Instructions |
|
|
|
|
|
|
|
|
|
|
|
|
|
Power supply |
|
|
|
|
|
|
|
|
|
|
|
|
<![if ! IE]> <![endif]>080R9257 |
AK-PS 075, AK-PS 150, AK-PS 250 |
|
|
||||||||||
AK-PS 075, 080Z0053 |
|
|
|
|
|
|
|
|
|
|
EN 50022-35. Ensure mounting rails are |
||
|
|
|
Input Voltage |
|
|
|
|
|
|
|
|
|
|
|
|
|
100 - 240 V a.c. |
|
|
|
|
|
|
|
|
The power supply can be snapped onto |
|
|
|
|
50-60 Hz |
|
|
|
|
|
|
|
|
|
all mounting rails in accordance with |
|
|
|
0.4 A (120 V a.c.) / |
|
|
|
|
|
|
||||
|
|
|
0.2 A (230 V a.c.) |
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
.4") |
|
|
fixed horizontally. |
|||
|
|
|
|
|
|
(1 |
|
|
|
|
|||
|
|
|
|
mm |
|
|
|
|
|
|
In order to comply with the UL approval, |
||
|
|
|
36 |
|
|
|
|
|
|
|
|
use copper cables that are designed for |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
operating temperatures of 75 °C (167 °F) |
|
|
|
<![if ! IE]> <![endif]>mm(3.5") |
|
|
|
|
|
|
|
|
|
DIN rail mounting |
|
|
|
<![if ! IE]> <![endif]>90 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Max |
61 |
mm |
|
|
|
|
||||
|
|
|
|
|
|
|
Output: |
|
|||||
|
|
|
|
|
|
|
(2. |
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
4") |
24 V d.c. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
0.75 A |
|
|
AK-PS 150, 080Z0054 |
|
|
|
|
|
|
|
|
|
18 VA |
|
|
|
Input Voltage |
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
100 - 240 V a.c. |
|
|
|
|
|
|
|
|
|
|
|
|
|
50-60 Hz |
|
|
|
|
|
|
|
|
|
Flat surface mounting |
|
|
|
0.85 A (120 V a.c.) / |
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|||||
|
|
|
0.4 A (230 V a.c.) |
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
.1") |
|
|
|
|||
|
|
|
|
|
|
(2 |
|
|
|
|
|
||
|
|
|
|
mm |
|
|
|
|
|
|
|
||
|
|
|
54 |
|
|
|
|
|
|
|
|
|
|
|
|
|
<![if ! IE]> <![endif]>mm(3.5") |
|
|
|
|
|
|
|
|
|
Environmental Range: |
|
|
|
<![if ! IE]> <![endif]>90 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
IP20 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Operation: |
|
|
|
Max |
|
|
|
|
|
|
|
|
|
-25°C tamb +70°C (-13°F < tamb < 158°F) |
|
|
|
61 |
mm |
|
|
|
|
|
Derating of output current: |
|||
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
2.5 % /K > +55°C (131°F) |
||||
|
|
|
|
|
(2. |
|
Output: |
||||||
|
|
|
|
|
|
|
|
|
24 V d.c. |
Storage: |
|||
|
|
|
|
|
|
|
|
|
|
4") |
|
||
|
|
|
|
|
|
|
|
|
|
|
|
1.5 A |
-40°C to +85°C (-40°F < tamb < 185°F) |
|
|
|
|
|
|
|
|
|
|
|
|
36 VA |
Humidity: |
|
AK-PS 250, 080Z0055 |
Input Voltage |
|
|
|
|
|
|
|
|
0 - 95% RH, non condensing |
||
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
100 - 240 V a.c. |
|
|
|
|
|
|
|
|
|
|
|
|
|
50-60 Hz |
|
|
|
|
|
|
|
|
|
|
|
|
|
1.4 A (120 V a.c.) / |
|
|
|
|
|
|
Approvals |
|||
|
|
|
0.65 A (230 V a.c.) |
|
|
.8") |
|
|
|
||||
|
|
|
|
72 |
|
|
|
|
|
S |
|||
|
|
|
|
|
(2 |
|
|
|
|||||
|
|
|
|
|
mm |
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
UL File # E312396 |
|
|
|
<![if ! IE]> <![endif]>90mm(3.5") |
|
|
|
|
|
|
|
|
|
|
|
|
|
Max |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
61 |
mm |
|
|
|
Output: |
|
|||
|
|
|
|
|
|
(2. |
|
Class II |
|||||
|
|
|
|
|
|
|
|
|
|
24 V d.c. |
|||
|
|
|
|
|
|
|
|
|
|
4") |
|
||
|
|
|
|
|
|
|
|
|
|
|
|
2.5 A |
|
|
|
|
|
|
|
|
|
|
|
|
|
60 VA |
|
|
RI8LJ402 |
12-2017 |
|
|
|
|
|
|
|
|
|
|
|
<![endif]>080R9257
Connection / Connecting cable
To achieve a reliable and shockproof connection, strip the connecting ends according to table 1!
