Danfoss AK-PC 710 User guide [fr]

Page 1
Design Guide
Régulation de capacité
AK-PC 710
ADAP-KOOL® Refrigeration control systems
Page 2
Sommaire
1. Introduction ............................................................................. 3
Utilisation..................................................................................................... 3
2. Conception d'un régulateur ....................................................7
Sommaire des Modules .......................................................................... 8
Données communes aux Modules ................................................... 10
Régulateur ......................................................................................... 12
Modules d'extension AK-XM 102A / AK-XM 102B ............... 14
Modules d'extension AK-XM 204A / AK-XM 204B ............... 16
Module d'extension AK-OB 110 ................................................. 18
Module d'extension AK-OB 101A .............................................. 19
Modules d'achage EKA 163B / EKA 164B / EKA 166 ........20
Module alimentation AK-PS 075 ................................................21
Sélectionner l'application .................................................................... 22
Généralités ......................................................................................... 22
Application ........................................................................................ 22
Sommaire des modules ........................................................................ 33
3. Montage et câblage ...............................................................35
Montage ..................................................................................................... 36
Montage d’un module sortie analogique .............................. 36
Montage d'un module E/S sur le module de base .............. 37
Câblage.......................................................................................................38
4. Conguration et opération ...................................................39
Conguration via service tool AK-ST 500 .......................................41
Raccordement du PC ou du PDA ...............................................41
Authorization .................................................................................... 42
Déblocage de la conguration du régulateur ......................43
Réglage système .............................................................................44
Régler le type d'installation ......................................................... 45
Modication de la régulation de fonction d'aspiration ....46
Réglage de la régulation des condenseurs ............................49
Conguration des entrées et des sorties ................................ 50
Réglage des priorités d'alarmes ................................................. 52
Blocage de la conguration ........................................................54
Contrôle de la conguration .......................................................55
Contrôle des connexions .....................................................................57
Contrôle des réglages ...........................................................................59
Schéma fonctionnel ............................................................................... 61
Installation du réseau LON ..................................................................62
Démarrage initial du régulateur ........................................................63
Démarrage du régulateur ............................................................64
Marche manuelle ............................................................................65
Conguration rapide .............................................................................66
EKA 164, EKA 166 ou AKM commande ........................................... 67
5. Fonction de régulation ..........................................................73
Groupe d'aspiration ...............................................................................74
Capteur de régulation ...................................................................74
Référence ...........................................................................................74
Régulation de la capacité des compresseurs ........................75
Méthode de répartition de capacité .................................76
Types de centrales à compresseurs combinés .............. 77
Temporisateur de compresseur .........................................79
Ecrêtage ......................................................................................80
Injection ON .............................................................................. 80
Sécurités ............................................................................................. 81
Condenseur ..............................................................................................82
Régulation de capacité de condenseur ..................................82
Référence de la pression de condensation ............................82
Répartition de capacité .................................................................84
Enclenchement /déclenchement des étages ................ 84
Variation de vitesse .................................................................84
Marche/arrêt des condenseurs ..................................................84
Sécurités du condenseur .............................................................. 85
Fonctions de surveillance - Séparées ..............................................85
Divers ..........................................................................................................86
Annexe – Combinaisons de compresseurs et schémas d’enclenche-
ment ............................................................................................................ 89
2 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 3
1. Introduction
Utilisation
AK-PC 710 est un système complet pour réguler la capacité des compresseurs et des condenseurs ; il est destiné aux systèmes de refroidissement. En plus de la régulation de capacité, ces régulateurs permet la transmission de signaux vers d’autres régulateurs selon la situa­tion du fonctionnement (fermeture forcée des vannes de régula­tion de capacité, signaux et messages d’alarme, etc.).
La fonction primaire du système est de contrôler que les compres­seurs et les condenseurs fonctionnent en permanence sous des pressions optimales du point de vue énergétique. Il faut que les pressions d’aspiration et de condensation soient toujours régulées par des signaux de transmetteurs de pression émettant un signal de tension. La régulation de la capacité peut s’eectuer sur base de la pres­sion d’aspiration P0.
Parmi les diérentes fonctions, citons :
- Régulation de capacité allant jusqu’à 6 compresseurs
- Vitesse variable de 1 compresseur
- Une entré sécurité par compresseur
- Possibilité de limitation de capacité pour réduire les pics de consommation
- lors d’un arrêt des compresseurs, un signal peut être transmis aux autres régulateurs pour qu’ils ferment les vannes de régula­tion de capacité électroniques (signal par la ligne de transmis­sion de données);
- Surveillance de sécurité de haute/basse pression/temp. de refoul.
- Régulation de capacité allant jusqu’à 6 ventilateurs
- Enclenchement d’étage, vitesse variable ou combinasion
- Référence ottante avec température extérieure
- Surveillance de sécurité de ventilateurs
- l’état des sorties et des entrées est aché par des diodes en luminescentes an façade de l’appareil ;
- possibilité de générer des signaux d’alarme directement à partir du régulateur ou par une ligne de transmission ;
- les alarmes sont accompagnées d’un texte expliquant la cause.
- Ainsi que certaines fonctions séparées et totalement indépen­dantes de la régulation : la surveillance du niveau de liquide et de la température ambiante par exemple.
Aperçu des fonctions
AK-PC 710
Utilisation
Régulation d’un groupe de compresseur x
Régulation d'une centrale x
Régulation de la capacité des compresseurs
Capteur de régulation. P0
Régulation PI x Nombre de compresseurs maximum 6 Capacités de compresseurs identiques x
Diérentes capacités de compresseur x
Fonction séquentielle (premier enclenché, dernier déclenché) x
Commande vitesse de compresseur 1 x
Egalisation horaire x
Anti court-cycle. x
Temps de marche mini. / Temps de arrêt mini. x
Référence de pression d’aspiration
Régulation par optimisation P0 x
Régulation par « régime de nuit » x
Régulation de capacité des condenseurs
Capteur de régulation Pc Régulation étages x Nombre d’étages maximum 6
Variation de vitesse x
Régulation étages et variation de vitesse x
Référence de pression de condensation
Référence de pression de condensation ottante x
Fonctions de sécurité
Pression d’aspiration mini x
Pression d’aspiration maxi x
Pression de condensation maxi x
Température de refoulement maxi x
Surchaue mini / maxi x
Surveillance de sécurité des compresseurs x
Surveillance haute pression commune aux compresseurs x
Surveillance basse pression commune aux compresseurs x
Surveillance de sécurité des ventilateurs des condenseurs x
Surveillance de la température ambiante x
Surveillance du niveau de liquide x
Surveillance du variateur de vitesse (VSD) x
Divers
Fonction marche arrêt des postes via la transmission de données x
Possibilité de raccorder un acheur séparé 2 Possibilité de raccorder un acheur graphique 1
SW = 1.4
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 3
Page 4
Principes
Le grand avantage de cette gamme de régulateurs est que l’on peut l'adapter à la taille de l’installation. Les régulateurs sont mis au point pour les commandes d’installations frigoriques, mais sans application spécique – la variation est créée par le logiciel installé et extension possible à 3 modules Les mêmes Modules s’inscrivent dans chaque régulation, et la composition peut être modiée selon besoin. Grâce à ces Modules (ou « briques »), il existe jusqu'à 40 types de régulations diérentes. Or, c’est au technicien d’adapter la régulation aux besoins actuels : le présent manuel vous ore la réponse aux questions permettant de dénir et d’établir les connexions. La programmation et la conguration du régulateur seront repris plus tard.
Régulateur
Partie supérieure
Avantages obtenus
• La puissance du régulateur s'adapte à l’agrandissement de l’installation
• Le logiciel convient à une seule régulation ou à plusieurs
• Davantage de régulations moyennant les mêmes composants
• Facilité d’extension si les besoins changent
• Concept souple :
- Gamme de régulateurs à conguration commune
- Un seul principe pour applications multiples
- On choisit les Modules selon les demandes de connexions
- Les mêmes Modules conviennent à toutes les régulations
Modules d'extension
Partie inférieure
Le régulateur est la pierre de voûte de la régulation. Ce Module comprend les entrées et les sorties nécessaires pour desservir les petites installations.
• La partie inférieure avec les bornes de raccordement sont les mêmes pour tous les types de régulateurs.
• La partie supérieure constitue l’intelligence avec le logiciel. C’est cette unité qui varie selon le type de régulateur. Elle sera toujours livrée avec la partie inférieure.
• En plus du logiciel, la partie supérieure comprend la connexion pour la communi­cation des données et les adresses.
Exemple
Une régulation avec peu de raccordements peut s’eectuer à l’aide d’un seul Module régulateur.
En cas d’agrandissement de l’installation nécessitant davantage de fonctions, on élargit simplement la régulation. Des Modules supplémentaires permettent la réception de plus de signaux et la commutation de plus de relais – le nombre étant fonction de l’application actuelle.
S’il y a de nombreux raccordements, il est devoir de monter un ou plusieurs Modules d’extension.
4 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 5
Connexion directe
Le programme « AK Service Tool » sert à la conguration et à l’opération d’un régulateur AK. Ce programme installé dans un PC, les menus du régulateurs guideront la conguration et l’opération des diérentes fonctions.
Ecrans
Les écrans à menus sont dynamiques, c’est à dire que les diérents points d’un menu ouvriront d’autres écrans à menus avec diérents choix possibles. Une application simple avec peu de connexions fera l’objet d’un montage simplié. Une application similaire avec beaucoup de connexions fera l’objet d’un montage plus complexe. Cet écran général donne accès à plusieurs écrans concernant la régulation de compresseurs et la régulation de condenseurs. En bas de l’écran, on a accès à un nombre de fonctions générales telles que « schéma horaire », « mode manuel », « alarmes » et « entretien » (conguration).
Raccordement sur un réseau
Le régulateur est préparé pour être raccordé sur un réseau formé par d’autres régulateurs dans un système de commande frigorique ADAP-KOOL®. Après le montage, l’opération à distance se fait, par exemple, à l’aide du logiciel AKM.
Utilisateurs
Le régulateur dispose à la livraison de plusieurs langues au choix de l’utilisateur. En cas de plusieurs utilisateurs, chacun peut choisir sa langue préférée. Tous les utilisateurs reçoivent un prol qui leur donne accès soit au niveau superviseur, soit à l’un des niveaux inférieurs de l’opération jusqu’au niveau minimum qui ne donne droit qu’à la consultation.
Ecran externe
Il est possible d’installer un écran externe de façon à acher les mesures P0 (pression d’aspiration) et Pc (condensation). La conguration peut être réalisée sur un écran avec des boutons de commande. Les diérentes fonctions peuvent être sélection­nées via un système de menus. Si l'achage des compresseurs, des ventilateurs et des fonctions opérationnels est nécessaire, un écran de type EKA 166 peut être installé. Conguration et lectures peuvent être réalisées via l'acheur graphique AK-MMI.
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 5
Page 6
Diodes luminescentes
Une série de diodes luminescentes permettent de suivre les signaux reçus et émis par le régulateur.
Enregistrement
La fonction Reg. permet de dénir les mesures à acher. Vous pouvez envoyer les résultats à une imprimante ou les exporter vers un chier. Ce chier peut être ouvert dans le programme Excel. Dans une situation d’entretien, on peut montrer les résultats de mesures dans une fonction tendance. Les mesures sont alors prises à l’instant et les résultats sont achés immédiatement.
Power
Comm
DO1 Status
DO2 Service Tool
DO3 LON
DO4
DO5 Alarm
DO6
DO7
DO8 Service Pin
Clignotement lent = en ordre Clignotement rapide = réponse de la passerelle Allumée en permanence = erreur
Eteinte en permanence = erreur
Clignotement = alarme active, non acquittée Allumée en permanence = alarme active, acquittée
Alarme
Cet écran montre la liste de toutes les alarmes actives. Pour conrmer que vous avez vu l’alarme, cochez la case d’acquittement. Pour en savoir plus sur une alarme actuelle, cliquez-la pour appeler un écran explicatif. Un écran similaire existe pour toutes les alarmes antérieures. Vous pourrez y trouver les informations supplémentaires pour connaître éventuellement l’historique des alarmes.
6 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 7
2. Conception d'un régulateur
Ce régulateur peut être conguré sur l'une des 40 applications xes.
• Il existe 20 applications avec un nombre diérent de compres­seurs et de ventilateurs de condenseur.
• Les mêmes applications peuvent aussi être activées avec une régulation de la vitesse d'un compresseur.
• Les ventilateurs de condenseur peuvent être raccordés par pas ou avec une régulation de la vitesse.
L'application sélectionnée a déterminé des points de connexion dénis. Ces derniers ne peuvent pas être modiés.
Outre le module du régulateur, un ou plusieurs des modèles sui­vants doivent être utilisés. L'application sélectionnée détermine :
• Le module de sortie avec des relais
• Un module d'entrée pour l'enregistrement des signaux On/O
• Un module de sortie analogique pour la régulation d'un ou de deux variateurs de fréquence : un pour un compresseur et un autre pour les ventilateurs de condenseur.
Cette section dénit l'application et les modules à utiliser.
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 7
Page 8
Sommaire des Modules
• Module régulateur de base qui répond aux exigences des petites et moyennes installations.
• Modules d’extension. Pour couvrir une plus grande gamme de régulation nécessitant un supplément d’entrées et de sorties, on peut raccorder des Modules d’extension au Module régulateur de base. Un connecteur sur le côté du Module permet le trans­fert de la tension d’alimentation et la transmission de données aux autres Modules.
• Partie supérieure
L’intelligence est logée dans la partie supérieure du Module régulateur de base. C’est dans cette unité qu’a lieu la dénition de la régulation ; c’est ici que se fait la transmission de données d’un réseau.
Module d’extension avec entrées analogiques supplémentaires.
Acheur externe pour indiquer la pression d’aspiration, par exemple
Types de connexions
Les entrées et les sorties sont de types diérents. Un type reçoit, par exemple, le signal émis par des capteurs et des contacts, un autre reçoit un signal de tension et un troisième fait fonction de sortie relais, etc. Les diérents types ressortent du tableau
ci-contre.
• Fixed connection
La conception et le montage de la régulation nécessitent un certain nombre de connexions des types cités. Ce raccordement
doit être réalisé de la façon indiquée sur les schémas suivants.
Module d’extension avec sorties relais et entrées analogiques supplémentaires.
Partie inférieure
Module régulateur de base avec entrées analogiques et sorties à relais.
Partie supérieure
Le Module d’extension avec sorties relais existe également dans une autre version : la partie supérieure est ici dotée de commutateurs pour la commande manuelle
des relais Module d’extension avec signal de sortie analogique.
8 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 9
1. Régulateur
Type Fonction Utilisation
AK-PC 710
Régulateur pour régulation de capacité des compresseurs (6) et des condenseur ventilateurs (6)
Compresseur / condenseur / centrale
2. Modules d’extension et aperçu des entrées et sorties
Type Entrées
analogiques
Pour capteurs, transmetteurs de pression etc.
Régulateur 11 4 4 - - - -
Module d'extension
AK-XM 102A 8
AK-XM 102B 8
AK-XM 204A 8
AK-XM 204B 8 x
AK-OB 110 2
Sorties tout/rien Entrées de tension tout/rien
Relais (SPDT)
Relais statique Basse tension
(Signal DI)
(80 V maxi)
Haute tension (260 V maxi)
Sorties analogiques
0-10 V c.c. Pour la comman-
Module avec commutateurs
de manuelle des relais de sortie
3. Commande et accessoires AK
Type Fonction Utilisation
Opération
AK-ST 500 Logiciel pour la commande des régulateurs AK AK-commande
- Câble reliant le PC et le régulateur AK AK - Com port
-
Accessoires Module alimentation 230 V / 115 V jusqu’à 24 V
AK-PS 075 18 VA Alimentation du régulateur
Accessoires Acheur externe pour raccordement au module régulateur. Pour indiquer la pression d’aspiration, par exemple
EKA 163B Acheur
EKA 164B Acheur avec boutons de commande
EKA 166
AK-MMI Acheur graphique avec commande
-
Accessoires
AK-OB 101A Horloge en temps réel avec pile de réserve A monter à l’intérieur d’un régulateur AK
Câble reliant le câble du modem et le régulateur AK Câble reliant le câble et le régulateur AK
Acheur avec boutons de commande et voyants LED pour les entrées et les sorties
Câble entre acheur EKA et régulateur Longueur = 2 m, 6 m
Câble entre acheur graphique et régulateur Longueur = 0,8 m, 1,5 m, 3 m
Horloge en temps réel pour régulateurs nécessitant une fonction d’horloge sans être connecté à une transmission de don­nées
AK - RS 232
Aux pages suivantes, vous trouverez davantage d’informations sur chacun des Modules.
