Danfoss AK-PC 781 User guide

Design Guide
Capacity controller with heat recovery function
AK-PC 781
ADAP-KOOL® Refrigeration control systems
Contents
1. Introduction ............................................................................. 3
2. Design of a controller ..............................................................7
Common data for modules .................................................................10
Controller ...........................................................................................12
Extension module AK-XM 101A .................................................14
Extension module AK-XM 102A / AK-XM 102B .....................16
Extension module AK-XM 103A .................................................18
Extension module AK-XM 204A / AK-XM 204B .....................20
Extension module AK-XM 205A / AK-XM 205B .....................22
Extension module AK-XM 208C ................................................24
Extension module AK-OB 110 ....................................................26
Extension module AK-OB 101A..................................................27
Extension module EKA 163B / EKA 164B / EKA 166 ............ 28
Graphic display AK-MMI ...............................................................28
Power supply module AK-PS 075 / 150 / 250 ........................29
Communication module AK-CM 102 .......................................30
Preface to design ....................................................................................32
Functions ............................................................................................32
Connections ...................................................................................... 33
Limitations ......................................................................................... 33
Design of a compressor and condenser control .........................34
Procedure: ..........................................................................................34
Sketch .................................................................................................. 34
Compressor and condenser functions ....................................34
Connections ...................................................................................... 35
Planning table .................................................................................. 37
Length .................................................................................................38
Linking of modules ......................................................................... 38
Determine the connection points ............................................39
Connection diagram ...................................................................... 40
Supply voltage ................................................................................ 42
Ordering ..................................................................................................... 43
3. Mounting and wiring .............................................................45
Mounting ................................................................................................... 46
Mounting of analog output module ........................................ 46
Mounting of extension module on the basic module ....... 47
Wiring .......................................................................................................... 48
4. Conguration and operation ................................................51
Conguration ...........................................................................................52
Connect PC ........................................................................................ 52
Authorization .................................................................................... 54
Unlock the conguration of the controllers ..........................55
System setup ....................................................................................56
Set plant type ................................................................................... 57
Set control of compressors ..........................................................58
Set oil management ....................................................................... 61
Setup control of condenser fans ...............................................63
Setup control of high pressure ...................................................65
Setup control of receiver pressure ............................................66
Setup control of heat recovery..................................................67
Setup Display .................................................................................... 70
Setup Functions for General purpose ......................................71
Separate thermostats ............................................................. 72
Separate pressostats ..............................................................72
Separate voltage signals .......................................................73
Separate alarm inputs ............................................................ 73
Separate PI functions ............................................................. 74
Conguration of inputs and outputs .......................................75
Set alarm priorities..........................................................................77
Lock conguration ..........................................................................79
Check conguration .......................................................................80
Check of connections ............................................................................ 82
Check of settings.....................................................................................84
Schedule function .................................................................................. 86
Installation in network .......................................................................... 87
First start of control ................................................................................88
Start the control ............................................................................... 89
Manual capacity control ............................................................... 90
5. Regulating functions .............................................................91
Suction group ..........................................................................................92
Controlling sensor selection .......................................................92
Reference ...........................................................................................93
Capacity control of compressors ...............................................94
Capacity distribution methods ........................................... 96
Power pack types – compressor combinations ............97
Compressor timers ................................................................101
The capacity from the digital scroll compressor ........101
Load shedding ........................................................................102
Cascade systems – coordination and injection ..........103
Injection ON ............................................................................105
Liquid injection in suction line .........................................106
Safety functions .............................................................................106
Oil management............................................................................108
Condenser ...............................................................................................110
Capacity control of condenser .................................................110
Reference for condensing pressure ........................................110
Capacity distribution ...................................................................112
Step regulation ......................................................................................112
Speed regulation ..................................................................................112
Condenser couplings ...................................................................113
Safety functions for condenser ................................................113
EC motor ...........................................................................................113
CO2 transcritical system and heat recovery ........................114
Circuit for heat recovery or hot tap water ....................115
Circuit for recovery for heating .........................................116
Circuits for control of CO2 gas pressure ........................119
Receiver control .....................................................................121
Parallel compression ............................................................122
General monitoring functions .........................................................124
Miscellaneous ........................................................................................126
Appendix A – Compressor combinations and coupling pat-
terns ...........................................................................................................130
Appendix B - Alarm texts ...................................................................136
Appendix C - Recommended connection - AK-PC 781 ...........138
2 Capacity controller RS8GG602 © Danfoss 2015-03 AK-PC 781
Application
1. Introduction
SW = 4.5x
AK-PC 781 is complete regulating units for capacity control of compressors and condensers in refrigeration systems. The con­troller is with oil management, heat recovery function and CO2 gas pressure control. In addition to capacity control the controllers can give signals to other controllers about the operating condition, e.g. forced clos­ing of expansion valves, alarm signals and alarm messages.
The controller’s main function is to control compressors and condensers so that operation all the time takes place at the energy-optimum pressure conditions. Both suction pressure and condensing pressure are controlled by signals from pressure transmitters. Capacity control can be carried out by suction pressure P0, media temperature S4 or separate control pressure Pctrl (for cascade).
