Instructions
Power supply
AK-PS 075, AK-PS 150, AK-PS 250
AK-PS 075, 080Z0053
080R9257
Input Voltage
100 - 240 V a.c.
50-60 Hz
0.4 A (120 V a.c.) /
0.2 A (230 V a.c.)
36 mm (1.4")
Mounting
The power supply can be snapped onto
all mounting rails in accordance with
EN 50022-35. Ensure mounting rails are
fixed horizontally.
In order to comply with the UL approval,
use copper cables that are designed for
operating temperatures of 75 °C (167 °F)
080R9257
AK-PS 150, 080Z0054
080Z0054
AK-PS 250, 080Z0055
90 mm (3.5")
Max 61 mm (2.4")
Input Voltage
100 - 240 V a.c.
50-60 Hz
0.85 A (120 V a.c.) /
0.4 A (230 V a.c.)
54 mm (2.1")
90 mm (3.5")
Max 61 mm (2.4")
Input Voltage
100 - 240 V a.c.
50-60 Hz
1.4 A (120 V a.c.) /
0.65 A (230 V a.c.)
72 mm (2.8")
Output:
24 V d.c.
0.75 A
18 VA
Output:
24 V d.c.
1.5 A
36 VA
DIN rail mounting
Flat surface mounting
Environmental Range:
IP20
Operation:
-25°C t
+70°C (-13°F < t
amb
Derating of output current:
2.5 % /K > +55°C (131°F)
Storage:
-40°C to +85°C (-40°F < t
Humidity:
0 - 95% RH, non condensing
Approvals
S
amb
< 185°F)
amb
< 158°F)
RI8LJ402 12-2017
90 mm (3.5")
Max 61 mm (2.4")
Output:
24 V d.c.
2.5 A
60 VA
UL File # E312396
Class II
PHOENIX CONTACT GmbH & Co. KG
D-32823 Blomberg, Germany
Fax +49-(0)5235-341200, Phone +49-(0)5235-300
MNR 9037782-00 / 05.2007
1
5
2
3
4
Abb./Fig. 1
72
44
55
50
61
30
90
30
150
45
Abb./Fig. 2
Abb./Fig. 3
Einbauanleitung für den Elektroinstallateur
Installation notes for electrical personnel
Instruction d’installation pour l’électricien
Instrucción de montaje para el ingeniero eléctrico
Connection / Connecting cable
To achieve a reliable and shockproof connection, strip the connecting ends according to table 1!
Tabelle 1
Table 1
Tableau 1
Tabla 1:
22
1111
22
Starr
Flexibel
Solid
Stranded
Rigide
Souple
Rigido
Flexible
2
] [mm2] AWG [Nm] [lb in] L [mm]
[mm
0,2-2,5 0,2-2,5 24-12 0,6-0,8 5-7 6,5
Anzugsmoment
Torque
Couple de serrage
Par de apriete
Abisolierlänge
Stripping length
Longueur à dénuder
Longitud a desaislar
Fuse
For device protection, there is an internal fuse
(250 V AC / 125 V d.c.):
AK-PS 075 = 1.25 AT
AK-PS 150 = 3.15 AT
AK-PS 250 = 3.15 AT
LED
Normal operation of the
power supply
On Off
1. The output voltage is less than 21.5 V. There is a secondary consumer short circuit
2. There is no input voltage or there is a device fault
Load Table AK I/O Modules
The AK-PS ___ has an output rating to power I/O devices in any combination. Refer to table below for individual
I/O device power requirements.
Module name Description Inputs & Outputs Power
AK-CM 101_ / 102_ Communications module 2 VA
AK-XM 101_ Universal input module 8 universal inputs 2 VA
AK-XM 102_ Digital input module
AK-XM 103_ Universal input module &
AK-XM 107_ Pulse measuring 8 pulse inputs 2 VA
AK-XM 204_ Digital output module 8 relay outputs 5 VA
AK-XM 205_ Universal analog input &
AK-XM 208_ Bipolar stepper output module 4 bipolar stepper outputs 5 VA
AK-CC_ / PC_ ... AK controller 8 VA
(low voltage) / (high voltage)
analog output module
digital output module
or overload.
LED
If the internal fuse is triggered, there is most probably
a malfunction in the device. In this case, the device
must be replaced!
8 digital inputs, 2 VA
4 universal inputs,
4 analog outputs
8 relay outputs,
8 universal inputs
2 VA
5 VA
2 Instructions RI8LJ402 © Danfoss 12-2017 AK-PS
ADAP-KOOL®