AK-SM 720 is a complete system manager to control data communication to ADAP-KOOL® Refrigeration Control Systems.
The system unit makes it possible to transmit alarms and system
functions to external receivers.
The main function of the system manager is to transmit alarms.
It also contains the primary functions that the refrigeration system’s controllers can use to sub-optimise the individual refrigeration sites.
To mention some of the various functions briefly:
• Alarm receiver
• Forward alarms
• Collect logs
• Schedules
• Defrost groups
• Light functions
• Energy-saving functions
• Design of Boolean functions
Examples
Here are a couple of examples where the system manager takes
care of communication to other units.
Receive alarms and logs from the controllers in the application
Modem connection to the service company
Local data communication can be:
• LON RS 485
• MODBUS
• DANBUSS (this does, however, also require a protocol interface
type AK-PI 200. Literature no. RS8EX)
• There is a maximum of 200 controllers on the data communication.
A maximum of 120 units of the EKC incl. SLV, where there must
be a maximum of 15 different types and software versions.
Retrieve functions from some controllers and forward them to others
User Guide | Network control AK-SM 720
Principles
The great advantage of this series of controllers is that it can
be extended as the size of the plant is increased. It has been
developed for refrigeration control systems, but not for any
specific application – variation is created through the read-in
software and the way you choose to define the connections.
It is the same modules that are used for each regulation and the
composition can be changed, as required. With these modules
(building blocks) it is possible to create a multitude of various
kinds of regulations. But it is you who must help adjusting the
regulation to the actual needs – these instructions will assist you
to find your way through all the questions so that the regulation
can be defined and the connections made.
Controller
Top part
Bottom part
The controller is the cornerstone of the regulation. The module has inputs and
outputs capable of handling small systems.
• The bottom part – and hence the terminals – are the same for all controller types.
• The top part contains the intelligence with software. This unit will vary according
to controller type. But it will always be supplied together with the bottom part.
• In addition to the software the top part is provided with connections for data
communication and address setting.
Advantages
• The controller’s size can “grow” as systems grow
• The software can be set for one or more regulations
• Several regulations with the same components
• Extension-friendly when systems requirements are changed
• Flexible concept:
- Controller series with common construction
- One principle – many regulation uses
- modules are selected for the actual connection requirements
- The same modules are used from regulation to regulation
Extension modules
If the system grows and more functions have to be controlled, the regulation can be
extended.
With extra modules more signals can be received and more relays cut in and out
– how many of them – and which – is determined by the relevant application.
Examples
A regulation with few connections can
be performed with the controller module
alone
If there are many connections one or more
extension modules have to be mounted
Setup and operation of an AK controller must be accomplished via
the “AK-Service Tool” software program.
The programme is installed on a PC, and setup and operation of
the various functions are carried out via the controller’s menu
displays.
Displays
The menu displays are dynamic, so that different settings in one
menu will result in different setting possibilities in other menus.
A simple application with few connections will give a setup with
few settings.
A corresponding application with many connections will give a
setup with many settings.
From the overview display there is access to further displays for
the compressor regulation and the condenser regulation.
At the bottom of the display there is access to a number of general
functions, such as "network overview", “time table”, “log function”,
“alarms”, "plant control" and “service” (configuration).
Data communication
The controller forwards the data communication to all of the
connected controllers. It receives measurements from selected
functions. The measurements are sent to other controllers, which
use the value in the control function.
The controller receives alarms from all connected controllers and
forwards them to the defined receivers.
Users
All users must be assigned a user profile which either gives access
to full operation or gradually limits the operation to the lowest
level that only allows you “to see”.
Users are added and defined in the menu item “Configuration”/
”Authorisation”.
A number of light-emitting diodes makes it possible to follow the
signals that are received and transmitted by the controller.
Log
From the log function you can define the measurements you wish
to be shown.
The collected values can be printed, or you may export them to a
file. You can open the file in Excel.
If you are in a service situation you can show measurements in a
trend function. The measurements are then made realtime and
displayed instantly.
n Power
n Comm
n DO1 n Status
n DO2 n Alarm
n DO3 n Service Tool
n DO4 n LON
n DO5 n RS485
n DO6 n LAN
n DO7
n DO8 n Service Pin
Slow flash = OK
Quick flash = answer from master in 10 min.
after network installation
Constantly ON = error
Constantly OFF = error
Flash = Active alarm / not cancelled
Constant On = Aktive alarm / cancelled
External communication
Network installation
Alarm
The display gives you an overview of all active alarms. If you wish
to confirm that you have seen the alarm you can cross it off in the
acknowledge field.