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 9
Page 10
Données communes aux Modules
Tension d’alimentation 24 V c.c./c.a. +/- 20%
Puissance absorbée AK-__ (régulateur) 8 VA
AK-XM 102 2 VA
AK-XM 204 5 VA
Entrées analogiques Pt 1000 ohm /0°C
Transmetteur de pression AKS 32R / AKS 32 (1-5 V)
Signal de tension 0-10 V
Fonction de contact (tout/rien)
Entrées de tension tout/rien
Sortie à relais SPDT
Sorties relais statique
Ambiance
Basse tension 0 / 80 V c.a./c.c.
Haute tension 0 / 260 V c.a.
AC-1 (ohmique)
AC-15 (inductif)
U Min. 24 V
Utilisées pour la régulation du relais du compresseur
Transport -40 à 70°C
Résolution : 0,1°C Précision : ± 0,5°C
Résolution 1 mV Précision +/- 10 mV Un Module permet le raccordement d’un maximum de 5 transmetteurs de pression.
Fermé à R <20 ohm Ouvert à R >2 K ohm (contacts or pas nécessaires)
Fermé : U < 2 V Ouvert : U > 10 V
Fermé: U < 24 V Ouvert : U > 80 V
4 A
3 A
Max. 230 V Il ne faut pas raccorder basse et haute tension au même groupe de sortie
240 V c.a. maxi, 48 V c.a. mini Maxi. 0,5 A, Fuite < 1 mA
-20 à 55°C ,
Fonctionnement
Matériau PC / ABS
Boîtier
Poids, bornes vissées comprises Modules des séries 100- / 200- / régulateur Env. 200 g / 500 g / 600 g
Homologations Conformes à la directive EU sur les appa-
Les données spéciées s’appliquent à tous les Modules. En cas de données spéciques, celles-ci sont précisées concernant le Module actuel.
Charge capacitive
Les relais ne peuvent pas être utilisés pour le raccordement direct de charges capaci­tives telles que des LED et la commande marche/arrêt de moteurs EC. Toutes les charges présentant une alimentation à commutation doivent être con­nectées à l’aide d’un contacteur adapté ou similaire.
Etanchéité IP10 , VBG 4
Montage Pour intégration Pour montage mural ou sur rail DIN
reils basse tension et testés CEM.
UL 873,
Humidité relative de 0 à 95% RH (non condensate) Chocs et vibrations à proscrire
Testés LVD selon EN 60730 Testés CEM Immunité selon EN 61000-6-2 Emission selon EN 61000-6-3
UL le number: E166834 au XM UL le number: E31024 au PC
10 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 11
Dimension
AK-PC 710
AK-PC 710 + AK-XM 102
AK-PC 710 + AK-XM 204 + AK-XM 102
AK-PC 710 + AK-XM 204 + AK-XM 102 + AK-XM 102
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 11
Page 12
Régulateur
Fonction
Cette série comprend plusieurs régulateurs. Les fonctions sont dénies par le logiciel programmé, mais extérieurement les régulateurs sont identiques avec les mêmes connexions possibles :
11 entrées analogiques pour capteurs, transmetteurs de pression,
signaux de tension et signaux de contacts.
8 sorties numériques, dont 4 sorties relais statique et 4 sorties à
relais.
Tension d’alimentation
Le Module régulateur est alimenté en 24 V c.a. ou c.c. Il ne faut pas transmettre ces 24 V aux autres régulateurs puisque le régulateur n’est pas galvaniquement isolé des entrée et des
sorties. Il faut donc installer un transformateur par régulateur. La class II est indiquée. Il ne faut pas relier les bornes à la terre.
La tension d’alimentation des Modules d’extension éventuels est transmise par le connecteur du côté droit. La puissance du transformateur est fonction de la puissance absorbée par le nombre total de Modules.
PIN
La tension alimentant un transmetteur de pression peut être relevée de la sortie 5 V ou de la sortie 12 V.
Transmission de données
Si le régulateur doit faire partie d’un système, il faut le relier par le connecteur LON. L’installation correcte ressort d’un guide séparé.
Adresse Pour connecter le régulateur à une passerelle AKA 245, on choisit une adresse entre 1 et 119. ((Donc, en cas de system manager
AK-SM .., 1-999).
Service PIN Lorsque le régulateur a été branché sur le câble série, il faut informer la passerelle sur le nouveau régulateur. Appuyez sur le contact PIN. La diode « Status » clignote, lorsque la passerelle envoie son acceptation.
Utilisation
La conguration de la commande du régulateur se fait à l’aide du programme logiciel «Service Tool » (outil de service). Le programme est installé sur un PC et le PC est relié au régulateur par la prise réseau en façade.
Diodes luminescentes
Il y a deux rangs de diodes. Voici leur signication : Rang de gauche :
• Régulateur sous tension
• Communication avec la carte de fond active (rouge = erreur)
• Etat des sorties DO1 à DO8
Rang de droite :
• Etat du logiciel (clignotement lent = en ordre)
• Communication avec le programme « Service Tool »
• Communication par LON
• Clignotement : alarme
- 3 diodes disponibles
• Le contact « Service PIN » a été actionné
Adresse
Power
Comm
DO1 Status
DO2 Service Tool
DO3 LON
DO4
DO5 Alarm
DO6
DO7
DO8 Service Pin
Clignotement lent = en ordre Clignotement rapide = réponse de la passerelle Allumée en permanence = erreur
Eteinte en permanence = erreur
Clignotement = alarme active, non acquittée Allumée en permanence = alarme active, acquittée
Garder la distance de sécurité !
Il ne faut pas raccorder le haut voltage et le bas voltage au même groupe de sortie
Un petit Module (carte optionnelle ou Carte optionnelle) peut être installé au fond du régulateur. Ce Module est décrit plus loin.
12 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 13
Point
Point 1 2 3 4 5 6 7 8 9 10 11
Type AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8 AI9 AI10 AI11
Borne 15: 12 V Borne 16: 5 V
Borne 27: 12 V Borne 28: 5 V
Entrées analogiques
points 1 à 11
Sorties Relais statique points 12 à 15
Relais 230 V c.a., par exemple
Signal Type
S
Pt 1000 ohm/0°C
Saux1 Sc3 SS Sd
P
AKS 32R
3: Brun
2: Bleu
1: Noir
P0 Pc
AKS 32
3: Brun
2: Noir
1: Rouge
On/O Interr.
princ. Ext.
Jour/ Nuit
PLP PHP LL
DO
Comp 1-6
Ventila­teur 1
Alarme
Carte optionnelle
Voir le signal sur le côte du module, s.v.p.
points 24 et 25 utilisés seulement en cas de carte optionnelle (« Carte optionnelle »)
signal
Pt 1000
AKS 32R/ AKS 2050
-1 - xx bar
AKS 32
-1 - zz bar
Actif à:
Fermeture
/
Ouverture
Actif à:
Tout
/
Rien
Sorties de relais
points 16 à 19
Point 12 13 14 15 16 17 18 19
Type DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8
Signal Module Point Borne Type Signal /
1 (AI 1) 1 - 2
2 (AI 2) 3 - 4
3 (AI 3) 5 - 6
4 (AI 4) 7 - 8
5 (AI 5) 9 - 10
6 (AI 6) 11 - 12
7 (AI 7) 13 - 14
8 (AI 8) 19 - 20
9 (AI 9) 21 - 22
10 (AI 10) 23 - 24
11 (AI 11) 25 - 26
1
12 (DO 1) 31 - 32
La fonction et le numéro de borne sont indiqués sur le schéma réel
13 (DO 2) 33 - 34
14 (DO 3) 35 - 36
15 (DO 4) 37 - 38
16 (DO 5) 39 - 40- 41
17 (DO6) 42 - 43 - 44
18 (DO7) 45 - 46 - 47
19 (DO8) 48 - 49 - 50
24 -
25 -
Borne 17, 18, 29, 30: (Blindage)
Actif à
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 13
Page 14
Modules d'extension AK-XM 102A / AK-XM 102B
Fonction
Ces modules comprennent 8 entrées pour signaux de tension tout/rien (Basse et haute tension).
Signal
AK-XM 102A pour signaux à basse tension AK-XM 102B pour signaux à haute tension
Tension d’alimentation
La tension d’alimentation du Module est fournie par le module précédent de la chaîne.
Diodes luminescentes
Voici leur signication :
• Module sous tension
• Communication avec la carte socle active (rouge = erreur)
Etat de chacune des entrées de 1 à 8 (allumée = sous tension)
AK-XM 102A
Max. 24 V
On/O: On: DI > 10 V a.c. O: DI < 2 V a.c.
AK-XM 102B
Max. 230 V
On/O: On: DI > 80 V a.c. O: DI < 24 V a.c.
14 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 15
Point
DI
AK-XM 102A: Max. 24 V AK-XM 102B: Max. 230 V
Signal Actif á
Jour/ Nuit
Circuit sécu. Comp. 1-6
Circuit sécu. ventila­teurs
Fermeture
(sous
tension)
Ouverture
(hors tension)
Point 1 2 3 4
Type DI1 DI2 DI3 DI4
Point 5 6 7 8
Type DI5 DI6 DI7 DI8
/
Signal Module Point Borne Actif à
1 (DI 1) 1 - 2
2 (DI 2) 3 - 4
3 (DI 3) 5 - 6
4 (DI 4) 7 - 8
3 (2)
La fonction et le numéro de borne sont indiqués sur le schéma réel
5 (DI 5) 9 - 10
6 (DI 6) 11 - 12
7 (DI 7) 13 - 14
8 (DI 8) 15 - 16
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 15
Page 16
Modules d'extension AK-XM 204A / AK-XM 204B
Fonction
Ces modules comprennent 8 sorties de relais.
Tension d’alimentation
La tension d’alimentation du Module est fournie par le module précédent de la chaîne.
Commande manuelle du relais
En façade, huit commutateurs permettent la commande manuelle des relais. Soit en position O (rien) ou On (tout). En position Auto, le régulateur est en charge de la commande.
Diodes luminescentes
Il y a deux rangs de diodes. Voici leur signication : Rang de gauche :
• Régulateur sous tension
• Communication avec la carte socle active (rouge = erreur)
• Etat des sorties DO1 à DO8
Rang de droite : (seul AK-XM 204B)
Commande manuelle des relais
Allumée = commande manuelle Eteinte = pas de commande manuelle
Fusibles
En arrière de la partie supérieure, un fusible protège chaque sortie.
AK-XM 204A AK-XM 204B
Max. 230 V
AC-1: max. 4 A (ohmique) AC-15: max. 3 A (Inductief)
AK-XM 204B Forçage du relais
Garder la distance de sécurité !
Il ne faut pas rac­corder la haute et la basse tension au même module
16 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 17
Point
Point 1 2 3 4 5 6 7 8
Type DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8
DO
Signal Actif à
Ventila­teur 1
Alarme
On
O
/
Signal Module Point Borne Actif à
1 (DO 1) 25 - 27
2 (DO 2) 28 - 30
3 (DO 3) 31 - 33
2
4 (DO 4) 34 -36
5 (DO 5) 37 - 39
6 (DO 6) 40 - 41 - 42
7 (DO 7) 43 - 44 - 45
8 (DO 8) 46 - 47 - 48
La fonction et le numéro de borne sont indiqués sur le schéma réel
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 17
Page 18
Module d'extension AK-OB 110
Fonction
Ce Module comprend 2 sorties de tensions analogique de 0 à 10 V.
Tension d’alimentation
La tension d’alimentation du Module est fournie par le Module régulateur.
Emplacement
Le Module est installé sur la carte à l’intérieur du Module régulateur.
Point
Les deux sorties sont les points 24 et 25 montrés à la page précédente traitant du régulateur.
Charge max. I < 2,5 mA R > 4 kohm
AO AO1:
Comp. vitesse
AO2:
Cond.
vitesse
0 - 10 V
Module
Point 24 25
Type AO1 AO2
1
AO2
AO1
18 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 19
Module d'extension AK-OB 101A
Fonction
Ce module est une horloge avec pile de réserve.
Il convient aux régulateurs non connectés à une transmission de données avec d’autres régulateurs. On utilise le Module si le régulateur a besoin d’une pile de réserve pour les fonctions suivantes :
• Horloge
• Heures xes pour commutations jour/nuit
• Conservation du registre d’alarmes en cas de panne de courant
• Conservation du registre de températures en cas de panne de courant
Connexion
Le module est à connecteur.
Emplacement
Le module est à placer sur la carte à l’intérieur de l’unité à moteur.
Point
Il n’est pas nécessaire de dénir un point pour un Module d’horloge – il sut de le connecter.
Durée de vie de la pile
La pile a une vie de plusieurs années – même en cas de pannes de courant fréquentes. Une alarme indique le changement imminent de la pile. Au moment de l’alarme, la pile peut encore fonctionner plusieurs
mois.
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 19
Page 20
Modules d'achage EKA 163B / EKA 164B
Fonction
Achage des mesures relevées par le régulateur : pression d’aspi­ration ou de condensation, par exemple. Le réglage individuel des fonctions est possible en utilisant l’a­cheur à boutons de réglage.
Raccordement
Relier le module au régulateur par un câble avec connecteurs. Utiliser un câble par Module. Le câble existe en diérentes longueurs.
Les deux types d’acheurs (avec ou sans boutons) peuvent être raccordés à la sortie A et B. A = P0 . pression d’aspiration au °C B = Pc. pression de condensation au °C
L'EKA 166 comprend également plusieurs voyants LED qui per­mettent de suivre les fonctions individuelles.
EKA 163B EKA 164B
Quand le régulateur démarre, l'achage indique la sortie qui est connectée. . - - 1=sortie A, - - 2=sortie B, etc.
Emplacement
Placer le module à une distance maximum de 15 m du régulateur.
Point
Pas besoin de dénir un point pour un module d’achage – le raccorder simplement.
Achage graphique AK-MMI
Fonction
Réglage et achage des valeurs dans le régulateur.
Raccordement
L'acheur se connecte au régulateur via un câble avec des ches de connexion. Utiliser une che RJ45 pour connecter le régulateur ; la même che sert également pour Service tool AK-ST 500.
Tension d’alimentation
24 V c.a. / c.c. 1.5 VA.
EKA 166
Module
Point - -
Type - -
1
Emplacement
Placer le achage à une distance maximum de 3 m du régulateur.
Point
Pas besoin de dénir un point pour un d’achage – le raccorder simplement.
20 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 21
Module Alimentation AK-PS 075
Fonction
Alimentation de 24 V du régulateur.
Tension d’alimentation
230 V c.a. ou 115 V c.a. (de 100 V c.a. à 240 V c.a.)
Emplacement
Sur rail DIN
Eet
Type Tension de sortie Courant de sortie Eet
AK-PS 075 24 V c.c. 0.75 A 18 VA
Dimensions
Type Hauteur Largeur
AK-PS 075 90 mm 36 mm
Raccordement
Alimentation d’un régulateur principal
AK-PS 075
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 21
Page 22
Sélectionner l'application
Généralités
Fonction horloge
La fonction d’horloge et de passage entre heure d’été et heure d’hiver est logée dans le régulateur. L’horloge est mise à zéro en cas de panne de courant. Le réglage de l’horloge est conservé si le régulateur est raccordé sur un réseau avec passerelle, system manager ou si un Module horloge est installé dans le régulateur.
Marche/arrêt de la régulation
La marche/arrêt de la régulation est commandée par le logiciel, ou par une entrée sur le module du régulateur.
Application
40 exemples d'applications sont présentés dans le tableau ci-con­tre : sélectionner celle qui convient au système.
Le câblage doit être réalisé de la façon indiquée et le régula­teur doit être déni pour cette application.
Concernant la régulation de la vitesse
Une carte en option comporte 2 sorties : La sortie nº1 est dédiée au compresseur La sortie nº2 est dédiée aux ventilateurs de condenseur
Si la régulation de la vitesse n'est pas utilisée, ne pas tenir compte des sorties 0-10 V indiquées.
Seul le raccord du compresseur est présenté dans tous les exemples mais la sortie nº2 peut être utilisée à volonté pour les ventilateurs de condenseur.
Si la régulation de la vitesse a besoin d'un signal de marche/arrêt, elle peut être obtenue depuis la sortie « Compresseur 1 » ou « ventilateur 1 ».
Commande forcée
Le logiciel ore la possibilité d’une commande forcée. Si un Module d’extension avec sorties de relais est installé, la partie supérieure du Module comporte éventuellement des commutateurs ; dans ce cas, ces commutateurs permettent de forcer chaque relais en position marche ou en position arrêt.
