AK-PC 782A are complete regulating units for capacity control of
compressors and condensers in a transcritical CO booster system
with parallel compressor. The controller is with oil management,
heat recovery function and CO gas pressure control.
In addition to capacity control, the controllers can give signals to
other controllers about the operating condition, e.g. forced closing
of expansion valves, alarm signals and alarm messages.
The controller’s main function is to control compressors and
condensers so that operation all the time takes place at the
energy-optimum pressure conditions. Both suction pressure
and condensing pressure are controlled by signals from pressure
transmitters.
Capacity control must be carried out by suction pressure P0. (The
P0 signal for the parallel compressor is supplied by the pressure
transmitter on the receiver).
Among the different functions are:
• Capacity control of up to 10 compressors on MT and 8 on IT
• Capacity control of up to 4 compressors on LT
• Up to 3 unloaders for each compressor
• Control of oil separator and oil receiver
• Speed control of one or two compressors in each group
• Up to 6 safety inputs for each compressor
• Option for capacity limitation to minimize consumption peaks
• If the compressor does not start, signals can be transmitted to
other controllers so that the electronic expansion valves will be
closed
• Regulation of liquid injection into suction line
• Safety monitoring of high pressure / low pressure / discharge
temperature
• Capacity control of up to 8 fans
• Floating reference with regard to outside temperature
• Heat recovery function
• CO gas cooler control and receiver control
• Ejector regulation: HP, LE (liquid)
• Safety monitoring of fans
• The status of the outputs and inputs is shown by means of lightemitting diodes on the front panel
• Alarm signals can be generated via data communication
• Alarms are shown with texts so that the cause of the alarm is
easy to see.
• Plus some completely separate functions that are totally
independent of the regulation – such as alarm, thermostat,
pressure and PI-regulating functions.
SW = 3.5x
Examples
Traditional capacity control
Prec
Heat recovery functions, controlling the condensing pressure and
receiver pressure
The great advantage of this series of controllers is that it can
be extended as the size of the plant is increased. It has been
developed for refrigeration control systems, but not for any
specific application – variation is created through the read-in
software and the way you choose to define the connections.
The same modules that are used for each regulation and the
composition can be changed, as required. With these modules
(building blocks) it is possible to create a multitude of various
kinds of regulations. But it is you who must help adjusting the
regulation to the actual needs – these instructions will assist you to
find your way through all the questions so that the regulation can
be defined and the connections made.
Controller
Top part
Bottom part
The controller is the cornerstone of the regulation. The module has
inputs and outputs capable of handling small systems.
• The bottom part – and hence the terminals – are the same for all
controller types.
• The top part contains the intelligence with software. This unit will vary
according to controller type. But it will always be supplied together
with the bottom part.
• In addition to the software, the top part is provided with connections
for data communication and address setting.
Advantages
• The controller’s size can “grow” as systems grow
• The software can be set for one or more regulations
• Several regulations with the same components
• Extension-friendly when systems' requirements are changed
• Flexible concept:
– Controller series with common construction
– One principle – many regulation uses
– modules are selected for the actual connection requirements
– The same modules are used from regulation to regulation
Extension modules
If the system grows and more functions have to be controlled, the
regulation can be extended.
With extra modules more signals can be received and more relays cut in
and out – how many of them – and which – is determined by the relevant
application.
Examples
A regulation with few connections
can be performed with the controller
module alone.
If there are many connections, one or more
extension modules have to be mounted.
Setup and operation of an AK controller must be accomplished via
the “AK-Service Tool” software program.
The program is installed on a PC, set up and operation of the
various functions is carried out via the controller’s menu displays.
Displays
The menu displays are dynamic, so that different settings in one
menu will result in different setting possibilities in other menus.
A simple application with few connections will give a set-up with
few settings.
A corresponding application with many connections will give a
set-up with many settings.
From the overview display there is access to further displays for
the compressor regulation and the condenser regulation.
At the bottom of the display there is access to a number of general
functions, such as “time table”, “manual operation”, “log function”,
“alarms”, and “service” (configuration).
Network linking
The controller can be linked up to a network together with other
controllers in an ADAP-KOOL® refrigeration control system. After
the set-up, operation can be performed at a distance with e.g. our
software program type AKM.
Users
The controller comes supplied with several languages, one of
which can be selected and employed by the user. If there are
several users, they may each have their choice of language. All
users must be assigned a user profile which either gives access to
full operation or gradually limits the operation to the lowest level
that only allows you “to see”.
Language selection is part of the Service Tool settings.
If the language selection is not available in the Service Tool for the
current regulator, English texts will be displayed.