If you want to know more about a current alarm you can click on it
and obtain an information display on the screen.
A corresponding display exists for all earlier alarms. Here you can
upload information if you need further details about the alarm
history.
This section describes how the controller is designed.
The controller in the system is based on a uniform connection
platform where any deviations from regulation to regulation is
determined by the used top part with a specific software and
by which input and output signals the relevant application will
Module survey
• Controller module – capable of handling minor plant requirements.
• Extension modules. When the complexity becomes greater and
additional inputs or outputs are required, modules can be attached to the controller. A plug on the side of the module will
transmit the supply voltage and data communication between
the modules.
• Top part
The upper part of the controller module contains the intelligence.
This is the unit where the regulation is defined and where data
communication is connected to other controllers in a bigger
network.
• Connection types
There are various types of inputs and outputs. One type may, for
example, receive signals from sensors and switches, another may
receive a voltage signal, and a third type may be outputs with
relays etc. The individual types are shown in the table below.
require. If it is an application with few connections, the controller
module (top part with belonging bottom part) may be sufficient.
If it is an application with many connections it will be necessary to
use the controller module plus one or more extension modules.
This section will give you a survey of possible connections plus
assistance in selecting the modules required by your actual
application.
• Optional connection
When a regulation is planned (set up) it will generate a need for
a number of connections distributed on the mentioned types.
This connection must then be made on either the controller
module or an extension module. The only thing to be observed
is that the types must not be mixed (an analog input signal must
for instance not be connected to a digital input).
• Programming of connections
The controller must know where you connect the individual
input and output signals. This takes place in a later configuration where each individual connection is defined based on the
following principle:
- to which module
- at which point (”terminals”)
- what is connected (e.g. pressure transmitter/type/
pressure range)
Extension module with
additional analog inputs
Controller with analog inputs and
relay outputs.
Top part
Extension module with additional
relay outputs and additional
analog inputs.
The module with additional relay outputs is
also available in a version where the top part
is provided with change-over switches so
that the relays can be overridden.
The module dimension is 72 mm.
Modules in the 100-series consist of one module
Modules in the 200-series consist of two
modules
Controllers consist of three modules
The length of an aggregate unit = n x 72 + 8
A power supply module is either 36 mm or 54
mm
If there is space on the DIN rail, the power supply module can be positioned to the left of the
system manager.
There are several controllers in the series. The function is
determined by the programmed software, but outwardly the
controllers are identical – they all have the same connection
possibilities:
11 analog inputs for sensors, pressure transmitters, voltage signals
and contact signals.
8 digital outputs, with 4 Solid state outputs and 4 relay outputs
Supply voltage
24 V AC or DC to be connected to the controller.
The 24 V must not be retransmitted and used by other controllers
as it is not galvanically separated from inputs and outputs. In
other words, you must use a transformer for each controller. Class
II is required. The terminals must not be earthed.
The supply voltage to any extension modules is transmitted via
the plug on the right-hand side.
The size of the transformer is determined by the power
requirement of the total number of modules.
The supply voltage to a pressure transmitter can be taken either
from the 5 V output or from the 12 V output depending on
transmitter type.
PIN
Data communication
The installation has to be made as mentioned in the separate
instructions.
Address setting
When the system manager is configured, the address must be set
in the range 1 to 10. 1 must always be used. If there are more than
one, the rest must be set with addresses 2 to 10.
Service PIN
When the address has been set, the software must know the setting. This is done by pressing the Service PIN button. The “Status”
LED will flash when acceptance is received.
Operation
The configuration operation of the controller must take place from
the software programme “Service Tool”. The program must be
installed on a PC, and the PC must be connected to the controller
via the network plug on the front of the unit.
Light-emitting diodes
There are two rows with LED’s. They mean:
Left row:
• Voltage supply to the controller
• Communication active with the bottom PC board (red = error)
• Status of outputs DO1 to DO8
Right row:
• Software status
• Alarm when LED flashes. Alarm acknowledged = constant light
• Communication with Service Tool
• Communication on LON
• Communication on MODBUS
• Communication on TCP/IP
• “Service Pin” switch has been activated
Address
Internal communication
between the moduls:
Quick flash = error
Constantly On = error
n Power
n Comm
n DO1 n Status
n DO2 n Alarm
n DO3 n Service Tool
n DO4 n LON
n DO5 n MODBUS
n DO6 n LAN
n DO7
n DO8 n Service Pin
Status on output 1-8
Slow flash = OK
Quick flash = answer from master in 10 min.
after network installation
Constantly ON = error
Constantly OFF = error
Flash = Active alarm / not cancelled
Constant On = Active alarm / cancelled
External communication
Network installation
Keep the safety
distance!
