Danfoss AK-PI 100 User guide

User Guide
Woodley Protokol interface
AK-PI 100
ADAP-KOOL® Refrigeration control systems
Introduction
Function
The AK-PI 100 is an intermediary link allowing Woodley type units to be operated by an AK-SC 255 system controller.
This way of operating the Woodley units replaces the previous Woodley S5 operating interface.
Application
The AK-PI 100 is used on systems with an AK-SC 255 system con­troller, but which still contain older Woodley type units. These types can be:
• Woodley MDM units
• Woodley 4 way TPI cards
• Older units connected to the WTP bus (WTP = Woodley Third Party)
Measurements and status readings from the individual Woodley units are uploaded to the AK-PI 100 and on to the AK-SC 255, where the data is presented in the same way as other ADAP­KOOL(r) units.
Principle
The AK-SC 255 and the AK-PI 100 are linked by Ethernet.
For a straightforward connection, the two units can be linked by a switch. In this case, the IP addresses are set to static addresses. You can choose any addresses, but only if nothing else is connected. (It is easiest to use a router and dynamic address allocation. In this case, the router allocates one address to the AK-SC 255 and an­other to the PI unit. You can only use this solution if the system is self-contained with no contact to an external operating interface.)
In larger systems or if IP communication takes place from the sys­tem, the connection must be based on a router or a switch. If a router is used, the IP address of the AK-PI 100 may be dynamic, but the address of the AK-SC 255 must be static. If a switch is used, both must be static.
You will need to request static addresses from the IT department yourself, and then congure the addresses in both units. You should always use this solution if the system is accessed by an external service company, for example for log extraction, alarm handling or servicing.
2 Manual RS8FB102 © Danfoss 03-2008 AK-PI 100
Communication/number of addresses
An AK-PI 100 can be congured for two types of communication
- MDM communication or WTP communication. If both types of communication are needed in the system, two AK-PI 100 units must be used. With MDM communication, up to 160 controllers can be con­nected to one AK-PI 100. With WTP communication, up to 128 controllers can be connected to one AK-PI 100.
In total, the AK-SC 255 can handle up to 162 addresses, including units connected directly to the system controller.
Addresses
In principle, there are three types of address:
IP addresses
An IP address must be congured for the system controller and for the AK-PI 100. The address can be either static or dynamic - the choice is made by changing a setting. To use a static address, you also need to congure the address. If the system is accessed from the outside, the system controller should always be set to static, so that the external connection always knows the address and is able to contact the unit. (The IP is congured using a menu.)
Network addresses
A network must always have one, and only one, unit acting as master. In this case, the master is AK-SC 255. To specify this, the address is congured to = 0. This master controls communication with all other controllers in the network. A PI unit is handled as a controller in the network, and you can view its address in the “Channel PI-100/200” screen. Each PI unit is congured with a dierent address. You can choose 11, 12 or above, e.g. 21. (Addresses 1 to 10 are reserved for sub­nets.) Connection: When you congure the system controller, the relevant AK-PI 100 is assigned to the network. The system controller then recognises the link to all the MDM units/WTP units. The check marks in the screenshot on the right show that contact with PI units has been selected. One has the address 21 and the other has the address 90 (the numbers 084Z8521 and 22 indicate that there is one PI 200 and one PI 100).
Controller addresses
All controllers in the same network must have dierent addresses. This means all controllers connected to a system controller via:
• LON communication
• MOD bus communication
• DANBUSS communication via an AK-PI 200
• MDM communication via an AK-PI 100
• WTP communication via an AK-PI 100
A maximum of 162 controllers can be connected to a system con­troller. The system controller cannot handle addresses above 199.
The AK-PI 100 has an auxiliary function that can shift a group of addresses, so that you do not need to change the address in each individual MDM and WTP unit. The function is called “address oset”, and informs the AK-SC 255 of the changed addresses. After the function, a unit has the follow­ing address: Oset value + congured address of the unit.
DANBUSS communication: Address options 1 to 120 LON communication: Address options 1 to 199 MOD bus communication: Address options 1 to 199 MDM communication: Address options 1 to 199 (255) WTP communication: Address options 1 to 199 (248)
AK-SC 255: Address options 1 to 199
Max. number: 162
AK-PI 100 Manual RS8FB102 © Danfoss 03-2008 3
Loading...
+ 5 hidden pages