8.2 Door management ................................................................................................................................................ 9
8.4 Defrost control .......................................................................................................................................................10
8.5 Fan control ..............................................................................................................................................................11
8.8 Light control ...........................................................................................................................................................13
8.11 Operation of the auxiliary relays .....................................................................................................................13
• Using the unit without observing the manufacturer's
instructions may alter the appliance's safety requirements. Only
NTC probes supplied by Danfoss should be used for the unit to
operate correctly.
• From -40 – +68 °F, if the NTC probe is extended to 3,280 ft with
at least 20AWG cable, the maximum deviation will be 0.45 °F.
• IP65 protection degree is only valid if the cables enter the device
using electrical conduit + gland with IP65 or above. The size of
the glands should be suitable for the diameter of the conduit
used.
• Do not spray the unit directly with high-pressure hoses, as this
could cause damage.
• It should be installed in a place protected from vibrations, water
and corrosive gases, where the ambient temperature does not
exceed the value indicated in the technical data.
• For the reading to be correct, the probe should be used in a
place without heat influences apart from the temperature you
want to measure or control.
• IP65 protection degree is only valid with the protection cover
closed.
Important:
• Before starting the installation, you must take the advice of
local regulations in force.
• The AUXILIARY relays are programmable, and their operation
depends on the configuration.
• The function of the digital inputs depends on the configuration.
• The recommended currents and powers are the maximum
working currents and powers.
3.0 Maintenance
• Clean the surface of the unit with a soft cloth, water and soap.
• Do not use abrasive detergents, gasoline, alcohol or solvents, as this might damage the unit.
4.0 Description
Display
Keypad
Fixed: Stand-By Mode activated. Regulation is paused.
Flashing: Controlled shutdown process for the regulation
underway.
Fixed: The cold solenoid is active.
Flashing: The solenoid should be active but a delay or
protection is preventing this.
(Refer to the Fan start-up section).
Fixed: Cold room door open.
Flashing: The door has been open for a greater time than
has been defined in parameter A12.
Fixed: Compressor active.
Flashing: The compressor should be active but a delay
or protection is preventing this.
There is an active alarm, but not an active HACCP alarm.
Fixed: HACCP alarm active.
(Refer to the Compressor Protection timing section).
Defrost relay active.
Flashing: HACCP alarm registered and unconfirmed.
Press the key to confirm an HACCP alarm.
Fixed: Evaporator fans active.
Flashing: The evaporator fans should be active but a
Continuous cycle mode active.
Cold room light active.
delay is preventing this.
(Refer to the Drip time section).
Alarm in progress muted.
Temperature displayed in ° Fahrenheit / ° Centigrade.
User Guide | Temperature controller for walk-in coolers and freezers, Type AK-RC 251
CORECORE
1
Danfoss
CORECORE
2
Danfoss
80Z8119
6. Wiring
Always disconnect the power supply to do the wiring.
The probes and their cables should NEVER be installed in
a conduit together with power, control or power supply
cables.
For disconnection, the power supply circuit must be equipped
• The specific wiring to be performed depends on the option
selected in the initial configuration wizard.
• Use the appropriate diagram based on the option selected.
• Check the available options on the diagram sheet included
with your device.
with a switch of at least 2 A, 230 V, located near the device. The
power supply cable will be H05VV-F or NYM 1x16/3. The section to
be used will depend on the local standard in force but must never
be less than 14AWG.
Cables for relay or contactor outputs should have a section of
14AWG, allow working temperatures equal to or over 158 °F and
be installed with as few bends as possible.
The 120/230 V~ wiring must be kept clear of any other external
element.
Important:
• Before starting the installation, you must take the advice of
local regulations in force.
• The AUXILIARY relays are programmable, and their operation
depends on the configuration.
• The function of the digital inputs depends on the configuration.
• The recommended currents and powers are the maximum
working currents and powers.
7. Initial configuration
The first time the unit is powered up, it will enter into the Wizard mode. The display will show the message
flashing with 0.