External display
An external display can be fitted in order for P0 (Suction) and Pc
(Condensing) readings to be displayed.
A total of 4 displays can be fitted and with one setting it is possible
to choose between the following readings: suction pressure,
suction pressure in temperature, Ss, Sd, condenser pressure,
condenser pressure in temperature, S7 gas cooler temperature,
hot tap water at heat recovery and heat exchanger temperature at
heat recovery.
A graphical display with control buttons can also be fitted.
A number of light-emitting diodes makes it possible to follow the
signals that are received and transmitted by the controller.
Log
From the log function you can define the measurements you wish
to be shown.
The collected values can be printed, or you may export them to a
file. You can open the file in Excel.
If you are in a service situation, you can show measurements in a
trend function. The measurements are then made real-time and
displayed instantly.
n Power
n Comm
n DO1 n Status
n DO2 n Service Tool
n DO3 n LON
n DO4 n I/O Extension
n DO5 n Alarm
n DO6
n DO7 n Display
n DO8 n Service Pin
Slow flash = OK
Quick flash = answer from gateway
Constantly ON = error
Constantly OFF = error
Flash = active alarm/not cancelled
Constant ON = Active alarm/cancelled
Alarm
The display gives you an overview of all active alarms. If you wish
to confirm that you have seen the alarm you can cross it off in the
acknowledge field.
If you want to know more about a current alarm you can click on it
and obtain an information display on the screen.
A corresponding display exists for all earlier alarms. Here you can
upload information if you need further details about the alarm
history.
This section describes how the controller is designed.
The controller in the system is based on a uniform connection
platform where any deviations from regulation to regulation is
determined by the used top part with a specific software and
which input and output signals the relevant application will
require. If it is an application with few connections, the controller
2.1 Module survey
Controller module – capable of handling minor plant
requirements.
Extension modules
When the complexity becomes greater and additional inputs or
outputs are required, modules can be attached to the controller.
A plug on the side of the module will transmit the supply voltage
and data communication between the modules.
Top part
The upper part of the controller module contains the intelligence.
This is the unit where the regulation is defined and where data
communication is connected to other controllers in a bigger
network.
Connection types
There are various types of inputs and outputs. One type may, for
example, receive signals from sensors and switches. Another may
receive a voltage signal, and a third type may be outputs with
relays etc. The individual types are shown in the table below.
module (top part with belonging bottom part) may be sufficient.
If it is an application with many connections, it will be necessary to
use the controller module plus one or more extension modules.
This section will give you a survey of possible connections plus
assistance in selecting the modules required by your actual
application.
Optional connection
When a regulation is planned (set up), it will generate a need for a
number of connections distributed on the mentioned types. This
connection must then be made on either the controller module
or an extension module. The only thing to be observed is that
the types must not be mixed (an analogue input signal must for
instance not be connected to a digital input).
Programming of connections
The controller must know where you connect the individual input
and output signals. This takes place in a later configuration where
each individual connection is defined based on the following
principle:
• to which module?
• at which point (”terminals”)?
•
what is connected (e.g. pressure transmitter/type/pressure range)?
Controller with analogue inputs
and relay outputs.
Extension module with additional
relay outputs and additional
analogue inputs.
Top part
Extension module with
2x analogue output signals
The module with additional relay outputs is
also available in a version where the top part
is provided with change-over switches so
that the relays can be overridden.
If the row of modules needs to
be interrupted due to length or
external positioning, a communication module should be used.
Controller for capacity control of MT (10 compressors), IT (8 compressors) and
LT (4 compressors).
Up to 3 unloaders per compressor, 8 fans and max. 220 inputs/outputs.
LVD tested according to EN 60730
EMC tested
Immunity according to EN 61000-6-2
Emission according to EN 61000-6-3
E31024 for PC-module
E357029 for XM and CM-modules
The module dimension is 72 mm.
Modules in the 100-series consist of one
module.
Modules in the 200-series consist of two
modules.
Controllers consist of three modules.
The length of an aggregate unit = n x 72 + 8
There are several controllers in the series. The function is
determined by the programmed software, but on the outside
the controllers are identical – they all have the same connection
possibilities:
11 analogue inputs for sensors, pressure transmitters, voltage
signals and contact signals.
8 digital outputs, with 4 Solid state outputs and 4 relay outputs.
Supply voltage
24 V AC or DC to be connected to the controller.
The 24 V must not be retransmitted and used by other controllers
as it is not galvanically separated from inputs and outputs. In other
words, you must use a transformer for each controller. Class II is
required. The terminals must not be earthed.
