Danfoss AK-PI 100 Installation guide

-20°< t
-0°F < t 0 - 95% RH, non condensing IP10 / VBG4 UL: E166834
amb
amb
< 55°C
Instructions
Woodley Protocol interface AK-PI 100
AK-PI 100 installation:
See manual: RS8FB
Princip
Max. 199 addresses
RI8MK102 3-2008
Supply voltage:
Transformer Class II
The 24 V must not be shared by other controllers or units
The 24 V input must not have earth connection
Quick setup
1. Address = 000 (Factory setting)
2. Connect service tool
3. Configuration (IP and MDM/WTP). See manual.
4. Disconnect service tool
5. Set address on AK-PI 100
6. Connect to Woodley 4 way TPI card. (WTP) or to Woodley MDM-PI (MDM)
7. Connect to AK-SC 255
e.g. 012 ( from 11 to 199)
8. AK-SC 255 configuration
a) Ethernet b) I/O Network c) Rescan d) PI 100/ 200 e) Mark PI-address f) Rescan g) Configuration /Refrigeration / Add controls / Setup
Further information ! AK-PI 100 manual / AK-SC 255 manual
2 Instructions RI8MK102 © Danfoss 3/2008 AK-PI 100 Woodley Protocol interface