Among the dierent functions are:
- Capacity control of up to 8 compressors
- Up to 3 unloaders for each compressor
- Oil management. Either shared or individual for all of the com­pressor's oil valves. Receiver pressure control.
- Speed control of one or two compressors
- Up to 6 safety inputs for each compressor
- Option for capacity limitation to minimize consumption peaks
- When the compressor does not start, signals can be transmitted to other controllers so that the electronic expansion valves will be closed
- Regulation of liquid injection into suction line
- Start/stop of liquid injection in heat exchanger (cascade)
- MT/LT - coordination between controllers in cascade control
- Safety monitoring of high pressure / low pressure / discharge temperature
- Capacity control of up to 8 fans
- Floating reference with regard to outside temperature
- Heat recovery function
- CO2 gas cooler control and receiver control
- Parallel compression on transcritical CO2 system
- Step coupling, speed regulation or a combination
- Safety monitoring of fans
- The status of the outputs and inputs is shown by means of light­emitting diodes on the front panel
- Alarm signals can be generated via data communication
- Alarms are shown with texts so that the cause of the alarm is easy to see.
- Plus some completely separate functions that are totally inde­pendent of the regulation – such as alarm, thermostat ,pressure and PI-regulating functions.
Examples
Traditional capacity control
Booster control with 2 controls
(For pure booster control without MT cooling, the intermediate pressure must be connected to the receiver to prevent Pmin and Pmax cut-outs during the start-up).
Heat recovery functions, controlling the condensing pressure and receiver pressure of a CO2 plant
AK-PC 781 Capacity controller RS8GG602 © Danfoss 2015-03 3
Principles
The great advantage of this series of controllers is that it can be extended as the size of the plant is increased. It has been devel­oped for refrigeration control systems, but not for any specic application – variation is created through the read-in software and the way you choose to dene the connections. It is the same modules that are used for each regulation and the composition can be changed, as required. With these modules (building blocks) it is possible to create a multitude of various kinds of regulations. But it is you who must help adjusting the regulation to the actual needs – these instructions will assist you to nd your way through all the questions so that the regulation can be dened and the connections made.
Controller
Top part
Advantages
• The controller’s size can “grow” as systems grow
• The software can be set for one or more regulations
• Several regulations with the same components
• Extension-friendly when systems requirements are changed
• Flexible concept:
- Controller series with common construction
- One principle – many regulation uses
- modules are selected for the actual connection requirements
- The same modules are used from regulation to regulation
Extension modules
Bottom part
The controller is the cornerstone of the regulation. The module has inputs and outputs capable of handling small systems.
• The bottom part – and hence the terminals – are the same for all controller types.
• The top part contains the intelligence with software. This unit will vary according to controller type. But it will always be supplied together with the bottom part.
• In addition to the software the top part is provided with connections for data communication and address setting.
Examples
A regulation with few connections can be performed with the controller module alone
If the system grows and more functions have to be controlled, the regulation can be extended. With extra modules more signals can be received and more relays cut in and out – how many of them – and which – is determined by the relevant application.
If there are many connections one or more exten­sion modules have to be mounted
4 Capacity controller RS8GG602 © Danfoss 2015-03 AK-PC 781
Direct connection
Setup and operation of an AK controller must be accomplished via the “AK-Service Tool” software program.
The program is installed on a PC, and setup and operation of the various functions are carried out via the controller’s menu displays.
Displays
The menu displays are dynamic, so that dierent settings in one menu will result in dierent setting possibilities in other menus.
A simple application with few connections will give a setup with few settings. A corresponding application with many connections will give a setup with many settings. From the overview display there is access to further displays for the compressor regulation and the condenser regulation. At the bottom of the display there is access to a number of general functions, such as “time table”, “manual operation”, “log function”, “alarms”, and “service” (conguration).
Network linking
The controller can be linked up into a network together with other controllers in an ADAP-KOOL® refrigeration control system. After the setup operation can be performed at a distance with, say, our software program type AKM.
Users
The controller comes supplied with several languages, one of which can be selected and employed by the user. If there are sev­eral users, they may each have their choice of language. All users must be assigned a user prole which either gives access to full operation or gradually limits the operation to the lowest level that only allows you “to see”. Language selection is part of the service tool settings. If the language selection is not available in the service tool for the current regulator, English texts will be displayed.
External display
An external display can be tted in order for P0 (Suction) and Pc (Condensing) readings to be displayed. A total of 4 displays can be tted and with one setting it is pos­sible to choose between the following readings: suction pressure, suction pressure in temperature, Pctrl, S4, Ss, Sd, condenser pres­sure, condenser pressure in temperature, S7 gas cooler tempera­ture, hot tap water at heat recovery and heat exchanger tempera­ture at heat recovery. A graphical display with control buttons can also be tted.
AK-PC 781 Capacity controller RS8GG602 © Danfoss 2015-03 5
Light-emitting diodes
A number of light-emitting diodes makes it possible to follow the signals that are received and transmitted by the controller.
Log
From the log function you can dene the measurements you wish to be shown. The collected values can be printed, or you may export them to a le. You can open the le in Excel.
If you are in a service situation you can show measurements in a trend function. The measurements are then made real-time and displayed instantly.