Low and high
voltage must not
be connected to
the same output
group
A small module (option board) can be placed on the bottom part
of the controller. The module is described later in the document.
The supply voltage to the module comes from the previous
module in the row.
AK-XM 204B only
Override of relay
Eight change-over switches at the front make it possible to
override the relay’s function.
Either to position OFF or ON.
In position Auto the controller carries out the control.
Light-emitting diodes
There are two rows with LED’s. They indicate the following:
Left row:
• Voltage supply to the controller
• Communication active with the bottom PC board (red = error)
• Status of outputs DO1 to DO8
Right row: (AK-XM 204B only):
• Override of relays
Light ON = override
Light OFF = no override
AK-XM 204A AK-XM 204B
Fuses
Behind the upper part there is a fuse for each output.
Max. 230 V
AC-1: max. 4 A (ohmic)
AC-15: max. 3 A (Inductive)
AK-XM 204B
Override of relay
Keep the safety distance!
Low and high voltage
must not be connected to
the same output group
The module contains:
8 analog inputs for sensors, pressure transmitters, voltage signals
and contact signals.
8 relay outputs.
Supply voltage
The supply voltage to the module comes from the previous
module in the row.
AK-XM 205B only
Override of relay
Eight change-over switches at the front make it possible to
override the relay’s function.
Either to position OFF or ON.
In position Auto the controller carries out the control.
Light-emitting diodes
There are two rows with LED’s. They mean:
Left row:
• Voltage supply to the controller
• Communication active with the bottom PC board (red = error)
• Status of outputs DO1 to DO8
Right row: (AK-XM 205B only):
• Override of relays
ON = override
OFF = no override
AK-XM 205A AK-XM 205B
max. 10 V
Fuses
Behind the upper part there is a fuse for each output.
Max. 230 V
AC-1: max. 4 A (ohmic)
AC-15: max. 3 A (Inductive)
AK-XM 205B
Override of relay
Keep the safety distance!
Low and high voltage
must not be connected to
the same output group
In most cases the system manager may be able to manage the
control process without any kind of supplementary modules. Expansion modules will only be needed when measuring consumption, when using a large number of relays or when using Boolean
functions.
Be aware of the following when the number of extension modules
is being planned. A signal may have to be changed, so that an
additional module may be avoided.
• An ON/OFF signal can be received in two ways. Either as a contact
signal on an analog input or as voltage on a low or high-voltage
module.
Functions
Clock function
Clock function and change-over between summer time and winter time are contained in the system manager.
The clock’s setting is retained if there is a power failure.
Start/stop of regulation
Regulation can be started and stopped via the software. It cannot
be stopped with a switch function.
Alarm function
If the alarm is to be sent to a signal transmitter, a relay output will
have to be used.
System controls
Some of the possible system controls will require input signals or
output signals.
• Weekly schedule with the store’s hours of business
If there has to be an override to “day”, a switch function will be
required.
If there has to be an override to “night”, a switch function will be
required.
• An ON/OFF output signal can be given in two ways. Either with a
relay switch or with solid state. The primary difference is the permitted load and that the relay switch contains a cutout switch.
Mentioned below is a number of functions and connections
that may have to be considered when a regulation has to be
planned. There are more functions in the controller than the ones
mentioned here, but those mentioned have been included in
order that the need for connections can be established.
• Light control
A signal can be received from two light sensors. Each sensor
requires an analogue input.
Up to eight zones can be controlled. Each zone will require a
relay output or a triac output.
• Adaptive rail heat
A signal can be received from three dew point sensors. Each sensor requires two analogue inputs.
• Consumption measurement
When measuring consumption an expansion module must be
used for pulse counting.
A synchronisation signal will require an analogue or a digital
input.
A tariff signal will require an analogue or a digital input. Two
tariff signals can be received.
• Peak load limitation
This function requires a signal from a consumption measurement.
Up to ten relays can be connected.
• Weekly schedule for day/night operation
A switch signal will be required to override a schedule
• Weekly schedule for defrost
A switch signal will be required to override a schedule
• Weekly schedule for light
A switch signal will be required to override a schedule
• Inject ON function (closes the evaporator controls’ expansion valves
in the event of operational problems with the compressors)
The function can be enabled via data communication or it can
be wired outside the system manager
The controller module has terminals for LON data communication.