Step 1:
Select the most suitable InI option based on the type of installation to be carried out and press SET. The
available options will be shown in the following table:
Type of installationParameters
InI
Cold regulation
0Demo Mode: it displays the temp. but does not regulate or activate relays
1SolenoidNoElectricYes00200002000A
2Solenoid + compressorYesElectricYes11271002000B
3Solenoid + compressorNoElectricYes01200002000B
4SolenoidNoAirYes00100002011A
5Solenoid + compressorYesAirYe s11171002011B
6Solenoid + compressorNoAirYes01100002011B
7Solenoid + compressorYesHot gasYes1127191520C
8Solenoid + compressorNoHot gasYes0120091520C
9Solenoid + compressorYe s
10Solenoid + compressorNo
11SolenoidNoStaticNo0010000201-A
12Solenoid + compressorYesStaticNo1117100201-B
13Solenoid + compressorNoStaticNo0110000201-B
Pump
Down
Defrost
Reversed
cycle
Reversed
cycle
Evaporator
fans
Yes1127100530D
Yes0120000530D
Pd
o00 I00I10I11I20I21d1d7F3
80Z8118
CORECORE
Diagram
to be
used
Note: If options 2, 5, 7, 9 or 12 are chosen, check the configuration of parameter I11 according to the pressure switch type used. (See
diagram included with the device).
Step 2:
Use keys and to enter the desired Temperature Set Point value and press SET. The wizard has finished.
The unit will begin to regulate the temperature.
IIf this is not the first time you run the wizard, after completing the last step the display will show the
message dFp (default parameters). You may choose between two options:
0: Only change the parameters which affect the wizard. The other parameters will remain the same.
1: All parameters return to their factory setting except those which have been modified by the wizard.
CORECORE
Important: The wizard will not start automatically once the unit has been powered up at least once. To start the Wizard at any time turn
off the controller by pressing the power button for 3 seconds and wait until the power symbol is ON. The press the buttons listed here in
sequence , and SET.
If the pump down function is active, a certain amount of time may elapse between starting the stand-by function and the controller
stopping (see page 8).
0= Deactivated 1=Door contact 2=External alarm
3=Severe external alarm 4=Change of SP 5=Remote defrost
6=Defrost block 7=Register probe 8=Probe 2° evaporator
9=High pressure switch for Hot Gas 10=Remote Stand-by
0=Resistors 1=Air/fans 2=Hot gas
3=Reversal of cycle
8. Operation
Display messages
Pump down malfunction error (stop), the time configured in parameter C20 has been exceeded (see page 8).
Only displayed on screen.
Pump down malfunction error (start-up), the time configured in parameter C19 has been exceeded (see page 8).
Only displayed on screen.
Probe 1/2/3 failure (open circuit, crossed circuit or temperature outside the limits of the probe)
Only E2 and E3: Damp evaporator probe (see page 12).
Activates the alarm relay and the audible alarm.
Open door alarm.
Only if the door remains open for a longer time than defined in parameter A12 (see page 12).
Activates the alarm relay and the audible alarm.
Maximum temperature in control probe alarm.
The temperature value programmed in A1 has been reached (see page 12).
Activates the alarm relay and the audible alarm.
Minimum temperature in control probe alarm.
The temperature value programmed in A2 has been reached (see page 12).
Activates the alarm relay and the audible alarm.
External alarm activated (by digital input) (see page 12).
Activates the alarm relay and the audible alarm.
Severe external alarm activated (by digital input) (see page 12).
Activates the alarm relay and the audible alarm.
Alarm for defrost completed due to time-out.
The time set in d1 has been exceeded (see page 13).
Activates the alarm relay and the audible alarm.
HACCP alarm.
The temperature has reached the value of parameter h1 during a longer period than established in h2 (see page 12).
Activates the alarm relay and the audible alarm.
HACCP alarm due to a power supply failure.
The temperature established in h1 has been reached, following a power supply failure (see page 12).
Activates the alarm relay and the audible alarm.