The supply voltage to any extension module is transmitted via the
plug on the right-hand side.
The size of the transformer is determined by the power
requirement of the total number of modules.
The supply voltage to a pressure transmitter can be taken either
from the 5 V output or from the 12 V output depending on
transmitter type.
Data communication
If the controller is to be included in a system, communication must
take place via the LON connection.
The installation has to be made as mentioned in the separate
instructions for LON communication.
Address setting
If it is a system manager AK-SM .., then 1-999
Service PIN
When the controller is connected to the data communication
cable, the gateway must have knowledge of the new controller.
This is obtained by pushing the key PIN. The LED “Status” will flash
when the gateway sends an acceptance message.
Operation
The configuration operation of the controller must take place
from the software program “Service Tool”. The program must be
installed on a PC, and the PC must be connected to the controller
via the USB-B plug on the front of the unit.
Light-emitting diodes
There are two rows with LEDs indicating:
Left row:
• Voltage supply to the controller
• Communication active with the bottom PC board (red = error)
• Status of outputs DO1 to DO8
Right row:
• Software status (slow flash = OK)
• Communication with Service Tool
• Communication on LON
• Communication with AK-CM 102
• Alarm when LED flashes
– 1 LED that is not used
• Communication with display on RJ11 plug
• “Service Pin” switch has been activated
PIN
Address
n Power
n Comm
n DO1 n Status
n DO2 n Service Tool
n DO3 n LON
n DO4 n I/O Extension
n DO5 n Alarm
n DO6
n DO7 n Display
n DO8 n Service Pin
Keep the safety distance!
Low and high voltage must
not be connected to the
same output group
Slow flash = OK
Quick flash = answer from gateway
Constantly ON = error
Constantly OFF = error
Flash = active alarm/not cancelled
Constant ON = Active alarm/cancelled
A small module (option board) can be placed on the bottom part
of the controller. The module is described later in the document.
The module contains 8 analogue inputs for sensors, pressure
transmitters, voltage signals and contact signals.
Supply voltage
The supply voltage to the module comes from the previous
module in the row.
Supply voltage to a pressure transmitter can be taken from either
the 5 V output or the 12 V output depending on transmitter type.
Light-emitting diodes
Only the two top LEDs are used. They indicate the following:
• Voltage supply to the module
• Communication with the controller is active (red = error)
The module contains :
4 analogue inputs for sensors, pressure transmitters, voltage
signals and contact signals.
4 analogue voltage outputs of 0 - 10 V
Supply voltage
The supply voltage to the module comes from the previous
module in the row.
Supply voltage to a pressure transmitter can be taken from either
the 5 V output or the 12 V output depending on transmitter type.
Galvanic isolation
The inputs are galvanically separated from the outlets.
The outlets AO1 and AO2 are galvanically separated from AO3 and
AO4.
Light-emitting diodes
Only the two top LEDs are used. They indicate the following:
• Voltage supply to the module
• Communication with the controller is active (red = error)
Max. load
I < 2.5 mA
R > 4 kΩ
Accuracy
Analog inputs: +/- 10 mV
Analog outputs: +/- 100 mV
The supply voltage to the module comes from the previous
module in the row.
AK-XM 204B only
Override of relay
Eight change-over switches at the front make it possible to
override the relay’s function.
Either to position OFF or ON.
In position Auto the controller carries out the control.
Light-emitting diodes
There are two rows with LEDs. They indicate the following:
Left row:
• Voltage supply to the controller
• Communication active with the bottom PC board (red = error)
• Status of outputs DO1 to DO8
Right row: (AK-XM 204B only):
• Override of relays
ON = override
OFF = no override
AK-XM 204A AK-XM 204B
Fuses
Behind the upper part there is a fuse for each output.
Max. 230 V
AC-1: max. 4 A (ohmic)
AC-15: max. 3 A (Inductive)
AK-XM 204B
Override of relay
Keep the safety distance!
Low and high voltage must
not be connected to the
same output group
The module contains:
8 analogue inputs for sensors, pressure transmitters, voltage
signals and contact signals.
8 relay outputs.
Supply voltage
The supply voltage to the module comes from the previous
module in the row.
AK-XM 205B only
Override of relay
Eight change-over switches at the front make it possible to
override the relay’s function.
Either to position OFF or ON.
In position Auto the controller carries out the control.
Light-emitting diodes
There are two rows with LEDs. They indicate the following:
Left row:
• Voltage supply to the controller
• Communication active with the bottom PC board (red = error)
• Status of outputs DO1 to DO8
Right row: (AK-XM 205B only):
• Override of relays
– ON = override
– OFF = no override
Fuses
Behind the upper part there is a fuse for each output.
