Danfoss AK-RC 251 Installation guide

Installation Guide
Temperature controller for walk-in coolers
080 R9291
and freezers, Type AK-RC 251
AN362928 67744601-0 0 0101
ENGLISH
EN : Temperature controller for walk-in coolers and freezers ES : Controlador de temperatura para cuartos fríos y congeladores Type AK-RC 251
Warnings
• From -40 – +68 °F, if the NTC probe is extended to 3,280 ft with at least 20AWG cable, the maximum deviation will be 0.45 °F.
• It should be installed in a place protected from vibrations, water and corrosive gases, where the ambient temperature does not exceed the value indicated in the technical data.
• For the reading to be correct, the probe should be used in a place without heat influences apart from the temperature you want to measure or control.
• IP65 protection degree is only valid with the protection cover closed.
• IP65 protection degree is only valid if the cables enter the device using electrical conduit + gland with IP65 or above. The size of the glands should be suitable for the diameter of the conduit used.
• Do not spray the unit directly with high-pressure hoses, as this could cause damage.
IMPORTANT:
Before starting the installation, you must take the advice of local regulations in force.
• The AUXILIARY relays are programmable, and their operation depends on the configuration.
• The function of the digital inputs depends on the configuration.
• The recommended currents and powers are the maximum working currents and powers.
Wiring
Always disconnect the power supply to do the wiring.
The probes and their cables should NEVER be installed in a conduit together with power, control or power supply cables. For disconnection, the power supply circuit must be equipped with a switch of at least 2 A, 230 V, located near the device. The power
supply cable will be H05VV-F or NYM 1x16/3. The section to be used as wire rated according to local regulations but must never be less than 14AWG.
Cables for relay or contactor outputs should use 14AWG, allow working temperatures equal to or over 158 °F and be installed with as few bends as possible.
The 120/230 V~ wiring must be kept clear of any other external element.
The wiring to be done depends on the type of installation. Use the appropriate diagram based on the option selected in the wizard. Check the available options on the diagrams included in the controller's packaging. Wizard refers to a built in tool to guide the user through the set up process.
Maintenance
• Clean the surface of the unit with a soft cloth, water and soap.
• Do not use abrasive detergents, gasoline, alcohol or solvents, as this might damage the unit.
© Danfoss | DCS (vt) | 2021.02
AN36292867744601-000101 | 1
Keypad
Pressing it for 3 seconds activates/deactivates Stand-By mode. In this mode, regulation is paused and the icon is displayed.
In the programming menu, this exits the parameter without saving changes, returns to previous level or exits programming.
Pressing once displays the temperature of probe S2 for 10 seconds (If it is enabled). Pressing it for 3 seconds starts/stops the defrost. In the programming menu, this allows scrolling around the different levels, or, during the setting of a parameter, changing its
value.
Pressing it for 3 seconds activates/deactivates continuous cycle mode. In the programming menu, this allows scrolling around the different levels, or, during the setting of a parameter, changing its
value.
Pressing once activates/deactivates the cold room light. Pressing it for 3 seconds accesses the condensed programming menu. Pressing it for 6 seconds accesses the expanded programming menu. In the programming menu, this accesses the level shown on the display or, during the setting of a parameter, accepts the new
value.
Pressing once displays the current effective value of the Set Point, taking into consideration temporary modifications by other
parameters (C10 or C12).
When an alarm is underway, pressing once mutes the acoustic alarm. Pressing for 3 seconds accesses the Set Point setting.
Indicators
Fixed: Stand-By Mode activated. Regulation is paused.
Flashing: Controlled shutdown process for the regulation underway.
Fixed: Cold room door open.
Flashing: The door has been open for a greater time than has been defined in parameter A12.
There is an active alarm, but not an active HACCP alarm.
Fixed: HACCP alarm active.
Flashing: HACCP alarm registered and unconfirmed. Press the key to confirm an HACCP alarm.
Fixed: Evaporator fans active.
Flashing: The evaporator fans should be active but a delay is preventing this. (Refer to the Drip time section of the Manual for details).
Fixed: The cold solenoid is active.
Flashing: The solenoid should be active but a delay or protection is preventing this. (Refer to the Fan start-up section of the Manual for details).
Fixed: Compressor active.
Flashing: The compressor should be active but a delay or protection is preventing this. (Refer to the Compressor Protection timing section of the Manual for details).
Defrost relay active.
Continuous cycle mode active.
Cold room light active.
Alarm underway muted.
Temperature displayed in ° Fahrenheit / ° Centigrade.
Programming mode active.
STAND-BY
If the temperature regulation cannot be instantly stopped due to its configuration, a controlled stop process starts and the
icon flashes. To stop the controlled stop process and force the step to Stand-by, press the Stand-by key again for 3 seconds.