Transmission de données
Le Module régulateur est doté de bornes pour raccorder une communication de données LON. Les conditions imposées à l’installation ressortent d’un document séparé.
Nombre de compresseurs
2 0 1 21
3 0 5 25
4 0 9 29
5 0 13 33
6 0 17 37
Nombre de ventilateurs de condenseur
2 2 22
3 3 23
4 4 24
3 6 26
4 7 27
5 8 28
3 10 30
4 11 31
5 12 32
4 14 34
5 15 35
6 16 36
4 18 38
5 19 39
6 20 40
Régulation de la vitesse sur un compresseur
Oui No
Application n°
22 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 23
Applications 1 et 21 (pour la 21, retirer la connexion VSD de la carte en option)
Applications 2 et 22 (pour la 22, retirer la connexion VSD de la carte en option)
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 23
Page 24
Applications 3 et 23 (pour la 23, retirer la connexion VSD de la carte en option)
Applications 4 et 24 (pour la 24, retirer la connexion VSD de la carte en option)
24 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 25
Applications 5 et 25 (pour la 25, retirer la connexion VSD de la carte en option)
Applications 6 et 26 (pour la 26, retirer la connexion VSD de la carte en option)
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 25
Page 26
Applications 7 et 27 (pour la 27, retirer la connexion VSD de la carte en option)
Applications 8 et 28 (pour la 28, retirer la connexion VSD de la carte en option)
26 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 27
Applications 9 et 29 (pour la 29, retirer la connexion VSD de la carte en option)
Applications 10 et 30 (pour la 30, retirer la connexion VSD de la carte en option)
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 27
Page 28
Applications 11 et 31 (pour la 31, retirer la connexion VSD de la carte en option)
Applications 12 et 32 (pour la 32, retirer la connexion VSD de la carte en option)
28 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 29
Applications 13 et 33 (pour la 33, retirer la connexion VSD de la carte en option)
Applications 14 et 34 (pour la 34, retirer la connexion VSD de la carte en option)
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 29
Page 30
Applications 15 et 35 (pour la 35, retirer la connexion VSD de la carte en option)
Applications 16 et 36 (pour la 36, retirer la connexion VSD de la carte en option)
30 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 31
Applications 17 et 37 (pour la 37, retirer la connexion VSD de la carte en option)
Applications 18 et 38 (pour la 38, retirer la connexion VSD de la carte en option)
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 31
Page 32
Applications 19 et 39 (pour la 39, retirer la connexion VSD de la carte en option)
Applications 20 et 40 (pour la 40, retirer la connexion VSD de la carte en option)
32 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 33
Sommaire des modules
1. Régulateur
Type Fonction Langue
AK-PC 710 Régulateur de capacité des compresseurs (6) et des condenseurs ventilateurs (6)
Anglais, allemand, français, Italien, hollandais, espagnol
2. Modules d’extension et aperçu des entrées et sorties
Type Entrées
analogiques
Pour capteurs, transmetteurs de pression etc.
Régulateur 11 4 4 - - - - -
Module d'extension
AK-XM 102A 8 080Z0008
AK-XM 102B 8 080Z0013
AK-XM 204A 8 080Z0011
AK-XM 204B 8 x 080Z0018 AK-OB 110 2 080Z0251
Sorties tout/rien Entrées de tension tout/rien
Relais (SPDT)
Relais statique Basse tension
(Signal DI)
(80 V maxi)
Haute tension (260 V maxi)
Sorties analogiques
0-10 V c.c. Pour la
Module avec commuta­teurs
commande manuelle des relais de sortie
Numéros de
code
080Z0106
Numéros de code
Avec bornes à visser
3. Commande et accessoires AK
Type Fonction Utilisation
Opération
AK-ST 500 Logiciel pour la commande des régulateurs AK AK-commande 080Z0161
- Câble reliant le PC et le régulateur AK AK - Com port 080Z0262
-
- Câble reliant le PC et le régulateur AK AK -USB 080Z0264
Accessoires Module alimentation 230 V / 115 V jusqu’à 24 V AK-PS 075 18 VA Alimentation du régulateur 080Z0053
Accessoires Acheur externe pour raccordement au module régulateur. Pour indiquer la pression d’aspiration, par exemple
EKA 163B Acheur 084B8574
EKA 164B Acheur avec boutons de commande 084B8575
EKA 166
AK-MMI Acheur graphique avec commande 080G0311
- Câble entre acheur EKA et régulateur
- Câble entre acheur graphique et régulateur
Câble reliant le câble du modem et le régulateur AK Câble reliant le câble PDA et le régulateur AK
Acheur avec boutons de commande et voyants LED pour les entrées et les sorties
AK - RS 232 080Z0261
Longueur = 2 m 084B7298
Longueur = 6 m 084B7299
Longueur = 0.8 m 080G0074
Longueur = 1.5 m 080G0075
Longueur 3 m 080G0076
Numéros de
code
084B8578
Accessoires Horloge en temps réel pour régulateurs nécessitant une fonction d’horloge sans être connecté à une transmission de données
AK-OB 101A Horloge en temps réel avec pile de réserve A monter à l’intérieur d’un régulateur AK 080Z0252
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 33
Page 34
34 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 35
3. Montage et câblage
Ce chapitre décrit la façon dont le régulateur est :
• Monté
• Raccordé
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 35
Page 36
Montage
Montage d’un module sortie analogique
1. Enlevez la partie supérieure du module de base
Pour cela, il faut que le module soit hors tension.
Pressez (vers l’intérieur) le côté à gauche des diodes et le côté à droite des sélecteurs d’adresses. Enlevez la partie supérieure du Module de base.
Le module d’extension analogique doit fournir un signal au variateur de fréquence.
2. Mettez le module d’extension en place dans le module de base
3. Remettez la partie supérieure du module de base en place
36 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 37
Montage et câblage - Suite
Montage d'un module E/S sur le module de base
1. Pour déplacer le capuchon protecteur
Enlevez le capuchon du connecteur situé à droite du module de base. Placez le capuchon sur le connecteur à droite du module E/S qui sera monté tout à fait à droite sur l’ensemble AK.
2. Connectez le module E/S sur le module de base
Pour cela, le module de base doit être hors tension.
Quand les deux clips du rail DIN sont en position ouverte, le module peut s'intercaler sur le rail DIN, quelle que soit la série du module. Le démontage se déroule de la même façon, les deux clips en position ouverte.
La séquence est déterminée par le schéma électrique présenté
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 37
Page 38
Montage et câblage - Suite
Câblage
A la conception, l’on a déterminé la fonction qui doit être raccor­dée et l’endroit du raccordement.
1. Raccordement des entrées et des sorties
Voir le schéma électrique sélectionné plus haut :
2. Raccordement du réseau LON
L’installation de la transmission de données doit être conforme aux normes spéciées dans le document RC8AC.
3. Raccordement de la tension d’alimentation
L’alimentation en 24 V est à proscrire pour d’autres régulateurs ou appareils. Il ne faut pas relier les bornes à la terre.
4. Suivre les indications des diodes luminescentes
Lorsque le régulateur est mis sous tension, il est soumis à un contrôle interne. Le régulateur est prêt après une minute (la diode « Status » émet un clignotement lent).
5. En cas de réseau
Réglez l’adresse et activez le Service Pin.
6. Le régulateur est maintenant prêt à être conguré.
Exemple
Le blindage des câbles de trans­metteur de pression doit être relié au régulateur uniquement.
Communication interne entre les Modules : Clignotement rapide = erreur Allumée en permanence = erreur
Power
Comm
DO1 Status
DO2 Service Tool
DO3 LON
DO4
DO5 Alarm
DO6
DO7
DO8 Service Pin
Etat de sortie 1-8
Clignotement lent = OK Clignotement rapide = réponse de la passerelle dans les 10 minutes suivant l’installation du réseau Allumée en permanence = erreur Eteinte en permanence = erreur
Communication externe
Clignotement = alarme active / non acquittée Allumée en permanence = alarme active / acquitée
Installation de réseau
Attention : maintenez les câbles de transmission à distance des câbles haute tension.
38 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 39
4. Conguration et opération
Ce chapitre décrit la façon dont le régulateur est :
• conguré
• commandé
Nous avons décidé de travailler sur la base de l'application nº16, à savoir la commande de compresseur avec 5 compresseurs et la commande de condenseur avec 6 ventilateurs :
L’exemple est illustré en page suivante.
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 39
Page 40
Exemple d'installation frigorique
Nous avons choisi de décrire la conguration par un exemple consistant en une centrale de compresseurs et de condenseur. L’exemple est le même que celui qui est présenté sous le chapitre « Application nº16 », à savoir le régulateur d'un AK-PC 710 + 3 modules d'extension.
Groupe de compresseurs pour réfrigération :
• Réfrigérant R134a
• 1 compresseur à vitesse variable (30 kW, 30-60 Hz)
• 4 compresseurs (15 kW) avec égalisation de temps de marche
• Contrôle de sécurité de chaque compresseur
• Contrôle commun de la haute pression
• Contrôle commun de la basse pression
• Réglage P0 15°C, décalage nocturne de 5 K
Condenseur pour réfrigération :
• 6 ventilateurs à régulation étagée
• Régulation Pc en fonction de la température extérieure (Sc3)
Bouteille :
• Contrôle du niveau de liquide dans le réservoir
Carter du compresseur :
• Surveillance de la température dans la pièce de l'installation
Sécurités :
• Contrôle de P0, Pc, Sd et de la surchaue d’aspiration
• P0 max = -5°C, P0 min = -35°C
• Pc max = 50 °C
• Sd max = 120°C
• SH min = 5 °C, SH max = 35 °C
Autres :
• Sortie d’alarme utilisée
• Interrupteur principal externe utilisé
• Surveillance du variateur de vitesse (VSD)
Pour l’exemple actuel, nous utilisons les modules suivants :
• Module de base AK-PC 710
• Module de relais AK-XM 204B
• Module d’entrée digital AK-XM 102B
• Module de sortie analogique AK-OB 110
NB
La capacité variable du compresseur à régulation de vitesse doit être supérieure à celle des autres compresseurs. Il n’y a ainsi pas de « trous » dans la capacité enclenchée. Voir le chapitre 5. Fonctions de régulation.
Il y a également un interrupteur principal interne pour le réglage. Avant de procéder à la régulation, les deux doivent être en position « ON ».
Les modules utilisés sont sélectionnés au cours de la phase de concep­tion.
40 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 41
Conguration via service tool AK-ST 500
Raccordement du PC
Raccordez au régulateur le PC chargé du programme « Service Tool ».
Pour le raccordement et la commande du programme « AK-Service tool », il est conseillé de se référer au manuel du programme.
Avant de démarrer le programme Service Tool, il faut que le régulateur soit allumé (la diode « Status » clignote).
Démarrage du programme Service Tool
Accès (Login) sous le nom SUPV (Superviseur)
Choisissez SUPV et inscrivez le code d’accès correspondant.
Après le raccordement du Service Tool à une nouvelle version d’un régu­lateur, la première mise en route prendra plus de temps que normale­ment — des informations sont obtenues du régulateur.
On peut vérier le temps écoulé sur la barre en dessous de l’écran.
Lors de la livraison du régulateur, le code d’accès est 123.
Après accès au régulateur, son écran général apparaît.
Dans ce cas, l’écran général est vide. En fait, le régulateur n’a pas encore été conguré.
La cloche d’alarme rouge en bas à droite indique une alarme active dans le régulateur. Dans notre cas, l’alarme est active parce que l’horloge du régulateur n’a pas encore été réglée.
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 41
Page 42
Conguration - Suite
Authorization
1. Appel du menu de conguration
Appuyez sur le bouton orange (Outil) en bas de l’écran.
2. Autorisation
3. Modication des réglages utilisateur ‘SUPV‘
À sa livraison, le régulateur est conguré avec une autorisation standard pour les diérentes interfaces utilisateur. Ce réglage doit être modié et adapté à l'installation. Il peut être eectué maintenant ou ultérieure­ment.
Il convient d’utiliser ce bouton autant de fois que vous souhaitez avan­cer dans cet écran. Ici, à gauche, toutes les fonctions n’apparaissent pas encore. De plus en plus apparaissent au fur et à mesure que l’on avance dans la congura­tion.
Appuyez sur la ligne « Authorization » pour appeler l’écran de congu­ration d’utilisateur.
4. Sélection des nom d'utilisateur et code d'accès
5. Ouvrir une nouvelle session avec le nom d'utilisa-
teur et le nouveau code d'accès
Choisissez la ligne SUPV Appuyez sur le bouton « Change ».
C'est ici que vous pouvez sélectionner le superviseur pour le système en question et dénir un code d'accès pour cette personne.
Dans les versions précédentes du Service Tool AK-ST 500, il était possi­ble de sélectionner la langue dans ce menu. Une version améliorée du Service Tool sortira au printemps 2009. Si le régulateur est utilisé avec cette nouvelle version, le choix de la langue se fera automatiquement dans le cadre de la conguration du Service Tool. Le régulateur utilisera la même langue que celle choisie dans le Service Tool, mais uniquement s'il dispose de cette langue. Si la langue n'est pas disponible dans le régulateur, les réglages et achages seront achés en anglais.
Pour actionner la nouvelle réglage, accédez à nouveau au régulateur sous le nouvelle nom et utilisant le code d’accès correspondant. Pour appeler l’écran Login (accès), appuyez sur le cadenas en haut à gauche de l’écran.
42 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 43
Conguration - Suite
Déblocage de la conguration du régula­teur
1. Appel du menu de conguration
2. Choisir Bloquer conguration
3. Choisir Clef conguration
Appuyez sur la case bleue marquée Bloqué.
Le régulateur ne peut être conguré que s’il est « Bloqué ».
L’on peut procéder à des changements de valeurs lorsqu’il est bloqué mais uniquement pour les réglages qui n’endommagent pas la congu­ration.
4. Choisir Débloqué
Choisissez Débloqué et appuyez sur OK.
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 43
Page 44
Conguration - Suite
Réglage système
1. Appel du menu de conguration
2. Choisir Réglage système
3. Modier les réglages système
Chaque réglage système peut être modié en appuyant sur la case bleue du réglage ; inscrivez ensuite la valeur désirée. Lors du réglage du temps, l’heure du PC peut être transférée au régulateur. Au moment de raccorder le régulateur à un réseau, la date et l’heure seront automatiquement réglées par le concentrateur du réseau. Ceci s’applique aussi pour le passage entre heure d’été et heure d’hiver.
Si le régulateur est installé sur un réseau, une « automatic acknowled­gement of alarms » (reconnaissance automatique des alarmes) doit être réglée sur « disable » (désactivée). Le traitement et la reconnais­sance de l'alarme sont transférés vers l'unité du système. Si le régulateur est installé sans réseau, la « automatic acknowledge­ment of alarms » (reconnaissance automatique des alarmes) doit être réglée sur « enable » (activée). Le régulateur reconnaît alors lui-même les alarmes.
44 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 45
Conguration - Suite
Régler le type d'installation
1. Appel du menu de conguration
2. Choisir Choix type Inst.
Appuyez sur la ligne Choix type Inst.
3. Choisir Choix type Inst
Ce réglage se rapporte aux applications. Voir page 22.
Après réglage de cette fonction, le régulateur s’éteint et redémarre. Après redémarrage, cet ensemble de réglages sera enregistrés. Y compris les raccordement. Poursuivez les réglages et vériez les va­leurs. Si vous modiez l’un ou l’autre réglage, les nouveaux réglages seront applicables.
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 45
Page 46
Conguration - Suite
Modication de la régulation de fonction d'aspiration
1. Appel du menu de conguration
2. Choix du groupe d'aspiration
3. Régler les valeurs de référence
Appuyez sur le bouton + pour passer à la page suivante.
4. Régler les valeurs de la régula­tion de capacité
Le menu de conguration du Service Tool se modie alors. Il montre les réglages possibles pour le type d’installation choisi.
Réglages de notre exemple :
- Pression d’aspiration = -15°C
- Augmentation nocturne = 5 K. Les réglages sont illustrés ici.
Il y a plusieurs pages sous-jacentes. En l’occurrence, la barre noire indique à quelle page on se trouve. Pour passer d’une page à l’autre, il convient d’utiliser les boutons + et -.
Réglages de notre exemple :
- Réfrigérant = R134a
- Egalisation des temps de marche
- Valeurs pour la régulation de la vitesse
Une régulation de la vitesse se fera toujours au niveau du compresseur 1.