Power
Comm
DO1 Status
DO2 Service Tool
DO3 LON
DO4 I/O Extension
DO5 Alarm
DO6
DO7
DO8 Service Pin
Slow ash = OK Quick ash = answer from gateway Constantly ON = error Constantly OFF = error
Flash = active alarm/not cancelled Constant ON = Active alarm/cancelled
Alarm
The display gives you an overview of all active alarms. If you wish to conrm that you have seen the alarm you can cross it o in the acknowledge eld. If you want to know more about a current alarm you can click on it and obtain an information display on the screen.
A corresponding display exists for all earlier alarms. Here you can upload information if you need further details about the alarm history.
Trouble-shooting
The controller contains a function that continuously follows a number of measurements and deals with them. The result indicates whether the function is OK or whether an error may be expected within a given period of time (“the trip down the roller coaster has started”). At this time an alarm is transmitted about the situation – no error has appeared as yet, but it will come. One example may be slow clogging-up of a condenser. When the alarm comes the capacity has been reduced, but the situation is not serious. There will be time to plan a service call.
Alarm
Error
6 Capacity controller RS8GG602 © Danfoss 2015-03 AK-PC 781
2. Design of a controller
This section describes how the controller is designed.
The controller in the system is based on a uniform connection platform where any deviations from regulation to regulation is determined by the used top part with a specic software and by which input and output signals the relevant application will require. If it is an application with few connections, the controller module (top part with belonging bottom part) may be sucient. If it is an application with many connections it will be necessary to use the controller module plus one or more extension modules.
This section will give you a survey of possible connections plus assistance in selecting the modules required by your actual ap-
plication.
AK-PC 781 Capacity controller RS8GG602 © Danfoss 2015-03 7
Module survey
• Controller module – capable of handling minor plant require­ments.
• Extension modules. When the complexity becomes greater and additional inputs or outputs are required, modules can be attached to the controller. A plug on the side of the module will transmit the supply voltage and data communication between the modules.
• Top part The upper part of the controller module contains the intelli­gence. This is the unit where the regulation is dened and where data communication is connected to other controllers in a big­ger network.
• Connection types There are various types of inputs and outputs. One type may, for example, receive signals from sensors and switches, another may receive a voltage signal, and a third type may be outputs with relays etc. The individual types are shown in the table below.
Extension module with ad­ditional analog inputs
• Optional connection When a regulation is planned (set up) it will generate a need for a number of connections distributed on the mentioned types. This connection must then be made on either the controller module or an extension module. The only thing to be observed is that the types must not be mixed (an analog input signal must for instance not be connected to a digital input).
• Programming of connections The controller must know where you connect the individual input and output signals. This takes place in a later congura­tion where each individual connection is dened based on the following principle:
- to which module
- at which point (”terminals”)
- what is connected (e.g. pressure transmitter/type/
pressure range)
Extension module with additional relay outputs and additional ana­log inputs.
External display for suction pressure etc.
Bottom part
Controller with analog inputs and relay outputs.
Top part
Extension module with 2x analog output signals
The module with additional relay outputs is also available in a version where the top part is provided with change-over switches so that the relays can be overridden.
If the row of modules needs to be interrupted due to length or external positioning, a communi­cation module should be used.
8 Capacity controller RS8GG602 © Danfoss 2015-03 AK-PC 781
1. Controller
Type Function Application
AK-PC 781
Controller for capacity control of compressors and condensers 8 compressors with up to 3 unloaders, 8 fans, max. 120 inputs/outputs
Compressor / Condenser / Both/ Oil management / Heat recovery / CO2 gas pressure
2. Extension modules and survey of inputs and outputs
Type Analog
inputs
For sensors, pres­sure transmitters etc.
Controller 11 4 4 - - - -
Extension modules
AK-XM 101A 8
AK-XM 102A 8
AK-XM 102B 8
AK-XM 103A 4 4
AK-XM 204A 8
AK-XM 204B 8 x
AK-XM 205A 8 8
AK-XM 205B 8 8 x
AK-XM 208C 8 4
On/O outputs On/o supply voltage
Relay (SPDT)
Solid state Low voltage
(DI signal)
(max. 80 V)
High voltage (max. 260 V)
Analog outputs
0-10 V d.c. For valves
Stepper output
with step control
Module with switches
For override of relay outputs
The following extension module can be placed on the PC board in the controller module. There is only room for one module.
AK-OB 110 2
3. AK operation and accessories
Type Function Application
Operation
AK-ST 500 Software for operation of AK controllers AK-operation
- Cable between PC and AK controller AK - Com port
-
- Cable between PC and AK controller AK - USB
Accessories Power supply module 230 V / 115 V to 24 V d.c.
AK-PS 075 18 VA
AK-PS 250 60 VA
Accessories External display that can be connected to the controller module. For showing, say, the suction pressure
EKA 163B Display
EKA 164B Display with operation buttons
EKA 166 Display with operation buttons and LED for function cut in
AK-MMI Graphic display with operation
-
Cable between zero modem cable and AK controller / Cable between PDA cable and AK controller
Cable between display and controller Length = 2 m, 6 m
Cable between graphic display and controller Length = 1.5 m, 3.0 m
AK - RS 232
Supply for controllerAK-PS 150 36 VA
Accessories Real time clock for use in controllers that require a clock function, but are not wired with data communication.