The requirements to the installation are described in a separate
document.
User Guide | Network control AK-SM 720
Connections
In principle there are the following types of connections:
Analog inputs ”AI”
This signal must be connected to two
terminals.
Signals can be received from the following
sources:
• Temperature signal from Pt 1000 ohm
temperature sensor
• Contact signal where the input is short-
circuited or ”opened”, respectively
• Voltage signal from 0 to 10 V
• Signal from pressure transmitter AKS 32
or AKS 32R
The supply voltage is supplied from the
module’s terminal board where there is
both a 5 V supply and a 12 V supply.
When programming the pressure
transmitter’s pressure range must be set.
ON/OFF voltage inputs ”DI”
This signal must be connected to two
terminals.
• The signal must have two levels, either 0 V
or ”voltage” on the input.
There are two different extension
modules for this signal type:
- low-voltage signals, e.g. 24 V
- high-voltage signals, e.g. 230 V
When programming the function must be set:
• Active when the input is without voltage
• Active when voltage is applied to the
input.
ON/OFF output signals ”DO”
There are two types, as follows:
• Relay outputs
All relay outputs are with change-over
relay so that the required function can be
obtained when the controller is without
voltage.
• Solid state outputs
Reserved for AKV valves, but output can
cut an external relay in and out, as with a
relay output.
The output is only found on the
controller module.
When programming the function must be set:
• Active when the output is activated
• Active when the output is not activated.
Analog output signal ”AO”
This signal is to be used if a control signal is
to be transmitted to an external unit, e.g. a
frequency converter.
When programming the signal range must
be defined: 0 – 5 V, 1 – 5 V, 0 – 10 V
or 2 – 10 V.
Pulse counter inputs
This signal must be used if consumption
measurement is to take place.
Limitations
As the system is very flexible regarding the number of connected
units you must check whether your selection complies with the
few limitations there are.
The complexity of the controller is determined by the software,
the size of the processor, and the size of the memory. It provides
the controller with a certain number of connections from which
data can be downloaded, and others where coupling with relays
can be performed.
There must a maximum of 200 controllers on the data communication.
A maximum of 120 units of the EKC type, where there must be a
maximum of 15 different types and software versions.
• The number of extension modules must be limited so that the
total power will not exceed 32 VA (including controller).
• No more than five pressure transmitters may be connected to
one controller module.
• No more than five pressure transmitters may be connected to
one extension module.
User Guide | Network control AK-SM 720
Design of a System manager
Procedure:
1. Make a sketch of the system in question
2. Check that the controller’s functions cover the required
application
3. Consider the connections to be made
4. Use the planning table. / Note down the number of
connections. / add up
5. Are there enough connections on the controller module? – If
not, can they be obtained by changing an ON/OFF input signal
from voltage signal to contact signal, or will an extension
module be required?
Control of data communication on the refrigeration system
Control of data communication for external operation
Forward alarms and data collected x
Local data communication
LON RS485 together with
- Controllers type EKC
- Controllers type AK
- Frequency converter type AKD
MODBUS together with similar controllers that
have MODBUS communication
TCP/IP together with other AK-SM x
TCP/IP to AK-PI 200 and onwards to controllers
with DANBUSS
Max. number of controllers (addresses) in a
network
External data communication
Via modem and phone netx
Via TCP/IP and Internetx
200, although max.
120 EKC incl. SLV
x
x
x
x
x
User registration
User interface with Password and authorisation
levels
History Eventx
Operation
Via PC and software type AK-STx
Clock
Clock function with battery backupx
Resets the clock in the controllers after a power
failure
Safety
Communication controlx
Watchdog function with adjustable interval timex
Data communication with "I'm a live" informationx
High level of security against undesired user
access
x
x
x
A bit more about the functions ("2" continued)
Alarm management
LOG of alarmsx
Routing of alarms to Systemsoftwarex
A relay can be defined to an alarm relayx
System controls
Weekly schedule with the store’s hours of businessx
Weekly schedules with time specified in relation to
hours of business
On/off control5
Weekly schedules for use together with day/night
operation and start of defrost
Override weekly schedules with a switch function10
Switch between day operation and night opera-
tion
Defrost start
Coordinated defrost (common start after defrost)x
Inject ON function (closes the evaporator controls’
expansion valves in the event of operational problems with the compressors)
P0-control5 / 120 sections
Light control
Adaptive rail heat
Adaptive defrost
Consumption measurement8
Load sheedingx
Synchronising signalx
max. 30 controllers
max. 30 controllers
x
10
Max. 20 groups of
Max. 20 groups of
5 / 120 sections
2 light sensors,
8 relais,
8 zones
3 groups /
30 sections
10 groups /
30 sections
Here is a little more about some of the functions that must use
an input or an output.