Les réglages sont illustrés ici.
Ci-après, sur l’illustration, est activée la fonction qui dénit l’injection de liquide dans l’échangeur de chaleur. L’ajustement de la vitesse n’est pas possible sur tous les compresseurs. En cas de doute, veuillez prendre contact avec votre fournisseur de compresseur.
Pour davantage d’informations sur les diverses possibi­lités de réglage, voir ci-dessous. Les chires font référence aux chires et aux de la colonne de gauche. L’illustration présente uniquement les installations et les achages nécessaires pour une conguration déterminée.
3 - Mode reference
Référence = point de réglage + décalage nocturne + oset à optimisation P0 Réglage ( -80 á +30°C) Point de réglage pour la pression d’aspiration souhaitée en °C. Oset de nuit (-25 - 25 K) Décalage de la pression de l’évaporateur en régime de nuit (réglé en Kelvin) Le passage au régime de nuit peut être réalisé avec un signal envoyé par la transmission de données, avec un signal sur l'entrée « nuit » ou par la pro­grammation hebdomadaire du régulateur. Référence Max (-50 à +80 °C) Référence maximum de pression d’aspiration autorisée Référence Min (-80 à +25 °C) Référence minimum de pression d’aspiration autorisée
4 - Applications compresseur P0 Type Réfrigérant
Choisissez le réfrigérant.
P0 facteur réfrigérant K1, K2, K3
N’est utilisé que si le réfrigérant ne peut être choisi de la liste (contactez Danfoss pour davantage d’informations)
Mode réglage étage
Choisissez le schéma d’enclenchement pour les compresseurs Premier enclenché, dernier déclenché. (séquentiel) sortie (FILO) (compresseurs de même taille) Égalisation du temps de marche (FIFO) (compres­seurs de tailles diérentes) Best t:: Meilleure adaptation de capacité possible (le moins de sauts de capacité possible)
Pump down
Sélectionnez l’activation ou non d’une fonction pump down au niveau du dernier compresseur Ceci an d'éviter des cycles importants aux com­presseurs. Limite Po Pump down (-80 à +30 °C) Sélectionnez la limite pump down. Vit.mini AKD (0.5 – 60.0 Hz) Vitesse min. à laquelle le compresseur doit s’arrêter. Vit dém AKD (20.0 – 60.0 Hz) Vitesse minimum lorsque le compresseur doit s’en­clencher (doit être réglé sur une valeur supérieure à « vitesse min. VSD »). Vit. Max AKD (40.0 – 120.0 Hz) Vitesse la plus élevée autorisée pour le compresseur
Limites écrêtage
Réglez la capacité max. autorisée lorsqu’un signal est reçu au niveau de l’entrée "Load shed"
Forcage limite P0
Si P0 dépasse la valeur, une temporisation s'en­clenche. Quand la temporisation est expirée, la limitation de charge est neutralisée.
Forcage tempo
Temps max. pour la limitation de capacité si P0 est trop élevé Kp Po (0,1 – 10,0) Facteur d’amplication pour la régulation PI
Réglages avancés
Sélectionnez si les réglages avancés doivent être visibles.
Changement de capacité min. (0 – 100 %)
Réglez le changement de capacité minimum qui doit s’opérer avant que le distributeur de capacité coupe ou enclenche les compresseurs.
Réduc. cycle
La zone de régulation peut changer en fonction des arrêts et des enclenchements. Voir chapitre 5. Durée dém. Initale (15 – 900 s) Temps après démarrage, où la capacité est limitée au premier étage
46 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 47
Conguration - Suite
Appuyez sur le bouton + pour passer à la page suivante.
5. Régler les valeurs de la capacité du compresseur
Appuyez sur le bouton + pour passer à la page suivante.
6. Réglez les valeurs assurant un
fonctionnement sûr
Notre exemple concerne :
- Un compresseur à vitesse commandée de 30 kW (compresseur n° 1)
- 4 compresseurs de 25 kW
Les réglages sont illustrés ici
(Pour un fonctionnement cyclique, tous les compresseurs à un pas présentent la même taille. C'est la raison pour laquelle un seul réglage les couvre tous les 4).
Réglages de notre exemple :
- Limite de sécurité pour la température maximum de la conduite de pression = 120°C
- Limite de sécurité pour la pression de condensation maximum = 50°C
- Limite de sécurité pour la pression d’aspiration minimum = -35°C
- Limite d’alarme pour la pression d’aspiration maximum = -5°C
- Limites d’alarme pour la surchaue minimum et maximum respectivement = 5 et 35 K.
5 - Compresseurs
Est ici dénie la distribution de capacité des compresseurs. Le réglage de capacité est également destiné aux réglages de « l’utilisation du compresseur » et « le schéma d'enclen­chement ».
Cap. nominale (0,0 – 99,9 kW) Réglez la capacité nominale du compresseur. Les compresseurs à vitesse variable doivent avoir réglé la valeur nominale par la fréquence du réseau (50/60 Hz).
6 - Sécurité Temporisation de l'alarme du niveau de liquide
Régler la temporisation (depuis la perte du signal à l'entrée jusqu'à l'envoi de l'alarme)
Temporisation de l'alarme de variateur de vitesse
Régler la temporisation
Limite d'alarme de température
Régler la valeur seuil pour l'alarme de température
Temporisation de l'alarme de température
Régler la temporisation
Capacité d’urgence de jour
Capacité enclenchée souhaitée en régime de jour en cas d’urgence à la suite d’une erreur au niveau du capteur de pression d’aspiration / capteur de température de uide
Capacité d’urgence de nuit
Capacité enclenchée souhaitée en régime de nuit en cas d’urgence à la suite d’une erreur au niveau du capteur de pression d’aspiration / capteur de température de uide
Limitation Sd maximum
Valeur maximale pour la température de refoulement A 10 K sous la limite, la puissance enclenchée diminue et toute la capacité du condenseur s’enclenche. Si la limite est dépassée, toute puissance enclenchée est arrêtée.
Limite Pc maximum
Valeur maximale pour la pression de condenseur en °C. A 3 K sous la limite, toute la capacité du condenseur s’enclen­che et la puissance enclenchée du compresseur diminue. Si la limite est dépassée, toute la capacité du compresseur s’arrête.
Tempo Pc Max
Temporisation pour l’alarme Pc max.
Limite P0 minimum
Valeur minimum pour la pression d’aspiration en °C. Sous cette limite, toute la puissance enclenchée est arrêtée.
Alarme P0 maximum
Limite d’alarme pour une pression d’aspiration élevée P0.
Temporisation P0 maximum
Temporisation avant alarme pour une pression élevée P0.
Temps de redémarrage de sécurité
Temporisation commune avant redémarrage des compres­seurs. (Vaut pour les fonctions "Sd max limit", "Pc max limit" et "P0 min limit").
Alarme SH minimum
Limite d’alarme pour la surchaue minimum d’aspiration.
Alarme SH maximum
Limite d’alarme pour la surchaue maximum d’aspiration.
Temporisation de l’alarme SH
Temporisation avant alarme pour surchaue min./max. d’aspiration.
Appuyez sur le bouton + pour passer à la page suivante.
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 47
Page 48
Conguration - Suite
7. Réglez les temps de marche des compresseurs
Appuyez sur le bouton + pour passer à la page suivante.
8. Réglage des temps de déclen-
chement de sécurité
Réglage du temps de déclenchement (OFF) minimum du relais de compresseur. Réglage du temps d’enclenchement (ON) minimum du relais de compresseur. Réglage de la fréquence des démarrages du compresseur.
7 – Temps anti court cycle
L’on règle ici les temps de marche an d’éviter tout fonction­nement inutile.
Min. OFF time (Temps d'arrêt min)
Temps pendant lequel le compresseur doit tourner au ralenti avant d'être redémarré.
Min. ON time (Temps de marche min.)
Temps pendant lequel le compresseur doit fonctionner avant de pouvoir s'arrêter.
Restart time (Temps de redémarrage)
Intervalle de temps le plus réduit possible entre deux démar­rages consécutifs.
8 – Temps de sécurité Temporisation
Temporisation à partir de la suppression de la sécurité auto­matique et jusqu’au signalement d’une erreur du compres­seur.
Temporisation de redémarrage
Temps minimum pendant lequel un compresseur doit être OK après arrêt de la sécurité. L’on peut ensuite procéder au redémarrage. (Une alarme déclenchée par la fonction de sécurité automatique sera maintenue jusqu'à l'expiration du retard de redémarrage).
En cas de chevauchement des restrictions, le régulateur choisit
la plus longue.
48 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 49
Conguration - Suite
Réglage de la régulation des condenseurs
1. Appel du menu de conguration
2. Choisir Condenseur
3. Réglage du mode de régulation et de la référence
Appuyez sur le bouton + pour passer à la page suivante.
4. Réglage des valeurs de la régula­tion de capacité
Dans notre exemple, la pression de condensation est régulée selon la température extérieure (référence ottante). Les réglages sont illustrés ici.
Notre exemple utilise 6 ventilateurs à régulation etagée.
Les réglages sont illustrés ici, à droite.
3 – Référence PC Choix de référence
Choix de la référence de pression de condensation. Permanente : est utilisée si l’on souhaite une référence xe = « réglage » Flottante : est utilisée si la référence est modiée en fonction du signal de la température extérieure Sc3, entre la “diéren­ce dimensionnée tm K” /”tm K minimum” réglée et la capacité actuelle enclenchée du compresseur.
Réglage
Réglage de la pression de condensation souhaitée en °C Elle doit aussi être réglée lorsque des références ottantes sont utilisées. La valeur est utilisée comme référence si la sonde Sc3 est défectueuse.
Diérence Tm minimum
Diérence moyenne de température minimum entre la température de l’air Sc3 et la température de condensation Pc lorsqu'aucun compresseur n'est en marche.
Diérence Tm dimensionnée
Diérence moyenne de température dimensionnée entre la température de l’air Sc3 et la température de condensa­tion Pc en cas de charge maximum (diérence tm en cas de charge max., généralement de 8 à 15 K).
Référence min.
Référence minimum de pression de condensation admise
Référence max.
Référence maximum de pression de condensation admisee
4 – Régulation de la capacité Méthode de régulation
Choisissez la forme de régulation pour le condenseur. Etage : les ventilateurs se connectent par étage par le biais des sorties relais Etage/vitesse : la capacité du ventilateur est réglée par le biais de la combinaison de la régulation de la vitesse et de la connexion par étage Vitesse : la capacité du ventilateur est réglée par le biais de la régulation de la vitesse (variateur de fréquence).
Stratégie de régulation
Choix de la stratégie de régulation Bande P : la capacité du ventilateur est réglée par le biais de la régulation de la bande P. La bande P est réglée comme ”bande proportionnelle Xp”. Régulation PI : la capacité du ventilateur est réglée par le biais du régulateur PI.
Courbe de capacité
Choix de la forme de la courbe de capacité Linéaire : Même progression dans toute la zone Quadratique : forme quadratique de la courbe, qui donne une progression plus élevée en cas de charges élevées.
Commande démarrage de la vitesse
Vitesse minimum pour démarrer la commande de la vitesse (doit être réglée à une valeur supérieure à “VSD Min. Speed %”)
Commande vitesse minimum
Vitesse minimum à laquelle la commande de la vitesse est arrêtée (charge faible)
Bande proportionnelle Xp
Bande proportionnelle pour régulateur P/PI
Temps d’intégration Tn
Temps d’intégration pour régulateur PI
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 49
Page 50
Conguration - Suite
Conguration des entrées et des sorties
1. Appel du menu de conguration
2. Choisir la conguration I/O (Entrées / sorties)
3. Conguration des sorties
Appuyez sur le bouton + pour passer à la page suivante.
4. Conguration des rien (on/o)
Les sorties sont désactivées par On (relais activé)
!!! Cette alarme a été intervertie, c’est à dire que l’alarme est activée si
la tension d’alimentation du régulateur fait défaut.
Décidez en outre pour chaque entrée si sa destination doit être active lorsqu’elle est fermée ou ouverte. On a choisi ici Ouverture pour tous les circuits de sécurité, c’est à dire que le régulateur reçoit un signal en fonctionnement normal et enregis­tre une erreur si le signal est coupé.
Appuyez sur le bouton + pour passer à la page suivante.
50 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 51
Conguration - Suite
5. Conguration des sorties
analogiques
Appuyez sur le bouton + pour passer à la page suivante.
6. Conguration des entrées
analogiques
La sortie analogique est congurée pour commander la vitesse de compresseur.
Nous congurons les entrées analogiques pour les sondes.
5 - Sorties analogiques
Les signaux possibles sont les suivants : 0 -10 V 2 – 10 V 0 -5 V 1 – 5V
6 - Entrées analogiques
Les signaux possibles sont les suivants : Capteurs de température
• Pt1000
• PTC 1000
Transmetteurs de pres­sion :
• AKS 32, -1 – 6 Bar
• AKS 32R, -1 – 6 Bar
• AKS 32, - 1 – 9 Bar
• AKS 32R, -1 – 9 Bar
• AKS 32, - 1 – 12 Bar
• AKS 32R, -1 – 12 Bar
• AKS 32, - 1 – 20 Bar
• AKS 32R, -1 – 20 Bar
• AKS 32, - 1 – 34 Bar
• AKS 32R, -1 – 34 Bar
• AKS 32, - 1 – 50 Bar
• AKS 32R, -1 – 50 Bar
• AKS 2050, -1 – 59 Bar
• AKS 2050, -1 – 99 Bar
• AKS 2050, -1 – 159 Bar
• Application ratiomé­trique personnalisée : ici, les zones de pressions min. et max. des trans­metteurs sont dénies (lecture de la pression relative)
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 51
Page 52
Conguration - Suite
Réglage des priorités d'alarmes
1. Appel du menu de conguration
2. Choisir priorités d'alarmes
3. Réglage des priorités d'alarme compresseurs
Une alarme est raccordée à bon nombre de fonctions. Ce choix de fonctions et de réglages sous-tend l'accès aux alarmes actuelles. Elles sont indiquées par du texte dans les trois illustrations.
Toutes les alarmes possibles peuvent recevoir une priorité donnée :
• «Haut » est la plus importante
• « Enreg. seul » est la moins importante
• « Inactif » ne donne aucune réaction La corrélation entre réglage et action est indiquée à table.
Réglage Enreg. Relais d'alarme Réseau Dest.
Haut X X X X 1 Médium X X X 2 Bas X X X 3 Enreg.seule-
ment Inactif
Dans l’exemple actuel, nous avons choisi les réglages montrés à a­chage
Aucun Haut Bas - Haut
X 4
AKM
Appuyez sur le bouton + pour passer à la page suivante.
4. Réglage des priorités d’alarmes pour le condenseur
Dans l’exemple actuel, nous avons choisi les réglages montrés à achage
Appuyez sur le bouton + pour passer à la page suivante.
52 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 53
Conguration - Suite
5. Réglage des priorités d’alarmes concer­nant les temperatures et les signaux TOR
Dans l’exemple actuel, nous avons choisi les réglages montrés à gauche
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 53
Page 54
Conguration - Suite
Blocage de la conguration
1. Appel du menu de conguration
2. Choisir de Bloquer/Débloquer conguration
3. Bloqcage de la conguration
Appuyez sur la case en face de Clef conguration.
Choisissez Bloqué.
Appuyez sur OK.
La conguration du régulateur est alors bloquée. Pour modier la con­guration du régulateur, il faut à nouveau débloquer la conguration.
Le régulateur eectue alors une comparaison des fonctions choisies et des entrées et sorties dénies. Le résultat ressort du chapitre suivant où la conguration est contrôlée.
54 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 55
Conguration - Suite
Contrôle de la conguration
1. Appel du menu de conguration
2.Choisir la I/O conguration
3. Contrôle de la conguration des sorties tout ou rien
Pour procéder à ce contrôle, il faut que la conguration soit verrouillée.
(Tout d’abord, lorsque la conguration est verrouillée, tous les réglages pour les entrées et les sorties restent actifs.)
Une erreur est survenue si apparaît à l’écran ce qui suit :
Un 0 - 0 devant une fonction dénie.
Si un réglage est revenu à 0-0, il convient de revérier la conguration
L'erreur est due aux deux modules raccordés au régulateur activé.
Appuyez sur le bouton + pour passer à la page suivante.
4. Contrôle la conguration des Entrées digi­tales
Appuyez sur le bouton + pour passer à la page suivante.
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 55
Page 56
Conguration - Suite
5. Contrôle de la conguration des Sorties analogi­ques
Appuyez sur le bouton + pour passer à la page suivante.