AK-OB 101A Real time clock with battery backup. To be mounted in an AK controller
Accessories Communication modules for controllers where modules cannot be connected continuously
AK-CM 102 Communication module
Data communication for external extension modules
On the following pages there is data specic to each module.
AK-PC 781 Capacity controller RS8GG602 © Danfoss 2015-03 9
Common data for modules
Supply voltage 24 V d.c./a.c. +/- 20%
Power consumption AK-__ (controller) 8 VA
AK-XM 101, 102, 103, 107, AK-CM 102 2 VA
AK-XM 204, 205, 208 5 VA
Analog inputs Pt 1000 ohm /0°C Resolution: 0.1°C
Pressure transmitter type AKS 32R / AKS 2050 AKS 32 (1-5 V)
Other pressure transmitter: Ratiometric signal Min. and Max. pressure must be set
Voltage signal 0-10 V
Contact function (On/O ) On at R < 20 ohm
On/o supply voltage inputs Low voltage
Relay outputs SPDT
0 / 80 V a.c./d.c.
High voltage 0 / 260 V a.c.
AC-1 (ohmic) 4 A
AC-15 (inductive) 3 A
U Min. 24 V
Accuracy: +/- 0.5°C
Resolution:1 mV Accuracy +/- 10 mV Max. connection of 5 pressure transmitters on one module
O at R > 2K ohm (Gold -plated contacts not necessary)
O: U < 2 V On: U > 10 V
O: U < 24 V On: U > 80 V
Max. 230 V Low and high voltage must not be connected to the same output group
Solid state outputs Can be used for loads that are cut in and
out frequently, e.g. : Oil valves, fans and AKV valves
Stepper outputs Used for valves with stepper input 20-500 step/s
Ambient temperature During transport -40 to 70°C
During operation -20 to 55°C ,
Enclosure Material PC / ABS
Density IP10 , VBG 4
Mounting For mounting on panel wall or DIN rail
Weight with screw terminals Modules in 100- / 200- / controller-series Ca. 200 g / 500 g / 600 g
Approvals EU low voltage directive and EMC require-
ments are complied with
UL 873,
The mentioned data applies to all modules. If data is specic, this is mentioned together with the module in question.
Max. 240 V a.c. , Min. 48 V a.c. Max. 0,5 A, Leak < 1 mA Max. 1 AKV
Separate supply to stepper outputs : 24 a.c./d.c. / 13 VA
0 to 95% RH (non condensing) No shock inuences / vibrations
LVD tested according to EN 60730 EMC tested Immunity according to EN 61000-6-2 Emission according to EN 61000-6-3
UL le number: E166834 for XM and CM-modules UL le number: E31024 for PC-modules
10 Capacity controller RS8GG602 © Danfoss 2015-03 AK-PC 781
Dimensions
The module dimension is 72 mm. Modules in the 100-series consist of one module Modules in the 200-series consist of two modules Controllers consist of three modules The length of an aggregate unit = n x 72 + 8
AK-PC 781 Capacity controller RS8GG602 © Danfoss 2015-03 11
Controller
Function
There are several controllers in the series. The function is deter­mined by the programmed software, but outwardly the control­lers are identical – they all have the same connection possibilities: 11 analog inputs for sensors, pressure transmitters, voltage signals
and contact signals.
8 digital outputs, with 4 Solid state outputs and 4 relay outputs
Supply voltage
24 V a.c. or d.c. to be connected to the controller. The 24 V must not be retransmitted and used by other control­lers as it is not galvanically separated from inputs and outputs. In other words, you must use a transformer for each controller. Class II is required. The terminals must not be earthed. The supply voltage to any extension modules is transmitted via the plug on the right-hand side. The size of the transformer is determined by the power require­ment of the total number of modules.
The supply voltage to a pressure transmitter can be taken either from the 5 V output or from the 12 V output depending on trans­mitter type.
PIN
Data communication
If the controller is to be included in a system, communication must take place via the LON connection. The installation has to be made as mentioned in the separate instructions for LON communication.
Address setting
When the controller is connected to a gateway type AKA 245, the controller’s address must be set between 1 and 119. (If it is a system manager AK-SM .., then 1-999).
Service PIN
When the controller is connected to the data communication cable the gateway must have knowledge of the new controller. This is obtained by pushing the key PIN. The LED “Status” will ash when the gateway sends an acceptance message.
Operation
The conguration operation of the controller must take place from the software program “Service Tool”. The program must be installed on a PC, and the PC must be connected to the controller via the network plug on the front of the unit.
Light-emitting diodes
There are two rows with LED’s. They mean: Left row:
• Voltage supply to the controller
• Communication active with the bottom PC board (red = error)
• Status of outputs DO1 to DO8
Right row:
• Software status (slow ash = OK)
• Communication with Service Tool
• Communication on LON
• Communication with AK-CM 102
• Alarm when LED ashes
- 2 LED’s that are not used
• “Service Pin” switch has been activated
Address
Power
Comm
DO1 Status
DO2 Service Tool
DO3 LON
DO4 I/O Extension
DO5 Alarm
DO6
DO7
DO8 Service Pin
Slow ash = OK Quick ash = answer from gateway Constantly ON = error Constantly OFF = error
Flash = active alarm/not cancelled Constant ON = Active alarm/cancelled
Keep the safety distance!
