signal Module Point
1 (AI 1) 1 - 2
2 (AI 2) 3 - 4
3 (AI 3) 5 - 6
4 (AI 4) 7 - 8
5 (AI 5) 13 - 14
6 (AI 6) 15 - 16
7 (AI 7) 17 - 18
8 (AI 8) 19 -20
9 (DO 1) 25 - 27
10 (DO 2) 28 - 30
11 (DO 3) 31 - 33
12 (DO 4) 34 - 36
13 (DO 5) 37 - 39
14 (DO6) 40 - 42
15 (DO7) 43 - 45
16 (DO8) 46 - 48
Terminal
Signal type /
Active at
20 | BC041586425769en-000602 © Danfoss | DCS (vt) | 2020.01
User Guide | Network control AK-SM 720
Extension module AK-XM 107A
Function
The module contains eight inputs for pulse counting. As an alternative, the input can be used to register an On/Off signal. (DI function).
Supply voltage
The supply voltage for the module comes from the previous mod­ule in the sequence.
LEDs
These indicate the following:
• Voltage of the module
• Communication with the controller is active (red = error)
(There is no LED indication for the individual signal inputs)
Signal
The signal is registered in accordance with DIN 43864. Rise times and fall times must be less than 5 ms. On and off times must be greater than 30 ms.
© Danfoss | DCS (vt) | 2020.01 BC041586425769en-000602 | 21
User Guide | Network control AK-SM 720
Point
CI
Point 1 2 3 4
Type CI1 CI2 CI3 CI4
Point 5 6 7 8
Type CI5 CI6 CI7 CI8
Signal Active at
Puls - - -
Signal Module Point Terminal Active at
1 (CI 1) 1 - 2 - - ­2 (CI 2) 3 - 4 - - ­3 (CI 3) 5 - 6 - - ­4 (CI 4) 7 - 8 - - ­5 (CI 5) 9 - 10 - - ­6 (CI 6) 11 - 12 - - ­7 (CI 7) 13 - 14 - - ­8 (CI 8) 15 - 16 - - -
22 | BC041586425769en-000602 © Danfoss | DCS (vt) | 2020.01
User Guide | Network control AK-SM 720
Extension module AK-OB 110
Function
The module contains two analog voltage outputs of 0 – 10 V.
Supply voltage
The supply voltage to the module comes from the controller module.
Placing
The module is placed on the PC board in the controller module.
Point
The two outputs have points 24 and 25. They are shown on the earlier page where the controller is also mentioned.
Max. load I < 2.5 mA R > 4 kohm
AO
AO 0 – 10 V
Module
Point 24 25
Type AO1 AO2
1
AO2
AO1
© Danfoss | DCS (vt) | 2020.01 BC041586425769en-000602 | 23
User Guide | Network control AK-SM 720
Power supply module AK-PS 075 / 150
Function
24 V supply for controller.
Supply voltage
100 V AC to 240 V AC 50/60Hz
Placing
On wall or DIN-rail
Effect
Type Output tension Output current Power
AK-PS 075 24 V DC 0.75 A 18 VA
AK-PS 150 24 V DC
(adjustable)
Dimension
Type High Width
AK-PS 075 90 mm 36 mm
AK-PS 150 90 mm 54 mm
1.5 A 36 VA
Connections
Supply to a System manager
AK-PS 075
AK-PS 150
24 | BC041586425769en-000602 © Danfoss | DCS (vt) | 2020.01
User Guide | Network control AK-SM 720
Preface to design
In most cases the system manager may be able to manage the control process without any kind of supplementary modules. Ex­pansion modules will only be needed when measuring consump­tion, when using a large number of relays or when using Boolean functions.
Be aware of the following when the number of extension modules is being planned. A signal may have to be changed, so that an additional module may be avoided.
• An ON/OFF signal can be received in two ways. Either as a contact signal on an analog input or as voltage on a low or high-voltage module.
