Danfoss AK-PI 100 User guide

User Guide
Woodley Protokol interface
AK-PI 100
ADAP-KOOL® Refrigeration control systems
Introduction
Function
The AK-PI 100 is an intermediary link allowing Woodley type units to be operated by an AK-SC 255 system controller.
This way of operating the Woodley units replaces the previous Woodley S5 operating interface.
Application
The AK-PI 100 is used on systems with an AK-SC 255 system con­troller, but which still contain older Woodley type units. These types can be:
• Woodley MDM units
• Woodley 4 way TPI cards
• Older units connected to the WTP bus (WTP = Woodley Third Party)
Measurements and status readings from the individual Woodley units are uploaded to the AK-PI 100 and on to the AK-SC 255, where the data is presented in the same way as other ADAP­KOOL(r) units.
Principle
The AK-SC 255 and the AK-PI 100 are linked by Ethernet.
For a straightforward connection, the two units can be linked by a switch. In this case, the IP addresses are set to static addresses. You can choose any addresses, but only if nothing else is connected. (It is easiest to use a router and dynamic address allocation. In this case, the router allocates one address to the AK-SC 255 and an­other to the PI unit. You can only use this solution if the system is self-contained with no contact to an external operating interface.)
In larger systems or if IP communication takes place from the sys­tem, the connection must be based on a router or a switch. If a router is used, the IP address of the AK-PI 100 may be dynamic, but the address of the AK-SC 255 must be static. If a switch is used, both must be static.
You will need to request static addresses from the IT department yourself, and then congure the addresses in both units. You should always use this solution if the system is accessed by an external service company, for example for log extraction, alarm handling or servicing.
2 Manual RS8FB102 © Danfoss 03-2008 AK-PI 100
Communication/number of addresses
An AK-PI 100 can be congured for two types of communication
- MDM communication or WTP communication. If both types of communication are needed in the system, two AK-PI 100 units must be used. With MDM communication, up to 160 controllers can be con­nected to one AK-PI 100. With WTP communication, up to 128 controllers can be connected to one AK-PI 100.
In total, the AK-SC 255 can handle up to 162 addresses, including units connected directly to the system controller.
Addresses
In principle, there are three types of address:
IP addresses
An IP address must be congured for the system controller and for the AK-PI 100. The address can be either static or dynamic - the choice is made by changing a setting. To use a static address, you also need to congure the address. If the system is accessed from the outside, the system controller should always be set to static, so that the external connection always knows the address and is able to contact the unit. (The IP is congured using a menu.)
Network addresses
A network must always have one, and only one, unit acting as master. In this case, the master is AK-SC 255. To specify this, the address is congured to = 0. This master controls communication with all other controllers in the network. A PI unit is handled as a controller in the network, and you can view its address in the “Channel PI-100/200” screen. Each PI unit is congured with a dierent address. You can choose 11, 12 or above, e.g. 21. (Addresses 1 to 10 are reserved for sub­nets.) Connection: When you congure the system controller, the relevant AK-PI 100 is assigned to the network. The system controller then recognises the link to all the MDM units/WTP units. The check marks in the screenshot on the right show that contact with PI units has been selected. One has the address 21 and the other has the address 90 (the numbers 084Z8521 and 22 indicate that there is one PI 200 and one PI 100).
Controller addresses
All controllers in the same network must have dierent addresses. This means all controllers connected to a system controller via:
• LON communication
• MOD bus communication
• DANBUSS communication via an AK-PI 200
• MDM communication via an AK-PI 100
• WTP communication via an AK-PI 100
A maximum of 162 controllers can be connected to a system con­troller. The system controller cannot handle addresses above 199.
The AK-PI 100 has an auxiliary function that can shift a group of addresses, so that you do not need to change the address in each individual MDM and WTP unit. The function is called “address oset”, and informs the AK-SC 255 of the changed addresses. After the function, a unit has the follow­ing address: Oset value + congured address of the unit.
DANBUSS communication: Address options 1 to 120 LON communication: Address options 1 to 199 MOD bus communication: Address options 1 to 199 MDM communication: Address options 1 to 199 (255) WTP communication: Address options 1 to 199 (248)
AK-SC 255: Address options 1 to 199
Max. number: 162
AK-PI 100 Manual RS8FB102 © Danfoss 03-2008 3
Installation
Preparing the TCP/IP connection
The AK-PI 100 must be linked to the AK-SC 255 physically and also with a software setting. You can do this as follows:
1. Connection
Cables are run from the units to a router or to a switch.
2. Setting
a) Router
- Dynamic: If DHCP is enabled, no settings need to be changed in the router
- Static: Check that the static address range does not conict with the DHCP range
b) Switch
No direct settings are necessary, but addresses are always static for AK-SC 255 and AK-PI 100
c) AK-SC 255
- Choose static if the AK-SC 255 and AK-PI 100 are connected by a switch or if the system can be accessed from outside. Then congure the IP address (request an IP address from the IT ocer of the department).