AK-XM 205A AK-XM 205B
max. 10 V
Max. 230 V
AC-1: max. 4 A (ohmic)
AC-15: max. 3 A (Inductive)
Keep the safety distance!
Low and high voltage
must not be connected to
the same output group
The module contains:
8 analogue inputs for sensors, pressure transmitters, voltage
signals and contact signals.
4 outputs for stepper motors.
Supply voltage
The supply voltage to the module comes from the previous
module in the row. Here supplied with 5 VA.
An additional and separated power supply must be installed,
which must be galvanically separated from the supply for the
control range. Class II is required.
(Power requirements: 7.8 VA for controller + xx VA per valve).
2 separated UPS´s are recommended, one for the pack controller
and another AK-XM 208C module if the valves need to open/ close
during a power failure. If the AK-CM 102 module is installed it is
also recommended a separated UPS.
Light-emitting diodes
There is one row with LEDs, indicating the following:
• Voltage supply to the module
• Communication active with the bottom PC board (red = error)
• Step1 to step4 OPEN: Green = Open
• Step1 to step4 CLOSE: Green = Close
• Red flash = Error on motor or connection
Separate voltage supply
is required
24 V AC/DC / fx. 13 VA
Output:
24 V DC
20-500 step/s
Max. Phase current = 325 mA RMS
∑ P
= 21 VA
max.
The connection to the valve must
not be broken using a relay
Display of important measurements from the controller, e.g.
appliance temperature, suction pressure or condensing pressure.
Setting of the individual functions can be performed by using the
display with control buttons.
It is the controller used that determines the measurements and
settings that can occur.
Connection
The extension module is connected to the controller module via
a cable with plug connections. You have to use one cable per
module. The cable is supplied in various lengths.
Both types of display (with or without control buttons) can be
connected to either display output A, B, C and D.
Ex.
A: P0. Suction pressure in °C.
B: Pc. Condensing pressure in °C.
When the controller starts up, the display will show the output
that is connected.
- - 1 = output A
- - 2 = output B
etc.
EKA 163B EKA 164B
Placing
The extension module can be placed at a distance of up to 15 m
from the controller module.
Point
No point has to be defined for a display module – you simply
connect it.
2.3.9 Graphic display MMIGRS2
Function
Setting and display of values in the controller.
Connection
The display connects to the controller via a cable with RJ11 plug
connections.
Supply voltage
Received from the controller via cable and RJ11 connector.
Do not connect a seperate power supply for this display.
Termination
The display must be terminated. Mount a connection between the
terminals H and R.
(AK-PC 782A is terminated internally.)
Placing
The display can be placed at a distance of up to 3 m from the
controller.
Point / Address
No point has to be defined for a display – you simply connect it.
However, the address must be verified. See the instructions
accompanying the controller.
The module is a new communication module, meaning the row of
extension modules can be interrupted.
The module communicates with the regulator via data
communication and forwards information between the controller
and the connected extension modules.
Connection
Communication module and controller fitted with RJ 45 plug
connectors.
Nothing else should be connected to this data communication; a
maximum of 5 communication modules can be connected to one
controller.
Communication cable
One metre of the following is enclosed:
ANSI/TIA 568 B/C CAT5 UTP cable w/ RJ45 connectors.
Positioning
Max. 30 m from the controller
(The total length of the communication cables is 30 m)
Supply voltage
24 volt AC or DC should be connected to the communication
module.
The 24 V can be sourced from the same supply that supplies
the controller. (The supply for the communication module is
galvanically separated from the connected extension modules).
The terminals must not be earthed.
The power consumption is determined by the power consumption
of the total number of modules.
The controller strand load must not exceed 32 VA.
Each AK-CM 102 strand load must not exceed 20 VA.
Max. 32 VA
Max. 20 VA
Max. 20 VA
Point
Connection points on the I/O modules should be defined as if the
modules were an extension of each other.
Address
The address for the first communication module should be set
to 1. Any second module should be set to 2. A maximum of 5
modules can be addressed.
Termination
The termination switch on the final communication module
should be set to ON.
The controller should permanently be set to = ON.
Warning!
Additional modules may only be installed following the
installation of the final module. (Here following module no. 11;
see the sketch.)
After configuration, the address must not be changed.
Be aware of the following when the number of extension modules
is being planned. A signal may have to be changed, so that an
additional module may be avoided.
• An ON/OFF signal can be received in two ways. Either as a
contact signal on an analogue input or as voltage on a low or
high-voltage module.