6. Contrôle de la conguration des entrées
analogiques
(Si aucune régulation de la vitesse des ventilateurs de condenseur n'est utilisée, le module et le numéro du point peuvent être 0-0).
56 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 57
Contrôle des connexions
1. Appel du menu de conguration
2. Choisir de I/O état et manuel
Avant de mettre la le régulateur en fonctionnement, il faut contrôler que toutes les entrées et sorties sont raccordées correctement.
Pour procéder à ce contrôle, il faut que la congu­ration soit verrouillée.
3. Contrôle des sorties tout ou rien
Appuyez sur le bouton + pour passer à la page suivante.
4. Contrôle des entrées tout ou rien
Utilisant la commande manuelle de chaque sortie, contrôlez si elle est correctement raccordée
AUTO Sortie réglage de régulateur
MAN OFF Sortie forcée sur OFF
MAN ON Sortie forcée sur ON
Coupez le circuit de sécurité du compresseur 1. Vériez que la diode DI1 du Module d’extension (Module 3) s’éteint.
Vériez que la valeur de l’alarme de la surveillance du compresseur 1 passe à ON.
Contrôlez les autres entrées tout ou rien selon la même méthode.
Appuyez sur le bouton + pour passer à la page suivante.
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 57
Page 58
Contrôle des connexions - Suite
5. Contrôle des sorties analogiques
6. Remise de la commande de la sortie sur automati­que
Réglez la commande de la sortie sur manuel Appuyez sur la case Mode en face de sortie.
Choisissez MAN.
Appuyez sur OK.
Appuyez sur la case Valeur
Choisissez 50%, par exemple.
Appuyez sur OK.
La valeur attendue peut ainsi être mesurée à la sortie : dans notre exemple, 5 V.
Exemples de rapport entre le signal de sortie déni et une valeur déterminée manuellement.
Dénition Réglage
0 % 50 % 100 %
0 - 10 V 0 V 5 V 10 V 1 - 10 V 1 V 5,5 V 10 V 0 - 5 V 0 V 2,5 V 5 V 2 - 5 V 2 V 3,5 V 5 V
Appuyez sur le bouton + pour passer à la page suivante.
7. Contrôle des entrées analogiques
Vériez que toutes les sondes indiquent des valeurs raisonnables. Dans ce cas, il n’y a aucune valeur pour la température d’aspiration Ss et deux autres sondes. Ceci est probablement dû aux causes suivantes :
• Sonde non raccordée.
• Sonde court-circuitée.
• Numéros de point ou de module incorrectement congurés.
• La conguration n’est pas verrouillée.
58 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 59
Contrôle des réglages
1. Appeler l’écran général
2. Choisir le groupe de compresseurs
Avant que la commande ne commence, nous contrôlons que tous les réglages correspondent à ce que l'attend.
L’écran général montre, ligne par ligne, chacune des fonctions supérieur­es. Derrière chaque icône se trouve un certain nombre d’écrans montrant les diérents réglages. Voilà les réglages à contrôler.
3. Continuer à travers les diérentes images pour le groupe d’aspiration.
Utiliser le bouton + pour passer d’un écran à l’autre- Ne pas oublier les réglages au pied des pages – ceux qu’il faut montrer avec la bande de délement («Ascenseur»).
4. Limites de sécurité
5. Pour retourner à l’écran général
La dernière page présente les limites de sécurité et les délais de redémarrage.
6. Choix du groupe de condenseurs
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 59
Page 60
Contrôle des réglages - suite
7. Continuer à travers les diérentes images pour le groupe de condenseurs.
Utiliser le bouton + pour passer d’un écran à l’autre. Ne pas oublier les réglages au pied des pages – ceux qu’il faut montrer avec la bande de délement («Ascenseur »).
8. Limites de sécurité
La dernière page présente les limites de sécurité et les délais de redémarrage.
9. Fin du contrôle
60 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 61
Schéma fonctionnel
1. Appel du menu de conguration
2. Choix du schéma fonctionnel
À titre d'information Ce réglage n'est pas nécessaire dans l'exemple. Le signal entre via DI8.
3. Réglage du schéma
Avant de démarrer la commande, il faut régler la fonction du schéma pour l’augmentation nocturne de la pression d’aspiration.
Dans d’autres cas où le régulateur fait partie d’un réseau comprenant une unité de commande, ce réglage peut être fait dans cette unité qui envoie alors le signal jour/nuit au régulateur.
Ce réglage peut être utilisé uniquement si le régulateur est seul et installé avec un module d'horloge.
Cliquez sur un jour de la semaine et réglez la durée de la période diurne. Passez ensuite aux autres jours.
L’illustration ici à droite montre le déroulement d’une semaine entière.
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 61
Page 62
Installation du réseau LON
1. Réglage de l’adresse (3)
Tournez le sélecteur d’adresse droit pour que la èche pointe sur 3. La èche des deux autres sélecteurs d’adresse doit pointer sur
0.
2. Utilisation du Service Pin
Appuyez sur le bouton Service Pin et maintenez-le enfoncé jusqu’à ce que la diode Service Pin s’allume.
Le régulateur doit être surveillé par un réseau. Dans ce réseau, le régulateur reçoit l’adresse « 3 ».
Cette adresse ne peut être donnée à d’autres régulateurs du même réseau.
Conditions imposées à l’unité système
Il faut une passerelle AKA 245 avec logiciel version 6.0 ou plus récent, avec la possibilité de se connecter jusqu’à 119 régulateurs AK.
3. Attendre la résponse de l’unité
Suivant l'importance du réseau de l’importance du réseau, le régulateur doit parfois patienter jusqu’à une minute avant de recevoir le signal de l’installation sur le réseau. Après l’installation, la diode Status (état) se met à clignoter rapidement (deux clignotements par seconde). Cette fréquence continue pendant dix minutes environ.
4. Nouvel accès (Login) par l’outil Service Tool
Si le Service Tool était déjà raccordé au régulateur pendant l’installation sur le réseau, il faut procéder à un nouveau Login pour accéder au régulateur par le Service Tool.
Ou éventuellement un AK-SM 720. Il régule jusqu’à 200 régulateurs AK.
En cas de non-réponse de l’unité
Si la diode Status (état) ne clignote pas plus rapidement que normale­ment, le régulateur n’a pas été installé sur le réseau. Parmi les causes probables, citons :
Adresse incorrectement réglée:
L’adresse 0 n’est pas utilisable. Si l’unité du réseau est une passerelle AKA 243B, seules les adresses de 1
à 10 conviennent.
L’adresse choisie est déjà utilisée par un autre régulateur ou une autre unité du réseau : Il faut utiliser une autre adresse (libre).
Le câblage n’est pas correct. Le raccordement n’est pas correct :
Les conditions préalables à la transmission de données sont expliquées dans ce document : « Câbles de transmission de données pour les com­mandes frigoriques ADAP-KOOL® .
62 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 63
Démarrage initial du régulateur
Contrôle des alarmes
1. Appel de l’écran général
Appuyez sur le bouton bleu (compresseur et condenseur) en bas à gauche de l’écran.
2. Appel de la liste des alarmes
Appuyez sur le bouton bleu (cloche d’alarme) en bas de l’écran.
3. Contrôle des alarme actives
Dans notre cas, nous avons une série d’alarmes. Nous procédons à un nettoyage de façon à n’avoir que les alarmes actuelles.
4. Eliminer les alarmes disparues de la liste
Appuyez sur la croix rouge pour éliminer les alarmes annulées de la liste.
5. Nouveau contrôle des alarmes actives
Dans notre cas, une alarme active persiste parce que le régulateur est à l’arrêt. Cette alarme doit être active lorsque le régulateur est à l’arrêt. Le régula­teur est alors prêt au démarrage.
Notez que les alarmes actives dans l’installation sont automatiquement annulées si l’interrupteur général est mis à OFF. En cas d’alarme lors de la mise en route du régulateur, il faut en trouver la cause et réparer.
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 63
Page 64
Démarrage initial du régulateur - Suite
Démarrage du régulateur
1. Appel de l’écran Start/Stop
Appuyez sur le bouton bleu en bas de l’écran.
2. Démarrer le régulateur
Appuyez sur la case en face de Inter. général Choisissez ON.
Appuyez sur OK.
Le régulateur démarre alors les compresseurs et les ventilateurs.
NB : Le régulateur peut démarrer lorsque les deux commutateurs, interne et externe, sont positionnés sur « ON ».
64 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 65
Marche manuelle
1. Appel de l’écran général
2. Choisir le groupe de compresseurs
Appuyez sur le bouton en face du groupe à régler manuelle-
ment.
Appuyez sur le bouton + pour passer à la page suivante.
3. Mise sur marche manuelle
S’il y a besoin d’une commande manuelle de la capacité des compres­seurs, procédez ainsi :
Appuyez sur la case bleue en face de Mode régulation. Choisissez MAN. Appuyez sur OK.
4. Inscrire la capacité en pourcentage
Appuyez sur la case bleue en face de Capacité manuelle.
Réglez la capacité sur le pourcentage désiré. Appuyez sur OK.
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 65
Page 66
Contrôle des réglages - suite
Conguration rapide
Il est recommandé à l'installateur familiarisé avec le régula­teur de suivre la procédure suivante :
1. Déverrouiller la conguration
2. Sélectionner l'application (l'outil Service tool qui se
ferme ensuite)
3. Sélectionner le uide frigorigène
4. Dénir les tailles de compresseur (uniquement s'ils sont
diérents)
5. Verrouiller la conguration
6. Vérier les entrées et les sorties
7. Allumer l'interrupteur principal.
66 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 67
Contrôle des réglages - suite
EKA 164, EKA 166 ou AKM commande
Les fonctions du régulateur telles qu'elles apparaissent sur l'écran EKA 164 et via le logiciel du système de type AKM sont présentées dans les pages suivantes. Pour accéder aux paramètres, appuyer sur le bouton du haut et le maintenir enfoncé.
EKA-text AKM text R/W Description / Parameter Range Default
Reference
r01 Neutral zone K W Width of neutral zone for compressor control 0,1 – 20,0 K 6,0 K
r04 Po sensor adjust W Calibration of Po sensor -10,0 - 10,0 Bar 0,0 bar
r12 Main switch W "Main switch for start/stop of control
ON: Normal control OFF: Control is stopped"
r13 Night oset K W Displacement value for suction pressure in con¬nection with an active
night setback signal (set in Kelvin)
r23 Po setpoint °C W Setting of required reference pressure in °C -80,0 °C - 30,0 °C -15,0 °C
r24 Comp. ctrl. Ref. °C R Actual reference temp. for compressor capacity (incl. external reference
signal, if any)
r25 Max reference °C W Max. permissible suction pressure reference -50,0 °C - 80,0 °C 80,0 °C
r26 Min Reference °C W Min. permissible suction pressure reference -80,0 °C - 25,0 °C -80,0 °C
r27 Night setback R Actual status of night setback ON/OFF
r28 Pc setpoint °C W Setting of desired condensing pressure in °C -25,0 °C - 90,0 °C 35,0 °C
r29 Cond. ctrl. Ref. °C R Reference for condenser in °C
r30 Min Reference °C W Min. permitted condenser pressure reference -25,0 °C - 100,0 °C 10,0 °C
r31 Max Reference °C W Max. permitted condenser pressure reference -25,0 °C - 100,0 °C 50,0 °C
r32 Pc sensor adjust W Calibration of Pc sensor -10,0 - 10,0 Bar 0,0 bar
r33 Pc Reference mode W "Choice of condenser pressure reference
0: Reference = Pc setpoint 1: The reference is changed as a function of Sc3 the external temperature signal"
r35 Dimensioning tm K W Dimensioning mean temperature dierential between Sc3 air and Pc
condensing temperature at maximum load (compressor capacity = 100%). Dimensioning temp dierence at max load, typically 8-15 K).
r56 Min tm K W Minimum mean temperature dierence between Sc3 air and Pc condens-
ing temperature at no load (Compressor capacity = 0%)
r57 Po °C R Suction pressure in °C. (Measured with the Po pressure transmitter)
Capacity control
c08 Step mode W "Select coupling pattern for compressors
0: Sequential: Compressors are cut in/out in strict ac¬cordance with com­pressor number (FILO) 2: Cyclic: Runtime equalisation between compressors (FIFO) 3: Best t: Compressors are cut in/out in order to make the best possible t to actual load"
c10 + Zone band K W Width of “+ Zone” above neutral zone 0,1 – 20,0 K 4,0 K
c11 + Zone delay s W Integrationtime in ”+ Zone” 10,0 – 900,0 s 300 s
c12 ++ Zone delay s W Integrationtime in ”++ Zone” 10,0 – 900,0 s 300 s
c13 - Zone band K W Width of “- Zone” below neutral zone 0,1 – 20,0 K 3,0 K
c14 - Zone delay s W Integrationtime in ”- Zone” 10,0 – 900,0 s 150 s
c15 -- Zone delay s W Integrationtime in ”-- Zone” 1,0 – 300,0 s 30 s
c16 Comp. application R Readout compressor combinations 0: Single step only
c29 No. of fans R Read out number of fans 0 - 6 0
c31 Manual capacity % W "Manual setting of compressor capacity
The value is in % of total capacity controlled by the controller"
c32 Cap. control mode W Select whether capacity control is stopped, in manual control or controlled
via PI controller
c33 Po pump down limit°C W Set the actual pump down limit for the last compressor -80,0 °C - 30,0 °C -40,0 °C
c35 Load shed limit 1 W Set max compressor capacity limit for load shed input 0 - 100% 100%
"ON: Normal control OFF: Control is stopped"
-25,0 - 25,0 K 0,0 K
"0: Pc setpoint 1: Floating"
0,0 - 25,0 K 15,0 K
0,0 - 20,0 K 6,0 K
"0: Sequential 2: Cyclic 3: Best t "
4: 1 x variable speed + single step
0 - 100% 0%
0: Manual control 1: OFF 2: Auto
OFF
1: Floating
2: Cyclic
0: Single step only
2: Auto
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 67
Page 68
Contrôle des réglages - suite
c36 Override limit Po W Any load below the limit value is freely permitted. If the suction pressure
Po exceeds the value, a time delay is started. If the time delay runs out, the load limit is cancelled
c37 Override delay 1 min W Max. time for capacity limit, if Po is too high 0 - 240 min 10 min
c38 Pump down W Select whether a pump down function is required on the last running
compressor
c39 Initial start time W The time after start-up where the cut-in capacity is limited to the rst
compressor step.
c40 Compressor 1 size W "Set the nominal capacity for the compressor in question.
For compressors with variable speed drive the nominal capacity must be set for the mains frequency (50/60 Hz) Set the nominal capacity for the compressor in question."
c41 Compressor 2 size W Set the nominal capacity for the compressor in question. 0,0 - 99,9 kW 0 kW
c42 Compressor 3 size W Set the nominal capacity for the compressor in question. 0,0 - 99,9 kW 0 kW
c43 Compressor 4 size W Set the nominal capacity for the compressor in question. 0,0 - 99,9 kW 0 kW
c44 Compressor 5 size W Set the nominal capacity for the compressor in question. 0,0 - 99,9 kW 0 kW
c45 Compressor 6 size W Set the nominal capacity for the compressor in question. 0,0 - 99,9 kW 0 kW
c46 VSD Min speed Hz W Min. speed where the compressor must cutout 0,5 Hz 60,0 Hz
c47 VSD Start speed Hz W Minimum speed for start of Variable speed drive (Must be set higher than
“VSD Min. Speed Hz”)
c48 VSD Max speed Hz W Highest permissible speed for the compressor motor 40,0 Hz 120,0 Hz
c49 Emergency cap day% W The desired cut-in capacity for daily use in the case of emer¬gency opera-
tions resulting from error in the suction pressure sensor/ media tempera­ture sensor
c50 Emergency cap. night% W The desired cut-in capacity for night operations in the case of emergency
operations resulting from error in the suction pressure sensor/ media temperature sensor.
