Danfoss AK-RC 111, AK-RC 113 Installation guide

Installation Guide

Optyma™ control

AK-RC 111, AK-RC 113

080R9290

AN30923034432301-000102

English

Nederlands

Deutsch

Français

Español

Italiano

 

 

 

 

 

 

Compressor protection

Kriwan

Kriwan

Kriwan

Kriwan

Protezione compressore

 

 

 

 

 

 

Door limit switch

Deurschakelaar

Tür

Porte

Puerta

Micro porta

 

 

 

 

 

 

Ambient probe

Ruimtesensor

Raumfühler

Température ambiente

Temperatura ambiente

Sonda ambiente

 

 

 

 

 

 

Defrost probe

Ontdooisensor

Abtaufühler

Sonde de dégivrage

Sensor de desescarche

Sonda evaporatore

 

 

 

 

 

 

RS485 Modbus

RS485 Modbus

RS485 Modbus

RS485 Modbus

RS485 Modbus

RS485 Modbus

 

 

 

 

 

 

Supply 230 V AC

Voeding 230 V AC

Versorgung 230 V AC

Alimentation 230 V AC

Suministro 230 V AC

Alimentazione 230 V AC

 

 

 

 

 

 

Defrost heater

Ontdooiing

Abtauheizungen

Résistances de dégivrage

Resistencias de

Resistenze sbrinamento

descongelación

 

 

 

 

 

Evaporator fans

Verdamperventilator

Verdampferlüfter

Ventilateur évaporateur

Evaporador ventilador

Ventole evaporatore

 

 

 

 

 

 

Compressor

Compressor

Kompressor

Compresseur

Compresor

Compressore

 

 

 

 

 

 

Light

Verlichting

Licht

Éclairage

Iluminación

Luce

 

 

 

 

 

 

Alarm / Aux

Alarm / Aux

Alarm / Aux

Alarme / Aux

Alarma / Aux

Allarme / Aux

 

 

 

 

 

 

© Danfoss | DCS (vt) | 2020.05

AN30923034432301-000102 | 1

Danfoss AK-RC 111, AK-RC 113 Installation guide

OPTYMA™ Control, single phase

<![if ! IE]>

<![endif]>-B MODBUS

<![if ! IE]>

<![endif]>A+ MODBUS

<![if ! IE]>

<![endif]>probe Defrost

<![if ! IE]>

<![endif]>probe Ambient

<![if ! IE]>

<![endif]>probes Common

<![if ! IE]>

<![endif]>inputs .dig Common

<![if ! IE]>

<![endif]>2 input Digital

<![if ! IE]>

<![endif]>1 input Digital

1 2 3 4 5 6 7 8

Power

 

 

Supply

 

 

230 V AC Defrost

Fans Compr. Aux1/All. Aux2

Light

9 1011 12 13 14 15 16 17 20 21 18 19

 

 

<![if ! IE]>

<![endif]>Common

enable

 

 

 

/d

/d

 

Condensing

 

<![if ! IE]>

<![endif]>N

 

unit

<![if ! IE]>

<![endif]>F

 

Electric

 

 

 

switchboard

OPTYMA™ Control, three phase (4 HP)

<![if ! IE]>

<![endif]>protection .Comp

<![if ! IE]>

<![endif]>switch Door

<![if ! IE]>

<![endif]>inputs .dig Common

<![if ! IE]>

<![endif]>probes Common

<![if ! IE]>

<![endif]>probe Ambient

<![if ! IE]>

<![endif]>probe Defrost

<![if ! IE]>

<![endif]>A+ MODBUS

<![if ! IE]>

<![endif]>-B MODBUS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

2

 

3

 

4

 

5

 

6

 

7

8

 

1

 

 

2

 

 

3

 

 

13

 

14

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<![if ! IE]>

<![endif]>1.JB01

 

<![if ! IE]>

<![endif]>2.JB01

 

<![if ! IE]>

<![endif]>3.JB01

 

<![if ! IE]>

<![endif]>13.JB01

 

<![if ! IE]>

<![endif]>14.JB01

 

<![if ! IE]>

<![endif]>15.JB01

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

 

 

 

 

 

 

 

Supply

 

 

 

 

 

 

 

230 V AC

Defrost

Fans

Compr.