• An ON/OFF output signal can be given in two ways. Either with
a relay switch or with solid state. The primary difference is the
permitted load and that the relay switch contains a cut-out
switch.
Functions
Clock function
Clock function and change-over between summer time and
winter time are contained in the controller.
The clock setting is maintained for at least 12 hours at a power
failure.
The clock setting is kept updated if the controller is linked up in a
network with a system manager.
Start/stop of regulation
Regulation can be started and stopped via the software. External
start/stop can also be connected.
Warning!
The function stops all regulation, including any high-pressure
regulation.
Excess pressure can lead to a loss of charge.
Mentioned below are a number of functions and connections
that may have to be considered when a regulation has to be
planned. There are more functions in the controller than the ones
mentioned here, but those mentioned have been included in
order for the need for connections to be established.
I'm alive function
A relay can be reserved which is pulled during normal regulation.
The relay will be released if the regulation stops with the main
switch or if the controller fails.
Extra temperature sensors and pressure sensors
If additional measurements have to be carried out beyond the
regulation, sensors can be connected to the analogue inputs.
Forced control
The software contains a forced control option. If an extension
module with relay outputs is used, the module’s top part can
be with change-over switches – switches that can override the
individual relays into either OFF or ON position.
Wiring should be done with a safety relay. See Regulating
functions.
Start/stop of compressors
External start/stop can be connected.
Alarm function
If the alarm is to be sent to a signal transmitter, a relay output will
have to be used.
Data communication
The controller module has terminals for LON data communication.
The requirements to the installation are described in a separate
document.
In principle there are the following types of connections:
Analogue inputs ”AI”
This signal must be connected to two
terminals.
Signals can be received from the following
sources:
• Temperature signal from Pt 1000 ohm
temperature sensor
• Pulse signal or reset signal
• Contact signal where the input is shortcircuited or ”opened”, respectively
• Voltage signal from 0 to 10 V
• Signal from pressure transmitter AKS 32,
AKS 32R, AKS 2050 or MBS 8250.
• The supply voltage is supplied from the
module’s terminal board where there
is both a 5 V supply and a 12 V supply.
When programming, the pressure
transmitter’s pressure range must be set.
ON/OFF voltage inputs ”DI”
This signal must be connected to two
terminals.
• The signal must have two levels, either
0 V or ”voltage” on the input. There are
two different extension modules for this
signal type:
– low-voltage signals, e.g. 24 V
– high-voltage signals, e.g. 230 V
When programming, the function must be set:
• Active when the input is without voltage
• Active when voltage is applied to the input.
ON/OFF output signals ”DO”
There are two types, as follows:
• Relay outputs
All relay outputs are with change-over
relay so that the required function can be
obtained when the controller is without
voltage.
• Solid state outputs
Reserved for ejector valves, oil valves
and AKV valves, but output can cut an
external relay in and out, as with a relay
output.
The output is only found on the
controller module.
When programming, the function must be set:
• Active when the output is activated
• Active when the output is not activated.
Analogue output signal ”AO”
This signal is to be used if a control signal is
to be transmitted to an external unit, e.g. a
frequency converter.
When programming, the signal range must
be defined: 0-5 V, 1-5 V, 0-10 V or 2-10 V.
Pulse signal for the stepper motors.
This signal is used by valve motors of the
type ETS, KVS, CCM and CCMT.
The valve type should be set during
programming.
Limitations
As the system is very flexible regarding the number of connected
units, you must check whether your selection complies with the
few limitations there are.
The complexity of the controller is determined by the software,
the size of the processor, and the size of the memory. It provides
the controller with a certain number of connections from which
data can be downloaded, and others where coupling with relays
can be performed.
The sum of connections cannot exceed 220 (AK-PC 782A).
The number of extension modules must be limited so that
the total power in a row will not exceed 32 VA (including
controller). If the AK-CM 102 communication module is used,
each row of AK-CM 102 must not exceed 20 VA (incl. AK-CM
102). There must not be more than a total of 18 modules
(controller + 17 modules).
No more than 5 pressure transmitters may be connected to one
controller module.
No more than 5 pressure transmitters may be connected to one
If several controllers receive a signal from the same pressure
transmitter, the supply to the affected controllers must be wired so
that it is not possible to switch off one of the controllers without
also switching off the others. (If one controller is switched off, the
signal will be pulled down, and all the other controllers will receive
a signal which is too low).
Ejector valves
If ejector valves are used, the smallest ones must be connected to
the solid state outputs.
Loading...
+ 116 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.