Compressor timers
c51 Comp. 1 Min. ON-time W Minimum duration of ON period 0 - 60 min 0 min
c52 Comp. 2 Min. ON-time W Minimum duration of ON period 0 - 60 min 0 min
c53 Comp. 3 Min. ON-time W Minimum duration of ON period 0 - 60 min 0 min
c54 Comp. 4 Min. ON-time W Minimum duration of ON period 0 - 60 min 0 min
c55 Comp. 5 Min. ON-time W Minimum duration of ON period 0 - 60 min 0 min
c56 Comp. 6 Min. ON-time W Minimum duration of ON period 0 - 60 min 0 min
c57 Comp. 1 Min. OFF-time W Minimum duration of OFF periode 0 - 30 min 0 min
c58 Comp. 2 Min. OFF-time W Minimum duration of OFF periode 0 - 30 min 0 min
c59 Comp. 3 Min. OFF-time W Minimum duration of OFF periode 0 - 30 min 0 min
c60 Comp. 4 Min. OFF-time W Minimum duration of OFF periode 0 - 30 min 0 min
c61 Comp. 5 Min. OFF-time W Minimum duration of OFF periode 0 - 30 min 0 min
c62 Comp. 6 Min. OFF-time W Minimum duration of OFF periode 0 - 30 min 0 min
c63 Comp. 1 Recycle time W Minimum period between two succecive compressor starts 1 - 60 min 6 min
c64 Comp. 2 Recycle time W Minimum period between two succecive compressor starts 1 - 60 min 6 min
c65 Comp. 3 Recycle time W Minimum period between two succecive compressor starts 1 - 60 min 6 min
c66 Comp. 4 Recycle time W Minimum period between two succecive compressor starts 1 - 60 min 6 min
c67 Comp. 5 Recycle time W Minimum period between two succecive compressor starts 1 - 60 min 6 min
c68 Comp. 6 Recycle time W Minimum period between two succecive compressor starts 1 - 60 min 6 min
Neutral zone control
n04 Xp P-band K W Proportional band for condenser P/PI controller 0,0 - 100,0 K 10,0 K
n05 Tn Integr. time s W Integration time for condenser PI controller 30 - 600 sec 180 sec
n20 Kp Po W Ampliication factor for compressor capacity control 0,1 - 10,0 2
n52 Control mode W "0: MAN (The condenser capacity will be controlled manually)
1: OFF (The capacity control will be stopped) 2: AUTO (The capacity is controlled by the PI controller)"
n53 Manual capacity % W Manual setting of condenser capacity 0 - 100% 0%
n54 VSD Start speed % W Condenser minimum speed for start of speed control (Must be congu¬red
higher than "VSD Min. Speed %")
n55 VSD Min. speed % W Condenser minimum speed whereby speed control is cut-out (low load). 0,0 - 40,0 % 10,0%
-50,0 °C - 80,0 °C 80,0 °C
0: No 1: Yes
0 - 900 sec 120 sec
0,0 - 99,9 kW 0 kW
20,0 Hz 60,0 Hz
0 - 100% 50%
100% 25%
0: Manual control 1: OFF 2: Auto
0,0 - 40,0 % 20,0%
0: No
2: Auto
68 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 69
Contrôle des réglages - suite
n94 Step/speed W "Select control mode for condenser
0: Step: Fans are step-connected via relay outputs 1: Step/speed: The fan capacity is controlled via a combination of speed control and step coupling 2: Speed: The fan capacity is controlled via speed control (frequency converter)"
n95 Control type W "Choice of control strategy for condenser
0: P-band: The fan capacity is regulated via P-band control. The P band is congured as ""Proportional band Xp"" 1: PI-Control: The fan capacity is regulated by the PI controller"
Alarm/Safety Settings
A03 Saux 1 High alarm del W Alarm delay for high Saux temperature 0 - 360 min 5 min
A10 Po Max alarm °C W Alarm limit for high suction pressure Po -30,0 °C - 100,0 °C 100,0 °C
A11 Po Min limit °C W "Minimum value for the suction pressure in °C
If the limit is reduced, the entire compressor capacity will be cutout."
A28 Low liquid level delay W Time delay for the low liquid level alarm 0 - 360 min 5 min
A30 Pc Max limit °C W "Maximum value for the condenser pressure in °C
3 K below the limit, the entire condenser capacity will be cutin and the compressor capacity reduced. If the limit is exceeded, the entire compressor capacity will be cutout."
A35 Saux 1 High alarm °C W High temp. alarm limit for Saux sensor -80,0 °C - 120,0 °C 120,0 °C
A44 Po Max delay m W Time delay before alarm for high suction pressure P0. 0 - 240 min 5 min
A45 Pc Max alarm delay m W Time delay for the alarm Pc max 0 - 240 min 0 min
A58 Sd max limit°C W "Max. value for discharge gas temperature
10 K below the limit, the compressor capacity should be reduced and the entire condenser capacity will be cutin. If the limit is exceeded, the entire compressor capacity will be cutout"
A59 SH min alarm K W Alarm limit for min. superheat in suction line. 0,0 - 20,0 K 0,0 K
A60 SH max alarm K W Alarm limit for max. superheat in suction line. 20,0 - 80,0 K 80,0 K
A61 SH alarm delay W Time delay before alarm for min./max. superheat in suction line. 0 - 60 min 5 min
A62 Safety restart time m W "Common time delay before restarting the compressor.
(Applicable to the functions: ""Sd max. limit"", Pc max. limit"" and ""P0 min. limit)."
A64 VSDcutoutDel W Time delay before VSD alarm 0-360 min 5 min
Misceallanous
o12 Mains frequency W Select frequency of the power supply 0: 50 Hz
o19 No. of compressors R Readout number of compressors 0 - 6 0
o21 Po sensor W Select sensor type for Po
0: User dened, 1=AKS32-6, 2=AKS32R-6, 4=AKS32-9, 5=AKS32R-9, 7=AKS32-12, 8=AKS32R-12, 10=AKS32-20, 11=AKS32R-20, 13=AKS32-34, 14=AKS32R-34, 16=AKS32-50, 17=AKS32R-50, 31=AKS2050-59, 32=AKS2050-99, 33=AKS 2050-159
o23 Comp. 1 Runtime W Compressor’s total run time in hours 0 - 999999 h 0 h
o24 Comp. 2 Runtime W Compressor’s total run time in hours 0 - 999999 h 0 h
o25 Comp. 3 Runtime W Compressor’s total run time in hours 0 - 999999 h 0 h
o26 Comp. 4 Runtime W Compressor’s total run time in hours 0 - 999999 h 0 h
o30 Refrigerant type W Select refrigerant type for Po
1=R12, 2=R22, 3=134a, 4=R502, 5=R717, 6=R13, 7=R13b1, 8=R23, 9=R500, 10=R503, 11=R114, 12=R142b, 13=User def., 14=R32, 15=R227, 16=R401A, 17=R507, 18=R402A, 19=R404A, 20=R407C, 21=R407A, 22=R407B, 23=R410A, 24=R170, 25=R290, 26=R600, 27=R600a, 28=R744, 29=R1270, 30=R417A. 31=R422A, 32=R413A, 33=R422D, 34=R427A, 35=R438A, 36=XP10, 37=R407F
o48 Pc sensor W Select sensor type for Po
0: User dened, 1=AKS32-6, 2=AKS32R-6, 4=AKS32-9, 5=AKS32R-9, 7=AKS32-12, 8=AKS32R-12, 10=AKS32-20, 11=AKS32R-20, 13=AKS32-34, 14=AKS32R-34, 16=AKS32-50, 17=AKS32R-50, 31=AKS2050-59, 32=AKS2050-99, 33=AKS 2050-159
o50 Comp. 5 Runtime W Compressor’s total run time in hours 0 - 999999 h 0 h
o51 Comp. 6 Runtime W Compressor’s total run time in hours 0 - 999999 h 0 h
o61 Quick setup select W "Select a predened application.
Gives a choice between a number of prede¬ned applicatons, which at the same time determine the wiring connection points. (see manual for further details)"
o93 Conguration lock W The controller can only be congured when it is unlocked. 0: Unlocked
0: Step control 1: Step/Speed 2: Speed
0: P-band control 1: PI control
-120,0 °C - 30,0 °C -40,0 °C
-30,0 °C - 100,0 °C 50,0 °C
-0,0 °C - 150,0 °C 80,0 °C
0 - 60 min 5 min
1: 60 Hz
0-33 8
0: None 37
0-33 14
See documenation for quick selections
1: Locked
0: Step
1: PI control
0: 50 Hz
0: None selected
0: Unlocked
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 69
Page 70
Contrôle des réglages - suite
P40 Auto ack alarms W Select whether the controller should auto acknowledge alarms. In stand
alone applications it should be set to Enabled
Service
u01 Pc °C R Condensing pressure in °C. (measured with the Pc pressure transmitter)
u03 Saux 1 °C R Air temp Saux temperature in °C
u10 Lowliquid level alarm R Actual status of low liquid alarm ON/OFF
u21 Suction superheat K R Superheat in suction line
u37 Common fan safety R Actual status of common fan safety input ON/OFF
u44 Sc3 Air on °C R Outdoor temperature in °C measured with Sc3 temperature sensor
u48 Condenser status R Actual control status of condenser
0=Power up 1=Stopped 2=Manual 3=Alarm 4=Restart 5=Standby 10=Full loaded 11=Running
u49 Cond. Cap % R Cut-in condenser capacity in % (of total capacity) 0-100%
u50 Request Cond. Cap % R Reference for condenser capacity 0-100%
u51 Suction status R Actual control status of suction group
0=Power up 1=Stopped 2=Manual 3=Alarm 4=Restart 5=Standby 10=Full loaded 11=Running
u52 Compressor Cap % R Cut-in compressor capacity in % (of total capacity) 0-100%
u53 Request Comp. Cap % R Reference for compressor capacity (deviations may be due to time delays) 0-100%
u54 Sd discharge gas °C R Discharge gas temperature in °C
u55 Ss suction gas °C R Suction gas temperature in °C
u87 Load shed input 1 R Actual status on Load shed input ON/OFF
u88 HP common safety R Actual status of common HP safety input for all compressors ON/OFF
u89 LP common safety R Actual status of common LP safety input for all compressors ON/OFF
U12 Actual setup R Actual selected quic setup See documenation
U13 Injection ON R Status of the “Injection ON” function ON/OFF
0: Enabled 1: Disabled
for quick selections
1: Disabled
70 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 71
Contrôle des réglages - suite
Alarms
A02 Low suction pressure Po Minimum safety limit for suction pressore Po has been violated
A11 Refrigerant A not selected Refrigerant has not been selected
A17 High Cond. pressure Pc High safety limit for condensing pressure Pc has been violated
A19 Comp. 1 safety cutout Compressor no. 1 has been cut out on safety input
A20 Comp. 2 safety cutout Compressor no. 2 has been cut out on safety input
A21 Comp. 3 safety cutout Compressor no. 3 has been cut out on safety input
A22 Comp. 4 safety cutout Compressor no. 4 has been cut out on safety input
A23 Comp. 5 safety cutout Compressor no. 5 has been cut out on safety input
A24 Comp. 6 safety cutout Compressor no. 6 has been cut out on safety input
A28 Low liquid level Low liquid level alarm input has been activated
A31 LP common safety Compressors have been cut out on common LP safety input
A32 HP common safety Compressors have been cut out on common HP safety input
A34 Common fan safety Common fan safety input has been activated
A35 Air room High temp. The temperature measured by Saux 1 sensor is too high
A45 Main switch Control has been stopped via the setting ”Main Switch” = OFF or via the
A85 High discharge temp. Sd Safety limit for discharge temperature has been exceeded
A86 High superheat Ss Superheat in suction line too high
A87 Low superheat Ss Superheat in suction line too low
A88 System Critical excep-
tion #1
A89 Manual DI………. An input has been set in manual control mode via the service tool software
A93 VSD safety cutout VSD alarm input has been activated
E02 Po sensor error Pressure transmitter signal from Po defective
Ss sensor error Temperature signal from Ss suction gas temp. defective
Sd sensor error Temperature signal from Sd discharge gas temp. Sd defective
Pc sensor error Pressure transmitter signal from Pc defective
Sc3 sensor error Temperature signal from Sc3 air on condenser defective
Saux1 sensor error Signal from extra temp. sensor Saux1 defective
System alarm excep­tion #1
Alarm Destination disabled
Alarm Route failure Alarms can not be send to the alarm receiver – check the communication
Alarm Router full The internal buer for alarm has been exceeded. This can happen if the
Device is restarting Restart of controller after a ash update of the software
Common IO Alarm A communication problem has arised between the controller and the
Manual DO……… An output has been set in manual control mode via the service tool
- - 1 Initialisation. L'acheur est connecté à la sortie A. (- - 2 = sortie B, etc.)
external main switch input
A critical system fault has arisen – the controller needs to be exchanged
A minor system fault has arisen – power OFF/ON the controller
When this alarm is active the alarm transmission to the alarm receiver has been disabled. When the alarm is cancelled the alarm transmission is enabled
to controller/alarm receiver
alarm transmission to the alarm receiver is interrupted – see above.
extension modules – the problem should be checked immediately
software
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 71
Page 72
72 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 73
5. Fonction de régulation
Ce chapitre décrit le fonctionnement des diverses fonctions.
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 73
Page 74
Groupe d'aspiration
Capteur de régulation
Le distributeur de capacité peut se réguler selon la pression d'as­piration P0.
Décalage nocturne
Cette fonction est utilisée si les meubles frigoriques sont cou­verts la nuit. Elle permet de décaler la référence d’un maximum de + ou -25 K. (On obtient une pression d’aspiration plus élevée en inscrivant une valeur positive.) Trois méthodes permettent d’actionner le décalage :
• un signal sur une entrée
• à partir de la fonction régulation d’une passerelle maître
• selon un schéma horaire interne
La fonction « décalage nocturne » ne doit normalement pas être utili­sée en cas de régulation à l’aide de la fonction de forçage « optimisa­tion P0 ». (La fonction de régulation règle d’elle-même la pression
d’aspiration au maximum admissible.)
En cas d’utilisation d’un changement bref au niveau de la pression d’aspiration (par ex. jusqu’à 15 min., dans le cadre d’un dégivrage), les fonctions peuvent être utilisées.En l’occurrence, l’optimisation P0 ne parviendra pas à compenser le changement.
Régulation d’erreurs de capteur
Une faute de signal engendrera une régulation ultérieure avec 50 % d’enclenchement en régime de jour et 25 % d’enclenchement en régime de nuit – toutefois un étage minimum.
Référence
P0Ref = Réglage P0 + optimisation P0 + décalage nocturne
Réglage de la P0
On règle une valeur de base pour la pression d’aspiration.
Optimisation de la P0
Cette fonction permet de régler la référence pour éviter une pression d’aspiration inférieure au niveau nécessaire. Cette fonc­tion travaille avec les régulateurs des meubles individuels et une system manager. La system manager collecte les données des diérents régulateurs adaptant la pression d’aspiration au niveau optimal du point de vue énergétique. Pour plus de détails, repor­tez-vous au manuel de system manager. La fonction permet aussi d’indiquer le meuble actuellement le plus défavorisé et le décalage admis pour la référence de pression d’aspiration.
Limitation de la référence
Pour éviter une référence trop éle­vée ou trop basse, il faut la limiter.
P0 ref
Max.
Min.
Commande forcée de la capacité du groupe d’aspiration
Une commande forcée de la capacité permet de négliger la régu­lation normale. Dépendant de la forme de commande forcée choisie les fonctions de sécurité seront annulées.
Commande forcée via le forçage de la capacité souhaitée
La régulation se règle sur manuel et la capacité souhaitée se dé­nie en % de la capacité possible du compresseur.
Commande forcée via le forçage de la sortie numérique
Chacune des sorties peuvent être mises en MAN ON ou MAN OFF dans le logiciel. La fonction de régulation ne s’en préoccupe pas mais une alarme est émise comme quoi la sortie subit une commande forcée.
Commande forcée par les commutateurs
Si la commande forcée est engagée avec les commutateurs sur face avant du Module d’extension, ce ne sera pas enregistré par la fonction de régulation et il n’y aura donc aucune alarme. Le régu­lateur continue de fonctionner et enclenche avec les autres relais.
74 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 75
Régulation de la capacité des compres­seurs
Commande PI et zones de pilotage
AK-PC 710 peut piloter jusqu’à 6 compresseurs. Un compresseur peut être équipé de vitesse variable.
Le calcul de la capacité souhaitée du compresseur s’eectue à partir d’une commande PI mais l’installation se réalise de la même manière qu’avec une zone neutre divisée en 5 zones diérentes de pilotage comme illustré ci-dessous.
Suction pressure P0
La largeur des zones peuvent être dénies via les réglages “Zone+ K”, “ZN K” et “Zone - K”. En outre, il est possible de disposer des temps de zones égaux aux temps d’intégration Tn pour le régulateur PI, quand la pression d'aspiration se trouve dans la zone concernée (voir l’ illustration ci-dessus).