Aux1/All. Aux2

Light

9 10

11 12 13

14 15

16 17 20 21 18 19

5

6

7

L8

4

9

enable

L10

L11

<![if ! IE]>

<![endif]>.JB01

<![if ! IE]>

<![endif]>.JB01

<![if ! IE]>

<![endif]>.JB01

<![if ! IE]>

<![endif]>.JB01

<![if ! IE]>

<![endif]>.JB01

<![if ! IE]>

<![endif]>.JB01

Condensing

<![if ! IE]>

<![endif]>.JB01

<![if ! IE]>

<![endif]>.JB01

<![if ! IE]>

<![endif]>5

<![if ! IE]>

<![endif]>6

<![if ! IE]>

<![endif]>7

<![if ! IE]>

<![endif]>8

<![if ! IE]>

<![endif]>4

<![if ! IE]>

<![endif]>9

unit

<![if ! IE]>

<![endif]>10

<![if ! IE]>

<![endif]>11

Electric

 

 

 

 

 

 

switchboard

 

 

OPTYMA™ Control, three phase (7.5 HP)

<![if ! IE]>

<![endif]>protection .Comp

<![if ! IE]>

<![endif]>switch Door

<![if ! IE]>

<![endif]>inputs .dig Common

<![if ! IE]>

<![endif]>probes Common

<![if ! IE]>

<![endif]>probe Ambient

<![if ! IE]>

<![endif]>probe Defrost

<![if ! IE]>

<![endif]>A+ MODBUS

<![if ! IE]>

<![endif]>-B MODBUS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

2

 

3

 

4

 

5

 

6

 

7

8

 

1

 

 

2

 

 

3

 

 

13

 

14

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<![if ! IE]>

<![endif]>1.JB01

 

<![if ! IE]>

<![endif]>2.JB01

 

<![if ! IE]>

<![endif]>3.JB01

 

<![if ! IE]>

<![endif]>13.JB01

 

<![if ! IE]>

<![endif]>14.JB01

 

<![if ! IE]>

<![endif]>15.JB01

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

 

 

 

 

 

 

 

Supply

 

 

 

 

 

 

 

230 V AC

Defrost

Fans

Compr.

Aux1/All. Aux2

Light

9 10

11 12 13

14 15

16 17 20 21 18 19

5

6

7

8

4

9

enable

L10

L11

<![if ! IE]>

<![endif]>.JB01

<![if ! IE]>

<![endif]>.JB01

<![if ! IE]>

<![endif]>.JB01

<![if ! IE]>

<![endif]>.JB01

<![if ! IE]>

<![endif]>.JB01

<![if ! IE]>

<![endif]>.JB01

Condensing

<![if ! IE]>

<![endif]>.JB01

<![if ! IE]>

<![endif]>.JB01

<![if ! IE]>

<![endif]>5

<![if ! IE]>

<![endif]>6

<![if ! IE]>

<![endif]>7

<![if ! IE]>

<![endif]>8

<![if ! IE]>

<![endif]>4

<![if ! IE]>

<![endif]>9

unit

<![if ! IE]>

<![endif]>10

<![if ! IE]>

<![endif]>11

Electric

 

 

 

 

 

 

switchboard

 

 

2 | AN30923034432301-000102

© Danfoss | DCS (vt) | 2020.05

ENGLISH

Function

Press

 

 

 

 

 

 

View set point

 

 

 

 

 

 

 

Change set point

+

/

 

 

 

 

Change menu “User level”

+

(3 seconds)

 

 

 

Return

+

(3 seconds)

 

 

 

 

Change menu “Installer level”

+

+

(3 seconds)

 

 

 

Return

+

(3 seconds)

 

 

 

 

List of level 1 variables (user level)

Variables

Meaning

Value

Default

 

 

 

 

r0

Temperature difference compared to main SETPOINT

0.2 – 10 °C

2 °C

 

 

 

 

d0

Defrost interval (hours)

0 – 24 hours

4 hours

 

If d0 = 0 cyclical defrosts Off

 

 

 

 

 

 

d2

End-of-defrost setpoint.

-35 – 45 °C

15 °C

 

Defrost is not executed if the temperature read by the defrost sensor is greater than

 

 

 

d2. (If the sensor is faulty defrosting is timed)

 

 

 

 

 

 

d3

Max defrost duration (minutes)

1 – 240 min

25 min

 

 

 

 

d7

Drip duration (minutes)

0 – 10 min

0 min

 

At the end of defrost the compressor and fans remain at standstill for time d7, the

 

 

 

defrost LED on the front panel flashes.