2 | AN36292867744601-000101
© Danfoss | DCS (vt) | 2021.02
Initial configuration
The first time the unit is powered up, it will enter into the Wizard mode. The display will show the message
flashing with 0.
Step 1:
Select the most suitable InI option based on the type of installation to be carried out and press SET. The available options will be shown in the following table:
InI
Cold regulation Defrost Evaporator fans o00 I00 I10 I11 I20 I21 d1 d7 F3
0 Demo Mode: it displays the temp. but does not regulate or activate relays
1 Solenoid Electric Yes 0 2 0 0 0 0 20 0 0 A
3 Solenoid + compressor Electric Yes 1 2 0 0 0 0 20 0 0 B
4 Solenoid Air Yes 0 1 0 0 0 0 20 1 1 A
6 Solenoid + compressor Air Yes 1 1 0 0 0 0 20 1 1 B
11 Solenoid Static No 0 1 0 0 0 0 20 1 - A
13 Solenoid + compressor Static No 1 1 0 0 0 0 20 1 - B
Type of installation Parameters
Diagram to
be used
Note: Additional quick set up choices, including hot gas and reversed cycle options are detailed in the User Manual.
Step 2:
Use keys and to enter the desired Temperature Set Point value and press SET. The wizard has finished. The unit will begin to regulate the temperature.
If this is not the first time you use the wizard, after completing the last step the display will show the message dFp (default parameters). You may choose between two options:
0: Only parameters included in the wizard will be modified 1: Parameters modified by the wizard will be changed, all other parameters will return to their factory setting.
Important: The wizard will start automatically only on the first power on. To enter the wizard mode, initiate Stand-By mode by pressing
the key for 3 seconds and wait until the unit completely halts the temperature regulation (The indicator will light up permanently) and press the following keys in sequence, , , SET.
Wizard parameters list
o00 Configuration of relay AUX1
I00 Connected probes 1=Probe 1 (Cold room) 2=Probe 1 (Cold room) + Probe 2 (Evaporator)
I10 Configuration of digital input 1
I11 Polarity of the digital input 1 0=Activates on closing contact 1=Activates on opening contact
I20 Configuration of digital input 2
I21 Polarity of the digital input 2 0=Activates on closing contact 1=Activates on opening contact
d1 Maximum defrost duration (0=defrost deactivated)
d7 Type of defrost
F3 Status of the fans during the defrost 0=Shut down 1=Running
For more details, full User Manual and other information, scan the QR code.
0=Deactivated 1=Compressor/Crankcase heater 2=Light 3=Virtual control
0= Deactivated 1=Door contact 2=External alarm 3=Severe external alarm 4=Change of SP 5=Remote defrost 6=Defrost block 7= Low pressure switch 8=Remote Stand-by
0= Deactivated 1=Door contact 2=External alarm 3=Severe external alarm 4=Change of SP 5=Remote defrost 6=Defrost block 7=Register probe 8=Probe 2° evaporator 9=High pressure switch for Hot Gas 10=Remote Stand-by
0=Resistors 1=Air/fans 2=Hot gas 3=Reversal of cycle
© Danfoss | DCS (vt) | 2021.02
AN36292867744601-000101 | 3
Configuration
Condensed programming menu
Enables the rapid configuration of the most frequently-used parameters (SP, C1, d0, d1, d4, F3, A1 and A2). Press the SET key for 3 seconds to access it.
Extended programming menu
Use the extended programming menu to configure all of the unit’s parameters in order to adapt it to installation requirements. Press the
SET key for 6 seconds to access it.
Important:
• If the function of the password has been configured as a keypad block (b10=2), or as an access block to parameters (b10=1), you
will be requested to enter the access code programmed in PAS when attempting to access either of the two functions. If the entered password is not correct, the unit will go back to showing the temperature.
• Certain parameters or menus may not be visible depending on the configuration of the rest of the parameters.
Regulation and control
Level 1 Level 2 Description Values Min. Def. Max.