Low and high voltage must not be connected to the same output group
A small module (option board) can be placed on the bottom part of the controller. The module is described later in the document.
12 Capacity controller RS8GG602 © Danfoss 2015-03 AK-PC 781
Point
Point 1 2 3 4 5 6 7 8 9 10 11
Type AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8 AI9 AI10 AI11
Terminal 15: 12 V Terminal 16: 5 V
Terminal 27: 12 V Terminal 28: 5 V
Analog inputs on 1 - 11
Solid state outputs on 12 - 15
Relay or AKV coil fx 230 V a.c.
Signal Signal
S
S1 S2
Pt 1000 ohm/0°C
Saux_ SsA SdA Shr Stw Sgc
P
AKS 32R
3: Brown
2: Blue
1: Black
P0A P0B PcA PcB
AKS 32
3: Brown
2: Black
1: Red
Paux Pgc Prec
U
...
On/O Ext.
Main switch Day/ Night Door Level switch
DO
AKV
AKV
Comp 1 Comp 2 Fan 1 Alarm Light Rail heat Defrost Solenoid valve
Option Board
Please see the signal on the page with the module.
24 and 25 used only when "Op­tion board tted"
type
Pt 1000
AKS 32R / AKS 2050
-1 - xx bar
AKS 32
-1 - zz bar
0 - 5 V 0 - 10 V
Active at:
Closed
/
Open
Active at:
On
/
O
Point 12 13 14 15 16 17 18 19
Type DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8
Signal Module Point
1 (AI 1) 1 - 2
2 (AI 2) 3 - 4
3 (AI 3) 5 - 6
4 (AI 4) 7 - 8
5 (AI 5) 9 - 10
6 (AI 6) 11 - 12
7 (AI 7) 13 - 14
8 (AI 8) 19 - 20
9 (AI 9) 21 - 22
10 (AI 10) 23 - 24
11 (AI 11) 25 - 26
1
12 (DO 1) 31 - 32
13 (DO 2) 33 - 34
14 (DO 3) 35 - 36
15 (DO 4) 37 - 38
16 (DO 5) 39 - 40- 41
17 (DO6) 42 - 43 - 44
18 (DO7) 45 - 46 - 47
19 (DO8) 48 - 49 - 50
24 -
25 -
Terminal 17, 18, 29, 30: (Cable screen)
Relay outputs on 16 - 19
Terminal
Signal type /
Active at
AK-PC 781 Capacity controller RS8GG602 © Danfoss 2015-03 13
Extension module AK-XM 101A
Function
The module contains 8 analog inputs for sensors, pressure trans­mitters, voltage signals and contact signals.
Supply voltage
The supply voltage to the module comes from the previous mod­ule in the row.
Supply voltage to a pressure transmitter can be taken from either the 5 V output or the 12 V output depending on transmitter type.
Light-emitting diodes
Only the two top LED’s are used. They indicate the following:
• Voltage supply to the module
• Communication with the controller is active (red = error)
14 Capacity controller RS8GG602 © Danfoss 2015-03 AK-PC 781
Point
Point 1 2 3 4
Type AI1 AI2 AI3 AI4
Terminal 9: 12 V Terminal 10: 5 V
S
Pt 1000 ohm/0°C
P
AKS 32R
AKS 32
At the top the signal input is the left of the two terminals.
At the bottom the signal input is the right of the two terminals.
3: Brown
2: Blue
1: Black
3: Brown
2: Black
1: Red
Signal Signal
type
S1 S2 Saux SsA
Pt 1000
SdA Shr Stw Sgc
P0A P0B PcA PcB Paux Pgc Prec
AKS 32R / AKS 2050
-1 - xx bar
AKS 32
-1 - zz bar
Terminal 15: 5 V Terminal 16: 12 V
Terminal
11, 12, 13, 14:
(Cable screen)
Point 5 6 7 8
Type AI5 AI6 AI7 AI8
U
On/O
...
Ext. Main switch Day/ Night Door Level switch
0 - 5 V 0 - 10 V
Active at:
Closed
/
Open
Signal Module Point
1 (AI 1) 1 - 2
2 (AI 2) 3 - 4
3 (AI 3) 5 - 6
4 (AI 4) 7 - 8
5 (AI 5) 17 - 18
6 (AI 6) 19 - 20
7 (AI 7) 21 - 22
8 (AI 8) 23 - 24
Terminal
Signal type /
Active at
AK-PC 781 Capacity controller RS8GG602 © Danfoss 2015-03 15
Extension module AK-XM 102A / AK-XM 102B
Function
The module contains 8 inputs for on/o voltage signals.
Signal
AK-XM 102A is for low voltage signals. AK-XM 102B is for high voltage signals.
Supply voltage
The supply voltage to the module comes from the previous module in the row.