 

 

 

 

 

 

F5

Fan pause after defrost (minutes)

0 – 10 min

0 min

 

Allows fans to be kept at standstill for a time F5 after dripping. This time begins at the

 

 

 

end of dripping. If no dripping has been set the fan pause starts directly at the end of

 

 

 

defrost.

 

 

 

 

 

 

A1

Minimum temperature alarm

-45 – (A2-1) °C

-45 °C

 

Allows user to define a minimum temperature for the room being refrigerated. Below

 

 

 

value A1 an alarm trips: the alarm LED flashes, displayed temperature flashes and the

 

 

 

buzzer sounds to indicate the problem.

 

 

A2

Maximum temperature alarm

(A1+1) – 99 °C

99 °C

 

Allows user to define a maximum temperature for the room being refrigerated. Above

 

 

 

value A2 an alarm trips: the alarm LED flashes, displayed temperature flashes and the

 

 

 

buzzer sounds to indicate the problem.

 

 

 

 

 

 

tEu

Evaporator sensor temperature display (displays nothing if dE =1)

Evaporator temperature

read only

 

 

 

 

List of level 2 variables (installer level)

Variables

Meaning

 

Value

Default

 

 

 

 

 

F3

Fan status with compressor off

0

= Fans run continuously

1

 

 

1

= Fans only run when compressor is working

 

 

 

2

= Fans disabled

 

F4

Fan pause during defrost

0

= Fans run during defrost

1

 

 

1

= Fans do not run during defrost

 

F6

Evaporator fans activation for air recirculation.

0

– 240 min

0 min

 

The fans activate for a time defined by F7 if they have not started working for the F6

0

= (function not activated)

 

 

time. If activation time coincides with the defrosting time, end of defrosting is awaited.

 

 

 

 

 

 

 

 

F7

Evaporator fans duration for air recirculation.

0

– 240 sec

10 sec

 

Fans working time for F6

 

 

 

 

 

 

 

 

dE

Sensor presence

0

= evaporator sensor present

0

 

If the evaporator sensor is disabled defrosts are carried out cyclically with period d0:

1

= no evaporator sensor

 

 

defrosting ends when an external device trips and closes the remote defrost contact or

 

 

 

 

when time d3 expires.

 

 

 

 

 

 

 

 

d1

Defrost type, cycle inversion (hot gas) or with heater elements

0

= heating element

0

 

 

1

= hot gas

 

 

 

2

= heater with temperature control

 

 

 

 

 

 

dPo

Defrost at Power On

0

= disabled

0

 

 

1

= defrost at power-on (if possible)

 

dSE

Smart defrost

0

= disabled

0

 

 

1

= enabled

 

dSt

Smart defrost Setpoint (if dSE=1)

-30 – 30 °C

1 °C

 

The counting of the time between the defrost is incremented only if the compressor is

 

 

 

 

ON and the evaporator temperature is less than dSt.

 

 

 

 

 

 

 

 

© Danfoss | DCS (vt) | 2020.05

AN30923034432301-000102 | 3

Variables

Meaning

 

Value

Default

 

 

 

 

 

dFd

Display viewing during Defrost

0

= current temperature

1

 

 

1

= temperature at the start of the defrost

 

 

 

2

= “DEF”

 

Ad

Modbus Network address

0

– 247

0

Bdr

Modbus baudrate

0

= 300 baud

8

 

 

1

= 600 baud

 

 

 

2

= 1200 baud

 

 

 

3

= 2400 baud

 

 

 

4

= 4800 baud

 

 

 

5

= 9600 baud

 

 

 

6

= 14400 baud

 

 

 

7

= 19200 baud

 

 

 

8

= 38400 baud

 

Prt

Modbus parity check

0

= none

1

 

 

1

= even

 

 

 

2

= odd

 

Ald

Minimum and maximum temperature signalling and alarm display delay

0

– 240 min

120 min

 

 

 

 

 

C1

Minimum time between shutdown and subsequent switching on of the compressor

0

– 15 min

0 min

CAL

Cold room sensor value correction

-10 – 10 °C

0 °C

CE1

Duration of compressor ON time in the case of faulty ambient probe

0

– 240 min

0 min

 

(emergency mode).

0

= disabled

 

 

If CE1=0 the emergency mode in the presence of error E0 remains disabled, the

 

 

 

 

compressor remains off and defrosting is prevented in order to conserve the

 

 

 

 

remaining cold.