- Select dynamic if the system is self-contained and both units are connected to a router.
d) In the AK-PI 100, set IP addressing to either static or dynamic.
- Choose static if the AK-SC 255 and AK-PI 100 are linked by a switch. Then congure the IP address (request an IP address from the IT ocer of the department).
- Select dynamic if the system is self-contained and both units are connected to a router.
3. If a router or switch is connected, turn it on.
AK-PI 100 conguration
1. Set the address on the front to 0 (0 is the factory setting)
2. Switch on
3. Attach the service tool (the service tool can only be used if the address is set to 0)
4. Set AK-PI 100 a. Press the service key button b. Unlock the conguration c. Select System setup d. Enter a name for the controller (the name cannot be seen
outside the PI unit yet) e. Select the protocol you want to use (MDM or WTP) f. Select whether you want to use the “Address oset” function g. Switch to IP setup if you are using a static IP address.
Congure the address h. Lock the conguration
5. Disconnect the service tool
6. Set the address on the front (for example to 12). The address range is between 11 and 199.
4 Manual RS8FB102 © Danfoss 03-2008 AK-PI 100
Connect the units
AK-SC 255: Attach the connector to the Ethernet connector. AK-PI 100: The connection to the AK-SC 255 (switch/router) must use the
“LAN” connector.
AK-SC 255 settings
Dene the IP setup
Switch to the displayed screen with:
Communications / Internet / Cong
Set
• DHCP to Yes for Dynamic IP If necessary
• Congure the mask If necessary
• Congure the IP address
AK-PI 100: The connection to the Woodley unit must use the
connector for the “Service tool”.
Scanning for IP addresses and Woodley units
Switch to the displayed screen with:
Communications / I/O Network / Rescan channels
• Select the “Channel PI-100/200” eld
• Activate the “Rescan Network” function
• Click the “PI-100/200” button to switch to the next screen
• Select the addresses to be contacted (addresses 21 and 90 are shown here)
• Go back to the previous screen
• Activate the “Rescan Network” function
AK-PI 100 Manual RS8FB102 © Danfoss 03-2008 5
Dene the setup of the Woodley units
Switch to the displayed screen with:
Communications / Refrigeration / Add Controls
Specify the description le:
• Select No for “Pack controller”
• Select the number of controllers (in this example 10)
• Click the “Setup” button to switch to the next screen
• Click “Edit” on the rst controller type (in the “Type” eld)
• Select the description le matching the controller.
Congure the data in the unit:
• Go back to the overview screen for all Woodley units
• Press “Setup” for the relevant controller type
• Set the address. This is the address the unit is set to + any “address oset value”
• Edit the name if necessary
• Change the settings.
All controller types and software versions will require a description le. Select the relevant le. If the le is not listed, it must be uploaded to the AK-SC 255. Contact Danfoss.
6 Manual RS8FB102 © Danfoss 03-2008 AK-PI 100
Overview of functions in the AK-PI 100
The overview display will show the following:
• Status of alarm transmission
• Date and time
• Quality of the signal for communication with the Woodley MDM unit or to Woodley TPI unit (the value is always 0 if the service tool is attached).
The conguration display gives access to the following:
• The conguration lock is used with the following settings:
- Communication setting (MDM or WTP)
- Address oset setting (addresses are congured for all units on the communication line. If these address values conict with other addresses, the entire connected group can be “oset”. For example a group of units has the addresses 20 to 31. By setting “Address oset” to 50, the address will become 70 to 81 in the AK-SC 255. This removes the need to change the addresses of the existing units).
- Adjustment of a static IP address.
• In “System setup” you can give the unit a name
• You can change the IP setup
Examples of controller addresses
Example of IP addresses
AK-PI 100 Manual RS8FB102 © Danfoss 03-2008 7
Ordering
Type Function Application Language Code no.
AK-PI 100 Protokol interface
Accessories Accessories Transformer module 230 V / 115 V to 24 V
AK-PS 075 18 VA Supply 080Z0053
- RS 232 cable between AK-PI 100 and Woodley MDM / 4 way TPI card 080Z0263
Intermediary link between System controller AK-SC 255 and Woodley controllers. The unit makes is possible to change the user interface from Woodley's S5 to Danfoss' AK-SC 255
English, French, 080Z8522
Data
Supply voltage 24 V AC. +/- 20%
Power consumption AK-PI 100 8 VA
Ambient environment During transport -40 to 70°C
During operation -20 to 55°C ,
Enclosure Material PC / ABS
Protection IP10 , VBG 4
Installation Built in. On panel wall or DIN rail
Weight Ca. 600 g
Approvals EU low voltage directive and EMC require-
ments are complied with
0 to 95% RH (non condensing) No shock inuences / vibrations
LVD tested to EN 60730 EMC tested Immunity to: EN 61000-6-2 Emission to: EN 61000-6-3
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specications already agreed. All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
8 Manual RS8FB102 © Danfoss 03-2008 AK-PI 100
DE-DB
Loading...