Functions
Clock function
Clock function and change-over between summer time and win­ter time are contained in the system manager. The clock’s setting is retained if there is a power failure.
Start/stop of regulation
Regulation can be started and stopped via the software. It cannot be stopped with a switch function.
Alarm function
If the alarm is to be sent to a signal transmitter, a relay output will have to be used.
System controls
Some of the possible system controls will require input signals or output signals.
• Weekly schedule with the store’s hours of business
If there has to be an override to “day”, a switch function will be required. If there has to be an override to “night”, a switch function will be required.
• An ON/OFF output signal can be given in two ways. Either with a relay switch or with solid state. The primary difference is the per­mitted load and that the relay switch contains a cutout switch.
Mentioned below is a number of functions and connections that may have to be considered when a regulation has to be planned. There are more functions in the controller than the ones mentioned here, but those mentioned have been included in order that the need for connections can be established.
• Light control
A signal can be received from two light sensors. Each sensor requires an analogue input. Up to eight zones can be controlled. Each zone will require a relay output or a triac output.
• Adaptive rail heat
A signal can be received from three dew point sensors. Each sen­sor requires two analogue inputs.
• Consumption measurement
When measuring consumption an expansion module must be used for pulse counting. A synchronisation signal will require an analogue or a digital input. A tariff signal will require an analogue or a digital input. Two tariff signals can be received.
• Peak load limitation
This function requires a signal from a consumption measure­ment. Up to ten relays can be connected.
• Weekly schedule for day/night operation
A switch signal will be required to override a schedule
• Weekly schedule for defrost
A switch signal will be required to override a schedule
• Weekly schedule for light
A switch signal will be required to override a schedule
• Inject ON function (closes the evaporator controls’ expansion valves in the event of operational problems with the compressors)
The function can be enabled via data communication or it can be wired outside the system manager
© Danfoss | DCS (vt) | 2020.01 BC041586425769en-000602 | 25
Data communication
The controller module has terminals for LON data communication. The requirements to the installation are described in a separate document.
User Guide | Network control AK-SM 720
Connections
In principle there are the following types of connections:
Analog inputs ”AI”
This signal must be connected to two terminals. Signals can be received from the following
sources:
• Temperature signal from Pt 1000 ohm
temperature sensor
• Contact signal where the input is short-
circuited or ”opened”, respectively
• Voltage signal from 0 to 10 V
• Signal from pressure transmitter AKS 32
or AKS 32R The supply voltage is supplied from the module’s terminal board where there is both a 5 V supply and a 12 V supply. When programming the pressure
transmitter’s pressure range must be set.
ON/OFF voltage inputs ”DI”
This signal must be connected to two terminals.
• The signal must have two levels, either 0 V
or ”voltage” on the input. There are two different extension modules for this signal type:
- low-voltage signals, e.g. 24 V
- high-voltage signals, e.g. 230 V
When programming the function must be set:
• Active when the input is without voltage
• Active when voltage is applied to the
input.
ON/OFF output signals ”DO”
There are two types, as follows:
• Relay outputs All relay outputs are with change-over relay so that the required function can be obtained when the controller is without voltage.
• Solid state outputs Reserved for AKV valves, but output can cut an external relay in and out, as with a relay output. The output is only found on the controller module.
When programming the function must be set:
• Active when the output is activated
• Active when the output is not activated.
Analog output signal ”AO”
This signal is to be used if a control signal is to be transmitted to an external unit, e.g. a frequency converter. When programming the signal range must be defined: 0 – 5 V, 1 – 5 V, 0 – 10 V or 2 – 10 V.
Pulse counter inputs
This signal must be used if consumption measurement is to take place.
Limitations
As the system is very flexible regarding the number of connected units you must check whether your selection complies with the few limitations there are. The complexity of the controller is determined by the software, the size of the processor, and the size of the memory. It provides the controller with a certain number of connections from which data can be downloaded, and others where coupling with relays can be performed.