 

 

 

CE2

Duration of compressor OFF time in the case of faulty ambient probe

5

– 240 min

5 min

 

(emergency mode).

 

 

 

doC

Compressor safety time for door switch: when the door is opened the evaporator

0

– 5 min

0 min

 

fans shut down and the compressor will continue working for time doC, after which it

 

 

 

 

will shut down.

 

 

 

tdo

Compressor restart time after door opening. When the door is opened and after tdo

0

– 240 min

0 min

 

time, it’s setted back the normal functioning giving door open alarm (Ed)

0

= disabled

 

 

If the door switch is closed and the light stays on for a longer time than tdo light cell

 

 

 

 

alarm is signaled (E9).

 

 

 

 

With tdo=0 the parameter is disabled.

 

 

 

 

 

 

 

Fst

FAN shutdown TEMPERATURE

-45 – 99 °C

99 °C

 

The fans will stop if the temperature value read by the evaporator sensor is higher

 

 

 

 

than this value.

 

 

 

 

 

 

 

 

Fd

Fst differential

1

– 10 °C

2 °C

LSE

Minimum value attributable to setpoint.

-45 – (HSE-1) °C

-45 °C

 

 

 

 

HSE

Maximum value attributable to setpoint.

(LSE+1) – 99°C

99 °C

 

 

 

 

AU1

Auxiliary/alarm relay 1 control

-6 (NC) = relay de-energised during stand-by.

-1

 

 

-5 (NC) = Contact for casing element control

 

 

 

 

(AUX relay closed with compressor

 

 

 

 

output inactive).

 

 

 

-4 (NC) = pump down function(NC, see CHAP

 

 

 

 

5.16).

 

 

 

-3 (NC) = automatic auxiliary relay managed by

 

 

 

 

StA temp. setting with 2°C differential

 

 

 

 

(NC).

 

 

 

-2 (NC) = manual auxiliary relay controlled via

 

 

 

 

AUX key (NC).

 

 

 

-1 (NC) = alarm relay (NC).

 

 

 

0

= relay deactivated.

 

 

 

1 (NO) = alarm relay (NO).

 

 

 

2 (NO) =manual auxiliary relay controlled via

 

 

 

 

AUX key (NO).

 

 

 

3 (NO) = automatic auxiliary relay managed by

 

 

 

 

StA temp. setting with 2°C differential

 

 

 

 

(NO).

 

 

 

4 (NO) = pump down function (NO, see CHAP

 

 

 

 

5.16).

 

 

 

5 (NO) = free voltage contact for condensing

 

 

 

 

unit (AUX relay and compressor relay

 

 

 

 

in parallel).

 

 

 

6 (NO) = relay excited during stand-by.

 

 

 

 

 

AU2

Auxiliary/alarm relay 2 control

(like AU1 )

5

 

 

 

 

StA

Temperature setting for auxiliary relay

-45 – 99 °C

0 °C

nSC

Correction factor for the SET button during night operation (energy saving)

-20 – 20 °C

0 °C

 

(with In1 or In2 = 8 or -8)

 

 

 

 

During night operation the control set is: Set Control = Set + nSC

 

 

 

 

In night mode decimal point flashes.

 

 

 

4 | AN30923034432301-000102

© Danfoss | DCS (vt) | 2020.05

Variables

Meaning

 

Value

Default

 

 

 

 

In1

INP-1 input setting

8 = Night mode digital input (energy saving,

2

 

 

 

N.O.)

 

 

 

7

= Stop defrosting remotely (N.O.) (reads rising

 

 

 

 

edge of impulse)

 

 

 

6

= Start defrosting remotely (N.O.) (reads rising

 

 

 

 

edge of impulse)

 

 

 

5

= Stand-by remotely (N.O.) (In order to indicate

 

 

 

 

Stand-By mode, the display shows ‘In5’

 

 

 

 

alternating with the current view)

 

 

 

4

= Pump-down pressure switch (N.O.)

 

 

 

3

= Man-in-room alarm (N.O.)

 

 

 

2

= Compressor protection (N.O.)

 

 

 

1

= Door switch (N.O.)

 

 

 

0

= disabled

 

 

 

-1 = Door switch (N.C.)

 

 

 

-2 = Compressor protection (N.C.)

 

 

 

-3 = Man-in-room alarm (N.C.)

 

 

 

-4 = Pump-down pressure switch (N.C.)