Si le temporisateur de zone est réglé sur une valeur supérieure, le régulateur de PI fonctionne alors plus lentement dans cette zone, mais s’il est réglé sur une valeur inférieure alors le régulateur fonc­tionnera plus rapidement dans cette zone.
augmenter la capacité souhaitée puisque la pression d'aspiration se trouve au-dessus du point xé. Mais si la pression d'aspiration retombe très rapidement, la capacité souhaitée peut être abaissée également dans ces zones.
En“Zone -” et “Zone - -” le régulateur devrait normalement dimi­nuer la capacité souhaitée puisque la pression d'aspiration se trouve en-dessous du point xé. Mais si la pression d'aspiration monte très rapidement, la capacité souhaitée peut être augmen­tée également dans ces zones.
Modication de capacité
Le régulateur enclenche ou déclenche la capacité à partir de ces règles fondamentales :
Augmenter la capacité : Le distributeur de capacité sollicite alors une capacité du compresseur supplémentaire dès que la capacité souhaitée a augmenté jusqu’à une valeur qui permet au prochain étage de compresseur de démarrer. En référence à l’exemple qu’on trouvera ci-dessous – un étage de compresseur est ajouté dès qu’il y a de la ”place” pour ce étage de compresseur compris dans la courbe de capacité souhaitée.
Diminuer la capacité : Le distributeur de capacité stoppe alors un étage de compresseur dès que la capacité souhaitée est retombée jusqu’à une valeur qui permet au prochain compresseur de s’arrêter. En référence à l’exemple qu’on trouvera ci-dessous – un étage de compresseur est stoppé dès qu’il n’ y a plus de ”place” pour étage de compres­seur au-delà de la courbe de capacité souhaitée.
Exemple : 4 compresseurs de même taille – la courbe de capacité aura le prol suivant :
Le facteur de renforcement Kp s’ajuste comme paramètre ”Kp Po” Dans la zone neutre, le régulateur ne peut augmenter ou diminuer sa capacité qu’à l’aide de la vitesse variable et/ou de commutation des vannes de régulation de capacité. Dans les autres zones, le régulateur ne peut qu’augmenter ou diminuer sa capacité par démarrage ou arrêt des compresseurs.
Temps de marche, premier étage
Pour un démarrage, le dispositif de refroidissement doit avoir le temps de s'arrêter avant que le régulateur PI prenne le relais. A cet égard, on a prévu au démarrage de l'appareil une limitation de capacité de telle sorte que seul le premier niveau de capacité soit enclenché pour une période de temps bien déterminée (peut être dénie via ”premier niveau de temps de marche”).
Capacité souhaitée
L’achage ”capacité souhaitée” vient du régulateur PI et il indique la capacité réelle du compresseur que le régulateur PI souhaite. Le changement de vitesse dans la capacité souhaitée dépend de quelle zone la pression se trouve et dans quelle mesure la pression est constante ou bien varie constamment.
L’intégrateur n’observe que l’écart entre le point xé et la pression réelle et alors augmente /diminue la capacité souhaitée en consé­quence. Le facteur proportionnel Kp, pour sa part ne considère que les variations de pressions temporaires.
En “Zone +” et “Zone ++” le régulateur devrait normalement
Arrêt du dernier étage du compresseur : Normalement, le dernier étage du compresseur sera enclenché en premier lorsque la capacité souhaitée est de 0 % et que la pression d'aspiration se situe dans la « - Zone » ou dans la « —Zone ».
La fonction pump down :
Pour éviter trop de démarrage/arrêt du compresseur en cas de charge faible, il est possible de dénir une fonction pump down pour le dernier compresseur.
Tant que la fonction pump down est utilisée, les compresseurs resteront éteints si la pression d’aspiration à ce moment-là est à la limite pump down réglée.
Remarquez que la limite pump down dénie doit être réglée de façon à être supérieure à la limite de sécurité dénie pour la pres­sion d’aspiration basse ”Min Po”.
Remarquez que la limite pump down dénie doit être réglée de façon à être supérieure à la limite de sécurité dénie pour la pres­sion d’aspiration basse ”Min Po”.
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 75
Page 76
Extension dynamique des zones :
Tous les systèmes de refroidissement ont un temps de réaction dynamique quand ils démarrent ou arrêtent les compresseurs. Pour éviter que le régulateur démarre/arrête le compresseur peu de temps les uns après les autres, il faut donner au régulateur du temps supplémentaire après démarrage/arrêt d’un compresseur pour voir l’impact du changement précédant dans l’exploitation de capacité.
Pour obtenir ceci on a ajouté un élargissement dynamique des zones à l’élargissement xe des zones cité précédemment.
Bande actuelle
Suite à l’extension dynamique des zones, la pression d’aspiration peut bien se modier pendant une période quand le régulateur démarre/stoppe un compresseur, c.a.d. la pression d’aspiration est en Zone+, mais quand le régulateur démarre un compresseur les zones sont étendues pendant un certain temps et pendant ce laps de temps la pression d’aspiration est dans les limites de ZN.
Au régulateur, la lecture de ”bande actuelle” montrera dans quelle zone le régulateur PI travaille – ceci comprend l’extension des zones.
Les zones seront élargies un court laps de temps quand un com­presseur est démarré ou stoppé. En élargissant les zones, la vitesse du régulateur PI est ralentie pendant un court laps de temps après un changement de capacité de compresseur.
L’amplitude de l’élargissement de zone dépend de la capacité du compresseur qui est réellement en fonction ainsi que de la taille de l’étage du compresseur devant être stoppé/démarré. L’ampli­tude de l’élargissement de zone est plus grande quand on tourne avec une capacité de compresseur faible et quand des étages im­portants de la capacité de compresseur sont arrêtés/démarrés. Le laps de temps de l’élargissement de zone est cependant constant – après un laps de temps xe après le démarrage/arrêt d’un com­presseur, l’élargissement de zone dynamique est réduit à 0.
Via le réglage ”réduire le nombre d’enclenchement ” il est possible de déterminer le degré d’amplitude d’élargissement de la zone dynamique pour réduire le fonctionnement cyclique des com­presseurs.
Si ”réduire le nombre d’enclenchement” est mis sur ”aucune ré­duction” aucun élargissement dynamique des zones n’aura lieu.
Si ”réduire le nombre d’enclenchement ” est mis sur ”faible”, ”moyen” ou ”grand” l’extension dynamique des zones sera dé­clenchée. L’amplitude de l’extension de zone sera la plus grande quand ”réduire le nombre d’enclenchement ” est mis sur ”grand”. Voir le croquis qui montre un exemple avec le cas de 6 étages de compresseur avec ”réduire le nombre d’enclenchement ” mis sur ”grand”. Remarquez également que l’extension dynamique des zones est la plus importante avec une capacité de compresseur faible.
Méthode de répartition de capacité
Le distributeur de capacité peut travailler à partir de 3 principes de répartition.
Les schémas d’enclenchement – fonction séquentielle :
Les compresseurs enclenchent/dénclenchent selon le principe du ”rst in last out” (FILO) en fonction de l’ordre dans lequel ils ont été dénis par la conguration. D'éventuels compresseurs à vitesse commandée peuvent être utilisés pour combler des trous de capacité.
Restriction du minuteur Si un compresseur ne peut démarrer, parce qu’il est « xé » sur le minuteur de démarrage, cet étage ne sera pas remplacé par un autre compresseur, mais le coupleur d’étage, par contre, attend jusqu’à ce que le minuteur ait terminé.
Arrêt de sécurité Par contre, s’il y a un arrêt de sécurité sur un compresseur, ça ne se fera pas et le coupleur d’étage sélectionne aussitôt le prochain prévu dans la séquence.
Les schémas d’enclenchement – fonction cyclique :
Ce principe est utilisé au cas où tous les compresseurs sont de même type et de même puissance. Les compresseurs s’enclenchent et s’arrêtent selon le principe "First In First Out" (FIFO) pour atteindre une égalisation du temps de marche entre les compresseurs. Les compresseurs à vitesse commandée seront toujours enclen­chés en premier et la capacité variable est utilisée pour combler les trous de capacité entre les étages suivants.
“réduire le nombre d’enclenchement“ = “Grand“
76 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Restrictions de minuteur et arrêt de sécurité Si un compresseur ne peut démarrer, parce qu’il est « xé » sur le minuteur de démarrage ou parce qu’il a été soumis à un arrêt de sécurité, cet étage sera remplacé par un autre compresseur.
Egalisation des heures de service L’égalisation de ce type s’eectue entre des compresseurs de types identiques avec la même capacité totale.
- Lors des diérents démarrages, le compresseur ayant fonctionné le moins longtemps sera démarré en premier.
- Lors des diérents arrêts, le compresseur ayant fonctionné le plus longtemps sera arrêté en premier.
- Pour des compresseurs à plusieurs étages, l’égalisation du temps de marche s’opère entre l’étage principal des diérents compres­seurs.
Page 77
Schémas d’enclenchement – régime Best t
Ce principe est utilisé si les compresseurs sont de puissance diérente. Le distributeur de capacité démarrera et arrêtera la capacité du compresseur pour atteindre le moins de sauts de capacité possi­ble. Les compresseurs à vitesse commandée seront toujours enclen­chés en premier et la capacité variable est utilisée pour combler les trous de capacité entre les étages suivants.
Restrictions de minuteur et arrêt de sécurité Si un compresseur ne peut démarrer, parce qu’il est « xé » sur le minuteur de démarrage ou parce qu’il a été soumis à un arrêt de sécurité, cet étage sera remplacé par un autre compresseur ou par une autre combinaison.
Changement de capacité minimum Pour éviter que le distributeur de capacité choisisse une nouvelle combinaison de compresseurs (enclenche et arrête des compres­seurs) sur base d’un petit changement du besoin de capacité, il est possible d’évaluer ce changement minimum de besoin de ca­pacité avant que le distributeur de capacité passe à une nouvelle combinaison de compresseurs.
Types de centrales à compresseurs combinés
Le régulateur est en mesure de gérer des centrales allant jusqu’à 6 compresseurs de diérents types.
- Un compresseur à vitesse variable équipé ou non de décompres­seurs
- Des compresseurs à un étage – piston ou scroll
Le schéma ci-dessous présente les combinaisons de compresseurs que le régulateur est en mesure de commander. Il indique égale­ment les schémas d’enclenchement qui peuvent être utilisés pour chacune des combinaisons de compresseurs.
Combinaison Description Schéma
Compresseurs d’un étage *1
Un seul compresseur à vitesse comman­dée combiné à des compresseurs d’un étage *1 et *3
d’enclenche­ment
Séquentiel
x x x 21-40
x x x 1-20
Cyclique
Application
Best t
*1) En cas de schéma d’enclenchement cyclique, les compresseurs d’un étage doivent
avoir la même puissance.
*2) Des compresseurs à vitesse commandée peuvent avoir une puissance diérente
de celle des compresseurs suivants.
Dans l’annexe A vous est présentée une description plus détaillée des schémas d'enclenchement pour chacune des applications de compresseur avec des exemples illustratifs.
Ci-dessous vous est présentée une description de quelques règles générales d’utilisation pour des compresseurs à vitesse comman­dée.
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 77
Page 78
Compresseurs à vitesse commandée
Le régulateur est en mesure d’employer la vitesse variable au com­presseur pilote dans diverses combinaisons de compresseurs. La part variable des compresseurs à vitesse régulée est utilisée pour combler les trous de capacité dans les étages de compresseurs suivants.
Considérations générales concernant la régulation :
L’un des étages dénis pour la régulation des compresseurs peut être relié à une vitesse variable, un variateur de fréquence VLT, par exemple.
On relie une sortie à l’entrée tout/rien du variateur de fréquence et on relie la sortie analogique « AO » à l’entrée analogique du variateur de fréquence. Le signal tout/rien démarre et arrête le variateur de fréquence, le signal analogique déterminant la vitesse. La régulation de vitesse ne peut porter que sur le compresseur déni sous le numéro 1.
Lorsque l’étage est en marche, il comprend une capacité xe et une capacité variable. La capacité xe sera celle qui répond à l’intitulé ”vitesse min» et la variable se trouvera entre la vitesse min et max. Pour optimiser la régulation, il faut que la capacité variable soit supérieure à celle fournie par l’étage suivant qu’elle doit couvrir dans la régulation. S’il y a d’importantes variations de courte durée dans les besoins de l’installation, le besoin en capa­cité variable augmente.
Voici comment l’étage est enclenché et déclenché
Si le besoin de capacité s’avère supérieur à la ”vitesse Max.” alors l’étage du compresseur suivant sera enclenché. Dans le même temps, la vitesse est réduite de telle sorte que la capacité soit réduite d’une valeur qui compense l’étage du compresseur qui vient d’être déclenché. C’est ainsi que l’on obtient une transition particulièrement ”sans à-coups” et sans trous de capacité (voir éventuellement le schéma).
Régulation -- Capacité décroissante Si le besoin de capacité s’avère inférieur à la « vitesse min. » alors l’étage du compresseur suivant sera déclenché. Dans le même temps, la vitesse est accrue de telle sorte que la capacité soit augmentée d’une valeur qui compense l’étage du compresseur qui vient d’être déclenché.
Déclenchement L’étage de capacité sera déclenché quand le compresseur attein­dra la ”vitesse min” et le besoin de capacité (capacité souhaitée) tombé en dessous de 1 %.
Anti court-cycle sur un compresseur à vitesse variable Si le compresseur à vitesse variable n’est pas autorisé à démarrer en raison d’anti court-cycle, alors aucun autre compresseur ne le pourra. Le compresseur à vitesse variable démarrera quand la temporisation est écoulée.
Enclenchement Le compresseur à vitesse variable sera toujours le premier à dé­marrer et le dernier à stopper. Le variateur de fréquence est démarré lors d’un appel de capacité au niveau de « vitesse de mémarrage » (la sortie de relais commu­te à ON et la sortie analogique est alimentée en une tension cor­respondant à cette vitesse). Il est alors au variateur de fréquence de porter la vitesse à « vitesse de démarrage » . L’étage de capacité est alors enclenché et le régulateur détermine la capacité voulue. La vitesse de mémarrage doit toujours être déni susamment haute pour qu’un bon graissage du compres­seur soit rapidement obtenu pendant le démarrage. Régulation -- Capacité croissante
Déclenchement de sécurité sur un compresseur à vitesse variable Si le compresseur à vitesse variable est déclenché pour des raisons de sécurité, les autres compresseurs pourront démarrer. Aussitôt que le compresseur à vitesse variable est prêt à démarrer il sera le premier compresseur à démarrer. Comme on l’a dit précédemment, la part variable de la capacité sur la vitesse doit être supérieure à la capacité de l’étage des compresseurs suivants pour obtenir une courbe de capacité sans ”trous”. Pour illustrer de quelle manière la vitesse variable va réagir en fonction de diverses combinaisons de centrale on va mainte­nant présenter quelques exemples :
78 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 79
a) Capacité en vitesse variable, capacité supérieure à l’étage de com­presseur suivant :
Quand la part variable du compresseur à vitesse variable est supé­rieure aux compresseurs suivants, il n’y aura pas de ”trous” dans la courbe de capacité. Exemple : 1 compresseur à vitesse variable à capacité nominale pour 50 Hz de 10 kW – gamme de vitesses variable 30 – 90 Hz 2 compresseurs sans régulation de capacité de 10 kW
Capacité xe minimum = 30 Hz / 50 Hz x 10 kW = 6 kW Capacité variable = 60 Hz / 50 Hz x 10 kW = 12 kW
La courbe de capacité aura le prol suivant :
Comme la part variable du compresseur à vitesse variable est supérieure à l’étage des compresseurs suivants, il n’y aura pas de ”trous” dans la courbe de capacité.
1) Le compresseur à vitesse variable sera enclenché, quand la capacité souhaitée atteindra celle de la vitesse de départ.
2) Le compresseur à vitesse variable accélère la vitesse jusqu’à ce qu’elle atteigne la vitesse maximum à une capacité de 18 kW.
3) Le compresseur d’un étage C2 de 10 kW est enclenché, et la vitesse en C1 est réduite de manière à correspondre à 8 kW (40 Hz)
4) Le compresseur à vitesse variable accélère la vitesse jusqu’à ce que la capacité réunie atteigne les 28 kW à vitesse maximum
5) Le compresseur d’un étage C3 de 10 kW est enclenché, et la vitesse en C1 est réduite de manière à correspondre à 8 kW (40 Hz)
6) Le compresseur à vitesse variable accélère la vitesse jusqu’à ce que la capacité réunie atteigne les 38 kW à vitesse maximum
7) Quand la capacité est de nouveau réduite, le compresseur d’un étage est déclenché quand la vitesse en C1 est au minimum
b) Capacité en vitess variable inférieure à l’étage de compresseur suivant :
Si la part variable du compresseur à vitesse variable est inférieure aux compresseurs suivants, il y aura des ”trous” dans la courbe de capacité.