There must a maximum of 200 controllers on the data communi­cation. A maximum of 120 units of the EKC type, where there must be a maximum of 15 different types and software versions.
26 | BC041586425769en-000602 © Danfoss | DCS (vt) | 2020.01
• The sum of connections cannot exceed 80.
• The number of extension modules must be limited so that the total power will not exceed 32 VA (including controller).
• No more than five pressure transmitters may be connected to one controller module.
• No more than five pressure transmitters may be connected to one extension module.
User Guide | Network control AK-SM 720
Design of a System manager
Procedure:
1. Make a sketch of the system in question
2. Check that the controller’s functions cover the required application
3. Consider the connections to be made
4. Use the planning table. / Note down the number of connections. / add up
5. Are there enough connections on the controller module? – If not, can they be obtained by changing an ON/OFF input signal from voltage signal to contact signal, or will an extension module be required?
6. Decide which extension modules are to be used
7. Check that the limitations are observed
8. Calculate the total length of modules
9. The modules are linked together
10. The connection sites are established
11. Draw a connection diagram or a key diagram
12. Size of supply voltage/power supply
1. Sketch
Make a sketch of the system in question
© Danfoss | DCS (vt) | 2020.01 BC041586425769en-000602 | 27
User Guide | Network control AK-SM 720
2. System functions
Application
Control of data communication on the refrigera­tion system
Control of data communication for external opera­tion
Forward alarms and data collected x
Local data communication
LON RS485 together with
- Controllers type EKC
- Controllers type AK
- Frequency converter type AKD MODBUS together with similar controllers that
have MODBUS communication TCP/IP together with other AK-SM x TCP/IP to AK-PI 200 and onwards to controllers
with DANBUSS Max. number of controllers (addresses) in a
network
External data communication
Via modem and phone net x Via TCP/IP and Internet x
200, although max. 120 EKC incl. SLV
x
x
x
x
x
User registration
User interface with Password and authorisation levels
History Event x
Operation
Via PC and software type AK-ST x
Clock
Clock function with battery backup x Resets the clock in the controllers after a power
failure
Safety
Communication control x Watchdog function with adjustable interval time x Data communication with "I'm a live" information x High level of security against undesired user
access
x
x
x
A bit more about the functions ("2" continued)
Alarm management
LOG of alarms x
Routing of alarms to Systemsoftware x
A relay can be defined to an alarm relay x
System controls
Weekly schedule with the store’s hours of business x Weekly schedules with time specified in relation to
hours of business On/off control 5 Weekly schedules for use together with day/night
operation and start of defrost Override weekly schedules with a switch function 10 Switch between day operation and night opera-
tion
Defrost start
Coordinated defrost (common start after defrost) x Inject ON function (closes the evaporator controls’
expansion valves in the event of operational prob­lems with the compressors)
P0-control 5 / 120 sections
Light control
Adaptive rail heat
Adaptive defrost
Consumption measurement 8
Load sheeding x
Synchronising signal x
max. 30 controllers
max. 30 controllers
x
10
Max. 20 groups of
Max. 20 groups of
5 / 120 sections
2 light sensors,
8 relais, 8 zones
3 groups /
30 sections 10 groups /
30 sections
Here is a little more about some of the functions that must use an input or an output.
Modem connection
It is recommended that the supply voltage to the modem be provided through a relay, so that the system manager can start the modem in a controlled way.
The “Inject On” override function
This function closes expansion valves on evaporator controls when all compressors have stopped. The function can take place via data communication, or it can be wired via a relay output on the compressor control.
Boolean functions
A function in the system unit makes it possible to set up some logical functions. The functions can have both inputs and outputs. The function is described in a separate document. Please refer to literature sheet number RC8CA. This setup of Boolean functions should only be undertaken by trained personnel.
If you want to know more about the functions, go to chapter 5.