 

 

 

-5 = Stand-by remotely (N.C.) (In order to

 

 

 

 

indicate Stand-By mode, the display shows

 

 

 

 

‘In5’ alternating with the current view)

 

 

 

-6 = Start defrosting remotely (N.C.) (reads falling

 

 

 

 

edge of impulse)

 

 

 

-7 = Stop defrosting remotely (N.C.) (reads falling

 

 

 

 

edge of impulse)

 

 

 

-8 = Night mode digital input (energy saving,

 

 

 

 

N.C.)

 

In2

INP-2 input setting

( like In1 )

1

 

 

 

 

bEE

Buzzer enable

0 = disabled

1

 

 

1

= enabled

 

mOd

Thermostat functioning mode

0 = Cold function

0

 

 

1

= Hot function

 

 

 

 

(in this mode defrosting and fan disable Fst

 

 

 

 

are excluded)

 

P1

Password type of protection

0 = only display set point

3

 

(active when PA is not equal 0)

1 = display set point, AUX, light access

 

 

 

2

= access in programming not permitted

 

 

 

3

= access in second level programming not

 

 

 

 

permitted

 

 

 

 

 

PA

Password

0...999

0

 

(see P1 for the type of protection)

0 = not active

 

 

 

 

 

reL

Release software

indicates software version

read only

 

 

 

 

 

Troubleshooting

Alarm code

Possible cause

Solution

 

 

 

 

E0

Cold room temperature sensor not working properly

Check that cold room temperature sensor is working properly

 

 

If the problem persists replace the sensor

E1

Defrost sensor not working properly (in this case defrosts will last time d3)

Check that defrost sensor is working properly

 

 

If the problems persists replace the sensor

 

 

 

 

E2

Eeprom alarm

Switch unit off and back on

 

An EEPROM memory alarm has been detected

 

 

 

(All outputs except the alarm one are deactivated)

 

 

E8

Man in cold room alarm

Reset the alarm input inside the cold room

Ec

Compressor protection tripped

Check that compressor is working properly

 

(e.g. thermal protection or max pressure switch)

Check compressor absorption

 

(All outputs except the alarm one – where applicable – are deactivated)

If the problem persists contact the technical assistance service

 

 

 

 

Ed

Open door Alarm. When the door is opened and after tdo time, it’s setted back the

Check door switch status

 

normal functioning giving door open alarm (Ed)

Check door switch connections

 

 

If the problem persists contact the technical assistance service

 

 

 

 

E9

Cell light alarm.

Turn off the light

 

The light of the cell has been on for a time greater than tdo.

 

 

 

 

 

 

EH

Maximum temperature alarm.

Check that the compressor is working properly.

 

The temperature inside the cold room has exceeded the max. temperature alarm

Sensor not reading temperature properly or compressor start/stop

 

setting (see variables A2, user programming level)

 

control not working.

 

 

 

 

EL

Minimum temperature alarm.

Check that the compressor is working properly.

 

The temperature inside the cold room has exceeded the min. temperature alarm

Sensor not reading temperature properly or compressor start/stop

 

setting (see variables A1, user programming level)

 

control not working.

 

 

 

 

© Danfoss | DCS (vt) | 2020.05

AN30923034432301-000102 | 5

NEDERLANDS

Functie

Pers

 

 

 

 

 

 

Voor setpoint

 

 

 

 

 

 

 

Modificeren setpoint

+

/

 

 

 

 

 

Modificeren menu “Gebruikers

+

(3 seconden)

niveau”

 

 

 

 

 

 

Menu verlaten

+

(3 seconden)

 

 

 

 

Modificeren menu

+

+

(3 seconden)

“Installateursniveau”

 

 

 

 

 

 

Menu verlaten

+

(3 seconden)

 

 

 

 

Lijst met niveau 1 variabelen (gebruikersniveau)

Variabelen

Verklaring

Waarde

Fabr. Inst.

 

 

 

 

r0

Temperatuur differentie vergeleken met het SETPOINT

0.2 – 10 °C

2 °C

 

 

 

 

d0

Ontdooi interval (Uur)

0 – 24 uur

4 uur

 

indien d0 = 0 cyclische ontdooiing Uit

 

 

 

 

 

 

d2

Ontdooiing setpoint

-35 – 45 °C

15°C

 

Ontdooiing wordt niet uitgevoerd als de waarde van de temperatuur hoger is dan "d2".