Light-emitting diodes
They indicate:
• Voltage supply to the module
• Communication with the controller is active (red = error)
• Status of the individual inputs 1 to 8 (when lit = voltage)
AK-XM 102A
Max. 24 V
On/O: On: DI > 10 V a.c. O: DI < 2 V a.c.
AK-XM 102B
Max. 230 V
On/O: On: DI > 80 V a.c. O: DI < 24 V a.c.
16 Capacity controller RS8GG602 © Danfoss 2015-03 AK-PC 781
Point
DI
AK-XM 102A: Max. 24 V AK-XM 102B: Max. 230 V
Signal Active at
Ext. Main switch
Day/ Night
Comp. safety 1
Comp. safety 2
Level switch
Closed
(voltage on)
/
Open
(voltage o)
Point 1 2 3 4
Type DI1 DI2 DI3 DI4
Point 5 6 7 8
Type DI5 DI6 DI7 DI8
Signal Module Point Terminal Active at
1 (DI 1) 1 - 2
2 (DI 2) 3 - 4
3 (DI 3) 5 - 6
4 (DI 4) 7 - 8
5 (DI 5) 9 - 10
6 (DI 6) 11 - 12
7 (DI 7) 13 - 14
8 (DI 8) 15 - 16
AK-PC 781 Capacity controller RS8GG602 © Danfoss 2015-03 17
Extension module AK-XM 103A
Function
The module contains : 4 analog inputs for sensors, pressure transmitters, voltage signals and contact signals. 4 analog voltage outputs of 0 - 10 V
Supply voltage
The supply voltage to the module comes from the previous module in the row.
Supply voltage to a pressure transmitter can be taken from either the 5 V output or the 12 V output depending on transmitter type.
Galvanic isolation
The inputs are galvanically separated from the outlets. The outlets AO1 and AO2 are galvanically separated from AO3 and AO4.
Light-emitting diodes
Only the two top LED’s are used. They indicate the following:
• Voltage supply to the module
• Communication with the controller is active (red = error)
18 Capacity controller RS8GG602 © Danfoss 2015-03 AK-PC 781
Point
Point 1 2 3 4
Type AI1 AI2 AI3 AI4
Terminal 9: 12 V Terminal 10: 5 V
S
Pt 1000 ohm/0°C
P
AKS 32R
AKS 32
At the top the signal input is the left of the two terminals.
At the bottom the signal input is the right of the two terminals.
3: Brown
2: Blue
1: Black
3: Brown
2: Black
1: Red
Signal Signal
type
S1 S2 Saux SsA
Pt 1000
SdA Shr Stw Sgc
P0A P0B PcA
AKS 32R / AKS 2050
-1 - xx bar PcB Paux Pgc
AKS 32
-1 - zz bar Prec
Terminal 11, 12: (Cable screen)
Galvanic isolation: AI 1-4 ≠ AO 1-2 ≠ AO 3-4
Point 5 6 7 8
Type AO1 AO2 AO3 AO4
U
...
On/O Ext.
Main switch Day/ Night
Door Level switch
AO
0 - 5 V 0 - 10 V
Active at:
Closed
/
Open
0-10 V
Signal Module Point Terminal Signal type /Active at
1 (AI 1) 1 - 2
2 (AI 2) 3 - 4
3 (AI 3) 5 - 6
4 (AI 4) 7 - 8
5 (AO 1) 17 - 18
6 (AO 2) 19 - 20
7 (AO 3) 21 - 22
8 (AO 4) 23 - 24
AK-PC 781 Capacity controller RS8GG602 © Danfoss 2015-03 19
Extension module AK-XM 204A / AK-XM 204B
Function
The module contains 8 relay outputs.
Supply voltage
The supply voltage to the module comes from the previous mod­ule in the row.
AK-XM 204B only Override of relay
Eight change-over switches at the front make it possible to over­ride the relay’s function. Either to position OFF or ON. In position Auto the controller carries out the control.
Light-emitting diodes
There are two rows with LED’s. They mean: Left row:
• Voltage supply to the controller
• Communication active with the bottom PC board (red = error)
• Status of outputs DO1 to DO8
Right row: (AK-XM 204B only):
• Override of relays ON = override OFF = no override
Fuses
Behind the upper part there is a fuse for each output.
AK-XM 204A AK-XM 204B
Max. 230 V
AC-1: max. 4 A (ohmic) AC-15: max. 3 A (Inductive)
Keep the safety distance!
Low and high voltage must not be connected to the same output group
AK-XM 204B Override of relay
Note
If the changeovers are used to override the compressor operation, it is necessary to wire a safety relay into the circuit for oil manage­ment. Without this safety relay, the controller will fail to stop the compressor if it should run out of oil. See Regulating functions.
20 Capacity controller RS8GG602 © Danfoss 2015-03 AK-PC 781
Point
DO
Signal Active at
Comp. 1
Comp. 2
Fan 1
Alarm
Solenoid valve
On
/
O
Point 1 2 3 4 5 6 7 8
Type DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8
Signal Module Point Terminal Active at
1 (DO 1) 25 - 27
2 (DO 2) 28 - 30
3 (DO 3) 31 - 33
4 (DO 4) 34 -36
5 (DO 5) 37 - 39
6 (DO 6) 40 - 41 - 42
7 (DO 7) 43 - 44 - 45
8 (DO 8) 46 - 47 - 48
AK-PC 781 Capacity controller RS8GG602 © Danfoss 2015-03 21
Extension module AK-XM 205A / AK-XM 205B
Function
The module contains: 8 analog inputs for sensors, pressure transmitters, voltage signals
and contact signals.