SP Temperature setting (Set Point) ºF -58 32.0 210
C0 Probe 1 calibration (Offset) ºF -36.0 0.0 36.0
C1 Probe 1 differential (Hysteresis) ºF 0.1 3.6 36
C2 Set Point top locking (it cannot be set above this value) ºF -58 210 210
C3 Set Point bottom locking (it cannot be set below this value) ºF -58 -58 C2
Type of delay for the protection of the compressor:
C4
0=Minimum time of compressor in OFF 1=Minimum time of compressor in OFF and in ON in each cycle
C5 Protection delay time (Value of the option selected in parameter C4) Min. 0 0 120
COOL relay status with fault in probe 1:
C6
0=OFF; 1=ON; 2=Average according to last 24 h prior to probe error 3=ON-OFF according to prog. C7 and C8
Relay time in ON in the event of probe 1 failure
C7
(If C7=0 and C8≠0, the relay will always be disconnected in OFF)
Relay time in OFF in the event of probe 1 failure
C8
rE
C10
C12
C19
C20 Maximum time for pump down (0= deactivated) Min. 0 0 15
C21
C22 Stop fans and compressor on opening door 0=No, 1=Yes 0 0 1
C23 Start-up delay for fans and compressor with door open Min. 0 0 999
C27 Probe 3 calibration (Offset) ºF -36.0 0.0 36.0
(If C8=0 and C7≠0, the relay will always be connected in ON)
C9 Maximum duration of the continuous cycle mode. (0=deactivated) H. 0 0 48
Variation of the Set Point (SP) in continuous cycle mode. When it reaches this point (SP+C10), it reverts to the normal mode. (SP+C10 ≥ C3). The value of this parameter is always negative, unless it is 0. (0=OFF)
Variation of the Set Point (SP) when the change Set Point function is active. (SP+C12 ≤ C2) (0= deactivated)
Maximum start time from Pump Down (Values between 1 and 9 seconds will not be accepted) (0=deactivated)
Probe to be displayed 0=All probes (sequential) 1=Probe 1 (Cold Room), 2=Probe 2 (Evaporator), 3=Probe 3 (According to I20)
EP Exit to level 1
Min. 0 10 120
Min. 0 5 120
ºF 0 -90 C3-SP
ºF C3-SP 0.0 C2-SP
Sec. 0 0 120
0 0 1
0 2 3
0 1 3
4 | AN36292867744601-000101
© Danfoss | DCS (vt) | 2021.02
Defrost
Level 1 Level 2 Description Values Min. Def. Max.
d0 Defrost frequency (Time between 2 starts) H. 0 6 96
d1 Maximum defrost duration (0=defrost deactivated) Min. 0 * 255
Type of message during the defrost:
d2
0=Displays the real temperature; 1=Displays the temperature at the start of the defrost; 2=Displays the dEF message
Maximum duration of the message
d3
(Time added at the end of the defrost process)
d4 Final defrost temperature (by probe) (If I00 ≠ 1) ºF -58 46.4 122
dEF
d7**
* According to wizard. ** It can only be modified using the configuration wizard (InI).
Defrost on connecting the unit:
d5
0=NO First defrost according to d0; 1=YES, First defrost according to d6
d6 Delay of the defrost start on connecting the unit Min. 0 0 255
Type of defrost: 0=Resistors; 1=Air/fans, 2=Hot gas; 3=Reversal of cycle
Count of time between defrost periods:
d8
0=Total real time, 1 =Sum of compressor connected time
d9 Drip time when completing defrost (Shutdown of compressor and fans) Min. 0 1 255
EP Exit to level 1
Min. 0 5 255
0 2 2
0 0 1
0 * 3
0 0 1
Evaporator fans
Level 1 Level 2 Description Values Min. Def. Max.
F0 Shutdown temperature of fans ºF -58 113 122
F1 Probe 2 differential if fans are shut down ºF 0.1 3.6 36
F2 Shut down fans when the compressor shuts down 0=No, 1=Yes 0 0 1
FAn
F3 Status of the fans during the defrost 0=Shut down; 1=Running 0 0 1
Delay of start-up after defrost (If F3=0)
F4
It will only actuate if it is higher than d9
EP Exit to level 1
Min. 0 2 99
Alarms
Level 1 Level 2 Description Values Min. Def. Max.
A0 Configuration of the temperature alarms 0=Relative to SP 1=Absolute 0 1 1
A1 Alarm for maximum in probe 1 (It should be higher than the SP) ºF A2 210 210
A2 Alarm for minimum in probe 1 (It should be lower than the SP) ºF -58 -58 A1
A3 Delay of temperature alarms in the start-up Min. 0 0 120
A4 Delay of temperature alarms from the end of a defrost Min. 0 0 99
A5 Delay of temperature alarms from when the A1 or A2 value is reached 0 30 99
Delay of the external alarm/Severe external alarm on receiving a signal in
AL
A6
digital input (I10 or I20 =2 or 3)
Delay of external alarm deactivation/Severe external alarm deactivation
A7
when the signal in digital input disappears (I10 or I20=2 or 3)
A8 Show warning if the defrost ends for maximum time, 0=No, 1=Yes 0 0 1
Relay alarm polarity
A9
0= Relay ON in alarm (OFF without alarm); 1= Relay OFF in alarm (ON without alarm)
A10 Differential of temperature alarms (A1 and A2) ºF 0.1 1.8 36
A12 Delay of open door alarm (If I10 or I20=1) Min. 0 10 120
EP Exit to level 1
Min. 0 0 120
Min. 0 0 120
0 0 1
© Danfoss | DCS (vt) | 2021.02
AN36292867744601-000101 | 5
Loading...
+ 11 hidden pages