Modem connection
It is recommended that the supply voltage to the modem be
provided through a relay, so that the system manager can start the
modem in a controlled way.
The “Inject On” override function
This function closes expansion valves on evaporator controls when
all compressors have stopped.
The function can take place via data communication, or it can be
wired via a relay output on the compressor control.
Boolean functions
A function in the system unit makes it possible to set up some
logical functions. The functions can have both inputs and outputs.
The function is described in a separate document. Please refer to
literature sheet number RC8CA.
This setup of Boolean functions should only be undertaken by
trained personnel.
If you want to know more about the functions, go to chapter 5.
Here is a survey of the possible connections. The texts can be read
in context with the table on the next page.
Analog inputs
Temperature sensors
Up to 3 sensors for dew point measurement and 4 sensors for
boolean logic can be connected.
Pressure transmitter
A pressure transmitter type AKS 32 or AKS 32R can supply signals
to a maximum of five controllers.
Voltage signal
• 0 – 10 V
Used when signal is received from another control.
E.g. signal from dew point sensor. (A dew point sensor delivers
two signals – a temperature sensor signal and a voltage signal)
On/Off-inputs
Contact function (on an analog input)
or
Voltage signal (on an extension module)
• Switches to override a weekly schedule
• Switches to override light control
• Signal to register tariff levels
Pulse counter input (on an expansion module)
• E.g. for energy registration
On/off-outputs
Relay outputs
• Voltage supply to modem
• Watch dog function
• Injection On function (signal to evaporator control. One each
suction group)
• Alarm relay
• Light control
• Load sheeding
Solid state outputs
The solid state outputs on the controller module may be used
for the same functions as those mentioned under “relay outputs”.
(The output will always be “OFF” when the controller has a power
failure).
Example
• AK-SM 720 is with data communication for EKC controllers
• Modem connection for alarm routing (for System software AKM)
• Modem connection for external operation (for Service tool)
• Alarm output
• Contact to reset alarms
• Energy measurement, which receives puls signal from extern
unit.
Data from this example is used on the next page.
The result is that the following modules should be used:
The table helps you establish whether there are enough inputs
and outputs on the system manager.
If there are not enough of them, it must be extended by one or
more of the mentioned extension modules.
Note down the connections you will require and add them up
Analog inputs
Temperature signal from dew point sensor (max. 3)
Voltage signal from dew point sensor (max. 3)
Voltage signal from a light sensor (max. 2)
Analog input signal
Example
On/off voltage signal
Example
On/off voltage signal
Example
Pulse module
Example
On/Off output signal
Example
7
Limitations
On/off inputsCon-
tact
Contact for overriding of week schedule for day/night operation
Contact to overriding of weekly schedule for light
Pulse signal from meter for electr., gas, water etc.1
On/Off signal about tariff change
Pulse pressure for stop of alarm1
On/off outputs
Voltage supply for modem (reset function)1
Alarm relay1
Light zones (up to 8 relays)
5. Load sheeding limit (up to 10 relays)
6. Sum of connections112 Sum = max. 80
Number of connections on a System manager11 11 00000088
Missing connections, if applicable0--10
The missing connections to be supplied by one or more extension modules:Sum of power
AK-XM 101A (8 analog inputs)___ pcs. á 2 VA = __
AK-XM 102A (8 digital low voltage inputs)___ pcs. á 2 VA = __
AK-XM 102B (8 digital high voltage inputs)___ pcs. á 2 VA = __
AK-XM 107A (8 pulse inputs)1___ pcs. á 2 VA = __
AK-XM 204A / B (8 relay outputs)___ pcs. á 5 VA = __
AK-XM 205A / B (8 analog inputs + 8 relay outputs)___ pcs. á 5 VA = __
24 V230 V
Pressure transmitters: Max. 5 each/
module
Boolean logic:
There are limitations to the number of functions.
Refer to separate
document RC8CA.
1 pcs. á 8 VA = 8
Sum =
Sum = max. 32 VA
Example:
None of the 3 limitations are exceeded
=> OK