 

 

 

(Als de sensor defect is wordt de ontdooiing op tijd uitgevoerd)

 

 

 

 

 

 

d3

Maximale ontdooitijd (minuten)

1 – 240 min

25 min

 

 

 

 

d7

Duur druptijd (minuten)

0 – 10 min

0 min

 

Na een ontdooibeëindiging blijven de compressor en ventilator gedurende tijd d7

 

 

 

stilstaan, De ontdooi LED op het frontpaneel knippert.

 

 

 

 

 

 

F5

Ventilatorpauze na ontdooiing (minuten)

0 – 10 min

0 min

 

De ventilator blijft na de druptijd stilstaan gedurende tijd F5. Deze tijd begint na het

 

 

 

einde van de druptijd. Als er geen druptijd is ingesteld start de ventilatorpauze direct

 

 

 

na het einde van de ontdooiing.

 

 

 

 

 

 

A1

Minimum temperatuuralarm

-45 – (A2-1) °C

-45 °C

 

Maakt het mogelijk voor de gebruiker om een minimum ruimtetemperatuur in te

 

 

 

stellen. Beneden waarde A1 schakelt het alarmcontact: het alarm LED knippert,

 

 

 

weergave temperatuur knippert en de zoemer gaat aan om het probleem te melden.

 

 

 

 

 

 

A2

Maximum temperatuuralarm

(A1+1) – 99 °C

45 °C

 

Maakt het mogelijk voor de gebruiker om een maximum ruimtetemperatuur in te

 

 

 

stellen. Boven waarde A2 schakelt het alarmcontact: het alarm LED knippert, weergave

 

 

 

temperatuur knippert en de zoemer gaat aan om het probleem te melden.

 

 

 

 

 

 

tEu

Verdampersensor temperatuurweergave

Geeft verdampertemperatuur weer

Alleen lezen

 

 

(geeft niets weer als dE =1)

 

Lijst met niveau 2 variabelen (installateursniveau)

Variabelen

Verklaring

 

Waarde

Fabr. Inst.

 

 

 

 

 

F3

Ventilatorstatus bij compressor uit

0

= ventilatoren draaien continue

1

 

 

1

= ventilatoren alleen in bedrijf als compressor

 

 

 

 

in bedrijf is

 

 

 

2

= Fans uitgeschakeld

 

F4

Ventilator pauze tijdens ontdooiing

0

= ventilatoren draaien tijdens ontd.

1

 

 

1

= ventilatoren staan stil tijdens ontd.

 

 

 

 

 

 

F6

Verdamperventilatoren activeren voor luchtrecirculatie.

0

– 240 min

0 min

 

De ventilatoren worden gedurende een door F7 gedefinieerde tijd geactiveerd als ze

0

= (functie niet geactiveerd)

 

 

niet voor de F6-tijd zijn begonnen te werken. Als de activeringstijd samenvalt met de

 

 

 

 

ontdooitijd, wacht u het einde van het ontdooien.

 

 

 

F7

Verdamper ventilatieduur voor luchtrecirculatie.

0

– 240 sec

10 sec

 

Fans werktijd voor F6

 

 

 

dE

Sensor aanwezigheid

0

= verdampersensor aanwezig

0

 

Als de verdampersensor Is aangesloten worden ontdooiingen uitgevoerd volgens

1

= geen verdampersensor

 

 

cyclusperiode d0: ontdooiing eindigt als een externe sensor aanspreekt en het remote

 

 

 

 

ontdooicontact schakelt en sluit of als tijd d3 afloopt.

 

 

 

d1

Type ontdooicyclus, omkeersysteem (heet gas) of met ontdooi-elementen

0

= verwarmingselement

0

 

 

1

= heet gas

 

 

 

2

= kachel met temperatuurregeling

 

 

 

 

 

 

dPo

Ontdooien bij inschakelen

0

= uitgeschakeld

0

 

 

1

= ontdooien bij inschakelen (indien mogelijk)

 

dSE

Slim ontdooien

0

= uitgeschakeld

0

 

 

1

= ingeschakeld

 

dSt

Smart Defrost Setpoint (indien dSE = 1)

-30 – 30 °C

1 °C

 

Het tellen van de tijd tussen het ontdooien wordt alleen geïncrementeerd als de

 

 

 

 

compressor AAN staat en de verdampertemperatuur lager is dan dSt.

 

 

 

 

 

 

 

 

6 | AN30923034432301-000102

© Danfoss | DCS (vt) | 2020.05

Loading...
+ 14 hidden pages