8 relay outputs.
Supply voltage
The supply voltage to the module comes from the previous mod­ule in the row.
AK-XM 205B only Override of relay
Eight change-over switches at the front make it possible to over­ride the relay’s function. Either to position OFF or ON. In position Auto the controller carries out the control.
Light-emitting diodes
There are two rows with LED’s. They mean: Left row:
• Voltage supply to the controller
• Communication active with the bottom PC board (red = error)
• Status of outputs DO1 to DO8
Right row: (AK-XM 205B only):
• Override of relays ON = override OFF = no override
AK-XM 205A AK-XM 205B
max. 10 V
Fuses
Behind the upper part there is a fuse for each output.
Note
If the changeovers are used to override the compressor operation, it is necessary to wire a safety relay into the circuit for oil manage­ment. Without this safety relay, the controller will fail to stop the compressor if it should run out of oil. See Regulating functions.
Max. 230 V
AC-1: max. 4 A (ohmic) AC-15: max. 3 A (Inductive)
AK-XM 205B Override of relay
Keep the safety distance!
Low and high voltage must not be connected to the same output group
22 Capacity controller RS8GG602 © Danfoss 2015-03 AK-PC 781
Point
S
Pt 1000 ohm/0°C
P
AKS 32R
AKS 32
U
On/O
DO
3: Brown
2: Blue
1: Black
3: Brown
2: Black
1: Red
Signal Signal
type
S1 S2 Saux SsA
Pt 1000
SdA Shr Stw Sgc
P0A P0B PcA PcB Paux Pgc
AKS 32R / AKS 2050
-1 - xx bar
AKS 32
-1 - zz bar
Prec
0 - 5 V
...
Ext. Main switch Day/ Night Door
0 - 10 V
Active at:
Closed
Open
Level switch
Comp 1
Active at:
Comp 2 Fan 1
on Alarm Light Rail heat
O
Defrost Solenoid valve
Point 1 2 3 4 5 6 7 8
Type AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8
Point 9 10 11 12 13 14 15 16
Type DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8
Signal Module Point
/
/
Terminal 9: 12 V Terminal 10: 5 V
Terminal 21: 12 V Terminal 22: 5 V
Terminal 11, 12, 23, 24 :
(Cable screen)
Terminal
1 (AI 1) 1 - 2
2 (AI 2) 3 - 4
3 (AI 3) 5 - 6
4 (AI 4) 7 - 8
5 (AI 5) 13 - 14
6 (AI 6) 15 - 16
7 (AI 7) 17 - 18
8 (AI 8) 19 -20
9 (DO 1) 25 - 26 - 27
10 (DO 2) 28 - 29 - 30
11 (DO 3) 31 - 30 - 33
12 (DO 4) 34 - 35 - 36
13 (DO 5) 37 - 36 - 39
14 (DO6) 40 - 41 - 42
15 (DO7) 43 - 44 - 45
16 (DO8) 46 - 47 - 48
Signal type /
Active at
AK-PC 781 Capacity controller RS8GG602 © Danfoss 2015-03 23
Extension module AK-XM 208C
Function
The module contains: 8 analog inputs for sensors, pressure transmitters, voltage signals
and contact signals.
4 outputs for stepper motors.
Supply voltage
The supply voltage to the module comes from the previous mod­ule in the row. The supply voltage to the valves must be from a separate supply, which must be galvanically separated from the supply for the control range. 24 V d.c. +/-20%. (Power requirements: 7.8 VA for controller + 1.3 VA per valve).
A UPS may be necessary if the valves need to open/close during a power failure.
Light-emitting diodes
There is one row with LED’s. It indicate the following:
• Voltage supply to the module
• Communication active with the bottom PC board (red = error)
• Status of outputs step1 to step4
Separate voltage supply is required 24 V d.c. 13 VA
max. 10 V
Output:
24 V d.c.
I
= 500 m A / coil
max.
20-500 step/s
24 Capacity controller RS8GG602 © Danfoss 2015-03 AK-PC 781
Point
CCM
Step / Terminal
ETS
CCM / CCMT
KVS 15
KVS 42-54
Point 1 2 3 4 5 6 7 8
Type AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8
Terminal 17: 12 V Terminal 18: 5 V
Terminal 19, 20: (Cable screen)
Point 9 10 11 12
Step 1 2 3 4
Type AO
1 25 26 27 28
2 29 30 31 32
3 33 34 35 36
4 37 38 39 40
White Black Red Green
White Black Green Red
Valve Module Step Terminal
1 (point 9) 25 - 28
2 (point 10) 29 - 32
3 (point 11) 33 - 36
4 (point 12) 37 - 40
AK-PC 781 Capacity controller RS8GG602 © Danfoss 2015-03 25
Extension module AK-OB 110
Function
The module contains two analog voltage outputs of 0 – 10 V.