Tabelle 1 |
|
Starr |
|
Flexibel |
|
Anzugsmoment |
|
Abisolierlänge |
||||
|
|
|
|
|||||||||
Table 1 |
|
Solid |
|
Stranded |
|
Torque |
|
Stripping length |
||||
Tableau 1 |
|
Rigide |
|
Souple |
|
Couple de serrage |
|
Longueur à dénuder |
||||
Tabla 1: |
|
Rigido |
|
Flexible |
|
Par de apriete |
|
Longitud a desaislar |
||||
|
|
|
[mm2] |
|
[mm2] |
AWG |
[Nm] |
|
[lb in] |
|
L [mm] |
|
|
|
|
|
|
||||||||
12 |
|
0,2-2,5 |
|
0,2-2,5 |
24-12 |
0,6-0,8 |
|
5-7 |
|
6,5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Fuse
For device protection, there is an internal fuse (250 V AC / 125 V d.c.):
AK-PS 075 = 1.25 AT
AK-PS 150 = 3.15 AT
AK-PS 250 = 3.15 AT
LED
If the internal fuse is triggered, there is most probably a malfunction in the device. In this case, the device must be replaced!
|
LED |
|
|
On |
Off |
|
|
Normal operation of the |
1. The output voltage is less than 21.5 V. There is a secondary consumer short circuit |
power supply |
or overload. |
|
2. There is no input voltage or there is a device fault |
|
|
Load Table AK I/O Modules
The AK-PS ___ has an output rating to power I/O devices in any combination. Refer to table below for individual I/O device power requirements.
Module name |
Description |
Inputs & Outputs |
Power |
|
|
|
|
AK-CM 101_ / 102_ |
Communications module |
|
2 VA |
|
|
|
|
AK-XM 101_ |
Universal input module |
8 universal inputs |
2 VA |
|
|
|
|
AK-XM 102_ |
Digital input module |
8 digital inputs, |
2 VA |
|
(low voltage) / (high voltage) |
|
|
|
|
|
|
AK-XM 103_ |
Universal input module & |
4 universal inputs, |
2 VA |
|
analog output module |
4 analog outputs |
|
|
|
|
|
AK-XM 107_ |
Pulse measuring |
8 pulse inputs |
2 VA |
|
|
|
|
AK-XM 204_ |
Digital output module |
8 relay outputs |
5 VA |
|
|
|
|
AK-XM 205_ |
Universal analog input & |
8 relay outputs, |
5 VA |
|
digital output module |
8 universal inputs |
|
|
|
|
|
AK-XM 208_ |
Bipolar stepper output module |
4 bipolar stepper outputs |
5 VA |
|
|
|
|
AK-CC_ / PC_ ... |
AK controller |
|
8 VA |
|
|
|
|
2 |
Instructions RI8LJ402 |
© Danfoss 12-2017 |
AK-PS |
<![endif]>ADAP-KOOL®