LOG
Stores LOG data from the connected controllers x
28 | BC041586425769en-000602 © Danfoss | DCS (vt) | 2020.01
User Guide | Network control AK-SM 720
3. Connections
Here is a survey of the possible connections. The texts can be read in context with the table on the next page.
Analog inputs
Temperature sensors
Up to 3 sensors for dew point measurement and 4 sensors for boolean logic can be connected.
Pressure transmitter
A pressure transmitter type AKS 32 or AKS 32R can supply signals to a maximum of five controllers.
Voltage signal
• 0 – 10 V
Used when signal is received from another control. E.g. signal from dew point sensor. (A dew point sensor delivers two signals – a temperature sensor signal and a voltage signal)
On/Off-inputs
Contact function (on an analog input) or Voltage signal (on an extension module)
• Switches to override a weekly schedule
• Switches to override light control
• Signal to register tariff levels
Pulse counter input (on an expansion module)
• E.g. for energy registration
On/off-outputs
Relay outputs
• Voltage supply to modem
• Watch dog function
• Injection On function (signal to evaporator control. One each suction group)
• Alarm relay
• Light control
• Load sheeding
Solid state outputs
The solid state outputs on the controller module may be used for the same functions as those mentioned under “relay outputs”. (The output will always be “OFF” when the controller has a power failure).
Example
• AK-SM 720 is with data communication for EKC controllers
• Modem connection for alarm routing (for System software AKM)
• Modem connection for external operation (for Service tool)
• Alarm output
• Contact to reset alarms
• Energy measurement, which receives puls signal from extern unit.
Data from this example is used on the next page. The result is that the following modules should be used:
• AK-SM 720 controller
• AK-XM 107A pulse module
© Danfoss | DCS (vt) | 2020.01 BC041586425769en-000602 | 29
User Guide | Network control AK-SM 720
4. Planning table
The table helps you establish whether there are enough inputs and outputs on the system manager. If there are not enough of them, it must be extended by one or more of the mentioned extension modules.
Note down the connections you will require and add them up
Analog inputs
Temperature signal from dew point sensor (max. 3) Voltage signal from dew point sensor (max. 3) Voltage signal from a light sensor (max. 2)
Analog input signal
Example
On/off voltage signal
Example
On/off voltage signal
Example
Pulse module
Example
On/Off output signal
Example
7
Limitations
On/off inputs Con-
tact Contact for overriding of week schedule for day/night operation Contact to overriding of weekly schedule for light Pulse signal from meter for electr., gas, water etc. 1 On/Off signal about tariff change Pulse pressure for stop of alarm 1
On/off outputs
Voltage supply for modem (reset function) 1 Alarm relay 1 Light zones (up to 8 relays)
5. Load sheeding limit (up to 10 relays)
6. Sum of connections 1 1 2 Sum = max. 80
Number of connections on a System manager 11 11 0 0 0 0 0 0 8 8
Missing connections, if applicable 0 - - 1 0
The missing connections to be supplied by one or more extension modules: Sum of power
AK-XM 101A (8 analog inputs) ___ pcs. á 2 VA = __ AK-XM 102A (8 digital low voltage inputs) ___ pcs. á 2 VA = __ AK-XM 102B (8 digital high voltage inputs) ___ pcs. á 2 VA = __ AK-XM 107A (8 pulse inputs) 1 ___ pcs. á 2 VA = __ AK-XM 204A / B (8 relay outputs) ___ pcs. á 5 VA = __ AK-XM 205A / B (8 analog inputs + 8 relay outputs) ___ pcs. á 5 VA = __
24 V 230 V
Pressure transmit­ters: Max. 5 each/ module
Boolean logic: There are limita­tions to the num­ber of functions. Refer to separate document RC8CA.
1 pcs. á 8 VA = 8 Sum = Sum = max. 32 VA
Example: None of the 3 limita­tions are exceeded => OK
30 | BC041586425769en-000602 © Danfoss | DCS (vt) | 2020.01
Loading...
+ 68 hidden pages