Supply voltage
The supply voltage to the module comes from the controller module.
Placing
The module is placed on the PC board in the controller module.
Point
The two outputs have points 24 and 25. They are shown on the earlier page where the controller is also mentioned.
Max. load I < 2.5 mA R > 4 kohm
AO
AO 0 - 10 V
Module
Point 24 25
Type AO1 AO2
1
AO2
AO1
26 Capacity controller RS8GG602 © Danfoss 2015-03 AK-PC 781
Extension module AK-OB 101A
Function
The module is a real time clock module with battery backup.
The module can be used in controllers that are not linked up in a data communication unit together with other controllers. The module is used here if the controller needs battery backup for the following functions
• Clock function
• Fixed times for day/night change-over
• Fixed defrost times
• Saving of alarm log in case of power failure
• Saving of temperature log in case of power failure
Connection
The module is provided with plug connection.
Placing
The module is placed on the PC board inside the top part.
Point
No point for a clock module to be dened – just connect it.
Working life of the battery
The working life of the battery is several years – even if there are frequent power failures. An alarm is generated when the battery has to be replaced. After the alarm there are still several months of operating hours left in the battery.
AK-PC 781 Capacity controller RS8GG602 © Danfoss 2015-03 27
Extension module EKA 163B / EKA 164B / EKA 166
Function
Display of important measurements from the controller, e.g. ap-
pliance temperature, suction pressure or condensing pressure.
Setting of the individual functions can be performed by using the display with control buttons. It is the controller used that determines the measurements and settings that can occur.
Connection
The extension module is connected to the controller module via a cable with plug connections. You have to use one cable per module. The cable is supplied in various lengths.
Both types of display (with or without control buttons) can be
connected to either display output A, B, C and D. Ex. A: P0. Suction pressure in °C. B: Pc. Condensing pressure in °C.
When the controller starts up, the display will show the output that is connected.
- - 1 = output A
- - 2 = output B etc.
EKA 163B EKA 164B
Placing
The extension module can be placed at a distance of up to 15 m from the controller module.
Point
No point has to be dened for a display module – you simply con­nect it.
Graphic display AK-MMI
Function
Setting and display of values in the controller.
Connection
The display connects to the controller via a cable with plug con­nections. Use plug RJ45 to connect to the controller; the same plug is also used for service tool AK-ST 500.
Supply voltage
24 V a.c. / d.c. 1.5 VA.
Placing
The display can be placed at a distance of up to 3 m from the controller.
EKA 166
Point
No point has to be dened for a display – you simply connect it.
28 Capacity controller RS8GG602 © Danfoss 2015-03 AK-PC 781
Power supply module AK-PS 075 / 150 / 250
Function
24 V supply for controller.
Supply voltage
230 V a.c or 115 V a.c. (from 100 V a.c. to 240 V a.c.)
Placing
On DIN-rail
Eect
Type Output tension Output current Power
AK-PS 075 24 V d.c. 0.75 A 18 VA
AK-PS 150 24 V d.c. (adjustable) 1.5 A 36 VA
AK-PS 250 24 V d.c. (adjustable) 2.5 A 60 VA
Dimension
Type High Width
AK-PS 075 90 mm 36 mm
AK-PS 150 90 mm 54 mm
AK-PS 250 90 mm 72 mm
Connections
Supply to a controller
AK-PS 075
AK-PS 150
AK-PS 250
AK-PC 781 Capacity controller RS8GG602 © Danfoss 2015-03 29
Communication module AK-CM 102
Function
The module is a new communication module, meaning the row of extension modules can be interrupted. The module communicates with the regulator via data communi­cation and forwards information between the controller and the connected extension modules.
Connection
Communication module and controller tted with RJ 45 plug con­nectors. Nothing else should be connected to this data communication; a maximum of 5 communication modules can be connected to one controller. The communication module can be used only with controllers of the type AK-PC 781.
Communication cable
One metre of the following is enclosed: ANSI/TIA 568 B/C CAT5 UTP cable w/ RJ45 connectors.
Positioning
Max. 30 m from the controller (The total length of the communication cables is 30 m)
Max. 32 VA
Supply voltage
24 volt AC or DC should be connected to the communication module. The 24 V can be sourced from the same supply that supplies the controller. (The supply for the communication module is galvani­cally separated from the connected extension modules). The terminals must not be earthed. The power consumption is determined by the power consump­tion of the total number of modules. The controller strand load must not exceed 32 VA. Each AK-CM 102 strand load must not exceed 20 VA.
Point
Connection points on the I/O modules should be dened as if the modules were an extension of each other.
Address
The address for the rst communication module should be set to
1. Any second module should be set to 2. A maximum of 5 mod­ules can be addressed.
Termination
The termination switch on the nal communication module should be set to ON. The controller should permanently be set to = ON.
Warning
Additional modules may only be installed following the installa­tion of the nal module. (Here following module no. 11; see the sketch.) After conguration, the address must not be changed.
Max. 20 VA
Max. 20 VA
30 Capacity controller RS8GG602 © Danfoss 2015-03 AK-PC 781
Loading...
+ 112 hidden pages