Exemple : 1 compresseur à vitesse variable à capacité nominale pour 50 Hz de 20 kW – gamme de vitesses variable 25 -50 Hz 2 compresseur sans régulation de capacité de 20 kW Capacité xe = 25 Hz / 50 Hz x 20 kW = 10 kW Capacité variable = 25 Hz / 50 Hz x 20 kW = 10 kW La courbe de capacité aura le prol suivant :
Comme la part variable du compresseur à vitesse variable est inférieure à l’étage des compresseurs suivants, il y aura des ”trous” dans la courbe de capacité ne pouvant être comblés par la capa­cité variable.
1) Le compresseur à vitesse variable sera enclenché, quand la capacité souhaitée atteindra celle de la vitesse de départ.
2) Le compresseur à vitesse variable accélère la vitesse jusqu’à ce qu’elle atteigne la vitesse maximum à une capacité de 20 kW.
3) Le compresseur à vitesse variable plafonne à la vitesse max. jusqu’à ce que la capacité voulue atteigne les 30 kW.
4) Le compresseur d’un étage C2 de 20 kW est enclenché, et la vitesse en C1 est réduite au min. de manière à correspondre à 10 kW (25 Hz) Capacité réunie = 30 kW.
5) Le compresseur à vitesse variable accélère la vitesse jusqu’à ce que la capacité réunie atteigne les 40 kW à vitesse maximum
6) Le compresseur à vitesse variable plafonne à la vitesse max. jusqu’à ce que la capacité voulue atteigne les 50 kW.
7) Le compresseur d’un étage C3 de 20 kW est enclenché, et la vitesse en C1 est réduite au min. de manière à correspondre à 10 kW (25 Hz) Capacité réunie = 50 kW.
8) Le compresseur à vitesse variable accélère la vitesse jusqu’à ce que la capacité réunie atteigne les 60 kW à vitesse maximum
9) Quand la capacité est de nouveau réduite, le compresseur d’un étage est déclenché quand la vitesse en C1 est au minimum
Temporisateur de compresseur
Temporisation des enclenchements et des déclenchements
Pour protéger le moteur des compresseurs contre les redémarra­ges trop fréquents, on peut régler 3 temporisations.
- Un temps minimum entre deux démarrages d’un compresseur.
- Un temps minimum (temps de marche) entre le démarrage et
l’arrêt d’un compresseur.
- un temps moindre OFF, s’écoulant du moment où le compresseur
s’est arrêté à celui où ce dernier doit repartir.
Pour les enclenchements/déclenchements des étages, les tempo­risations ne sont pas utilisées.
Compteur horaire
Le temps de marche d’un moteur de compresseur est enregistré en continu. Les achages informent sur :
- le temps de marche des 24 heures en cours
- le temps de marche totalisé depuis la dernière mise à zéro
Compteur de commutations
Le nombre de commutations des relais est enregistré en continu. Les achages informent sur :
- le nombre de commutations des 24 heures en cours
- le nombre de commutations totalisé depuis la dernière mise à
zéro
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 79
Page 80
Ecrêtage
Sur certaines installations, on souhaite limiter la capacité du com­presseur enclenché de manière que par périodes on puisse limiter la charge totale électrique dans l’établissement.
1 entrée numérique est disponible à cet eet.
A chaque entrée numérique correspond une valeur limite de tolé­rance maximum pour la capacité du compresseur enclenché.
Dès qu’une entrée est activée, la capacité maximale permise du compresseur sera ramenée à la limite programmée. Ce qui veut dire que si la capacité actuelle du compresseur à la mise en mar­che de l’entrée numérique se trouve être supérieure à cette limite, alors une capacité du compresseur sera d’autant déclenchée qu’elle devra être égale ou inférieure à la valeur limite maximale programmée pour cette entrée numérique.
Forçage de l’écrêtage : Pour éviter que le l’écrêtage entraîne des problèmes de tempé­rature pour les produits réfrigérés on y a adjoint une fonction de forçage.
On a réglé une limite de forçage pour la pression d’aspiration ainsi qu’un temps de retard pour le entrée numérique.
Si la pression d’aspiration en écrêtage dépasse la limite dénie de forçage et les temps de retard épuisés, alors l’écrêtage force le signaux si bien que la capacité de compresseur peut être aug­mentée jusqu’à ce que la pression d’aspiration de nouveau se retrouve dans les limites de valeurs de référence normales. Ensuite l’écrêtage peut être activé à nouveau.
Injection ON
Il faut que les vannes de régulation de capacité électroniques soient fermés si tous les compresseurs sont arrêtés et un réenclenchement est bloqué. Les évaporateurs ne se remplissent alors pas de liquide qui risque d’être transféré à un compresseur lorsque la régulation redémarre. Le fonction ou l’obtenir à l’aide d’une transmission de données.
La fonction est décrite à partir du mode opératoire ci-dessous : T1) Le dernier compresseur a été déclenché T2) La pression d’aspiration est monté jusqu’à une valeur corres-
pondant à Po Ref + NZ + ”+ Zone K”, mais aucun compresseur peut démarrer à cause du temporisateur ou le déclenchement de sécurité.
T3) Le temps de retard ”Injection délais OFF ” est épuisé et les
soupapes d’injections sont en fermeture forcée via un signal de réseau.
T4) Le premier compresseur maintenant est prêt à démarrer. Le
signal de fermeture forcée via le réseau est annulé maintenant.
T5) Le temps de retard ”délais démarrage compr. ” est épuisé et le
premier compresseur obtient le droit de démarrer.
La raison pour laquelle le signal de fermeture forcée via le ré­seau est annulé avant que le premier compresseur ne démarre vient de ce que cela prend un certain temps de répartir le signal à tous les régulateurs de meubles via le réseau.
Alarme : Quand le entrée d’écrêtage est activée, un message d’alarme sera généré pour signaler que la régulation normale est mise hors jeu. Cette alarme peut cependant être inhibée si nécessaire.
80 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 81
Sécurités
Signal émis par les sécurités du compresseur
Le régulateur contrôle l’état du circuit de sécurité de chaque com­presseur. Le signal est relevé directement du circuit de sécurité et transmis à une entrée. (Il faut que le circuit de sécurité arrête le compresseur sans passer par le régulateur.) Si le circuit de sécurité est coupé, le régulateur déclenche le relais du compresseur dont il s’agit, en émettant une alarme. La régula­tion des autres compresseurs continue.
Circuit de sécurité commun Recevoir un signal de sécurité commun en provenance de tout le groupe d’aspiration est également possible. Tous les compresseurs sont déclenchés si le signal de sécurité est coupé.
L’alarme est annulée et le réenclenchement d’étages de compresseurs est autorisé lorsque les conditions suivantes sont remplies :
- la température a chuté à 10 K sous la limite
- la temporisation du réenclenchement s’est écoulée
La régulation de condensation est à nouveau autorisée lorsque la température a chuté à 10 K sous la limite.
Contrôle de la pression d’aspiration minimum (P0)
Cette fonction déclenche immédiatement tous les étages de compresseurs si la pression d’aspiration est inférieure à la limite admissible. On dénit la limite du déclenchement dans la plage de –120 à +30°C. La pression d’aspiration est captée par le transmetteur P0.
Lors d’un déclenchement, la fonction d’alarme activée
L’alarme est annulée et le réenclenchement d’étages de
compresseurs est autorisé lorsque les conditions suivantes sont remplies :
- la pression (la température) se trouve au-dessus de la limite de
déclenchement
- la temporisation du réenclenchement s’est écoulée (voir plus
loin)
Surveillance de la pression de condensation maximum (Pc)
Cette fonction enclenche tous les étages de condenseurs et déclenche un par un les étages de compresseurs si la pression de condensation dépasse la limite admissible. La limite du déclenchement est dénie dans la plage de -30 à +100°C. La pression de condensation est contrôlée par le transmetteur Pc.
Délais de réponse à un déclenchement de sécurité En relation avec la surveillance de sécurité d’un compresseur, il est possible de dénir deux temps de retard.
Temps de retard de déclenchement :
• Le temps de retard du signal de l’alarme du circuit de sécurité jusqu’à ce que la sortie du compresseur soit déclenchée (remar­quez que le temps de retard est commun à toutes les entrées).
• Temps de redémarrage de sécurité : Un moindre temps, un compresseur doit être OK après un déclenchement de sécurité jusqu’à ce qu’il puisse repartir.
Surveillance de la surchaue
Il s’agit d’une fonction d’alarme qui reçoit en continu des résultats de mesures émis par P0 et Ss. Si la surchaue dépasse les limites minimum ou maximum ré­glées, une alarme est émise après écoulement du retard.
Contrôle de la température de refoulement (Sd)
Cette fonction déclenche les étages un par un si la température de refoulement dépasse la limite admissible. La limite du déclenchement est dénie dans la plage de 0 à +150°C.
La fonction est activée à 10 K sous la consigne. Toute la capacité de condensation est alors enclenchée et, simultanément, 33% de la capacité de compression est déclenchée (un étage au moins). Cette procédure est répétée toutes les 30 secondes. La fonction d’alarme est activée. Si la température atteint la limite réglée, tous les étages de compresseurs sont immédiatement déclenchés
La fonction est activée à 3 K sous la consigne. Toute la capacité de condensation est alors enclenchée et, simultanément, 33% de la capacité de compression est déclenchée (un étage au moins). Cette procédure est répétée toutes les 30 secondes. La fonction d’alarme est activée.
Si la température (la pression) dépasse la limite réglée, les réactions sont les suivantes :
- tous les étages de compression sont immédiatement déclenchés
- la capacité de condensation est maintenue enclenchée
L’alarme est annulée et le réenclenchement d’étages de
compresseurs est autorisé lorsque les conditions suivantes sont remplies :
- la température (la pression) a chuté à 3 K sous la limite ;
- la temporisation du réenclenchement s’est écoulée.
Temporisation des alarmes Pc max. Il est possible de retarder la communication « Pc max alarm ». Le régulateur arrêtera toujours les compresseurs mais l’émission de la même alarme est retardée.
Temporisation
Il y a temporisation commune pour « Contrôle de température max. de refoulement » et « Pression d’aspiration min. ».
Alarme en cas de pression d’aspiration trop élevée
On peut choisir une limite d’alarme en cas de pression d’aspira­tion trop élevée. Une alarme est émise après écoulement de la temporisation correspondante. Il n’y a aucune réaction de la part de la régulation.
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 81
Page 82
Condenseur
La régulation du condenseur se fait par enclenchement/déclen­chement d’étages ou par la variation de vitesse des ventilateurs.
• Enclenchement/déclenchement d’étages Le régulateur peut commander jusqu’à 8 ou 12 étages de condenseurs, qui sont enclenchés et déclenchés de façon séquentielle.
• Variation de vitesse des ventilateurs La tension de sortie analogique est raccordée à un variateur de vitesse. Tous les ventilateurs sont alors régulés entre la vitesse nulle et maximum. S’il y a besoin d’un signal tout/rien, on peut le relever d’une sortie à relais La régulation suit l’un de ces deux principes :
- Tous les ventilateurs fonctionne à la même vitesse
- Les ventilateurs sont enclenchés selon besoin.
Régulation de capacité de condenseur
La capacité enclenchée est commandée par la pression de condensation actuelle et selon qu’il y a accroissement ou décrois­sement de la pression. La régulation est assurée par un régulateur PI qui peut être trans­formé en régulateur P si le concept de l’installation le nécessite.
Régulation PI
Le régulateur enclenche la capacité pour que l’écart entre la pres­sion de condensation actuelle et la référence soit aussi réduit que possible.
Sur certaines installations, l’on compense déjà le « problème » susmentionné en enclenchant les ventilateurs du condenseur de façon binaire, c’est-à-dire que l’on enclenche peu de ventila­teurs en cas de capacités faibles et beaucoup en cas de capacités élevées, par exemple 1 – 2 – 4 - 8, etc. En l’occurrence, on a par conséquent déjà compensé l'intensication non linéaire et il n’est pas nécessaire d’avoir une courbe de capacité incurvée.
Dans le régulateur, on peut dès lors choisir si l’on souhaite obtenir une courbe de capacité incurvée ou linéaire de la commande de capacité du condenseur.
Courbe de capacité = Linéaire / Puissance
Demandé capacité Demandé capacité
Courbe de capacité = Puissance Courbe de capacité = Linéaire
Capteur de régulation
Le distributeur de capacité se régule à partir de la pression de condensation Pc,.
Régulation d’erreurs de capteur :
Une erreur de signal engendrera l’enclenchement de la capacité du condenseur à 100 %, mais la régulation du compresseur reste normale.
Régulation P
Le régulateur enclenche la capacité en fonction de l’écart entre la pression de condensation actuelle et la référence. La bande proportionnelle Xp indi­que l’écart pour la capacité de condensation de 100%.
Courbe de capacité
En cas de condenseurs refroidis par air, le premier étage de capa­cité donnera toujours relativement plus de capacité que l’étage de capacité suivant. Un étage supplémentaire orira une augmen­tation de capacité qui chutera ensuite au fur et à mesure que le nombre d’étages enclenchés augmente. Cela signie que le régulateur de capacité a besoin d’une plus forte intensication en cas de capacités élevées qu’en cas de capacités faibles. Le régulateur de capacité pour la régulation du condenseur présente dès lors une courbe de capacité incurvée qui donne une intensication optimale tant en cas de capacités élevées qu’en cas de capacités faibles.
82 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Référence de la pression de condensation
On peut dénir la référence de cette régulation selon deux prin­cipes : soit comme une référence xe, soit comme une référence variable selon la température extérieure.
Référence xe
La référence de la pression de condensation est réglée en °C.
Référence ottante
Cette fonction permet à la référence de la pression de condensa­tion de varier selon la température extérieure, variation comprise dans une plage dénie. Si une pression de condensation liquide se combine avec les vannes d’expansion électroniques on peut obtenir d’appréciables économies d’énergies. Les vannes d’expansions électroniques donnent la possibilité d’abaisser la pression de condensation dépendant de la température extérieure et par là de réduire la consommation en énergie de 2 % pour chaque degré de tempéra­ture abaissée.
Page 83
Régulation PI
On prend comme point de départ :
- la température extérieure mesurée par le capteur Sc3
- La diérence de température la plus minime possible entre la température de l’air et celle de condensation à 0 % de capacité de compresseur,
- la diérence dimensionnée du condenseur entre la température ambiante et la température de condensation pour une capacité de compression de 100% (Dim tmK)
- la fraction enclenchée de la capacité de compression
La diérence de température la plus minime possible (tm min) en cas de charge doit être réglée sur environ 6 K, puisque cela élimine le risque que tous les ventilateurs se mettent en marche quand il n’y a pas de compresseurs en fonction.. Régler la diérence dimensionnée (dim tm) pour la charge maxi­mum (15 K, par exemple).
Commande forcée de la capacité de condensation
Une commande forcée de la capacité permet de négliger la régu­lation normale.
En commande forcée, les fonctions de sécurité sont annulées.
Commande forcée par le réglage Mettre la régulation en mode manuel. Régler la capacité en pourcentage de la capacité régulée.
Commande forcée des relais En cas d’une commande forcée par les commutateurs en façade d’un Module d’extension, la fonction de sécurité enregistre les dépassements éventuels en émettant éventuellement des alar­mes, mais le régulateur ne peut pas actionner les relais dans cette situation.
Le régulateur fournit ensuite une valeur pour la référence en fonc­tion de la fraction enclenchée de la capacité de compression – et au moins 3 K au-dessus de la température extérieure.
Régualtion P
En régulation P, la référence est 3°C au-dessus la température extérieure mesurée. La bande proportionnelle Xp indique l’écart à 100% de capacité de condenseur.
Limitation de la référence
Pour éviter une référence trop élevée ou trop basse, il faut la limiter.
PcRef
Max
Min
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 83
Page 84
Répartition de capacité
Enclenchement /déclenchement des étages
Les enclenchements/déclenchements sont séquentiels. Le dernier étage enclenché est déclenché en premier.
Variation de vitesse
Les enclenchements/déclenchements sont séquentiels. Le dernier étage enclenché est déclenché en premier.
1 au moment où le besoin en capacité correspond à la vitesse de démarrage réglée. Le régulateur enclenche les ventilateurs au fur et à mesure du besoin en capacité croissant en adaptant ensuite la vitesse à la nouvelle situation. Le régulateur arrête les ventilateurs lorsque le besoin en capacité est inférieur à la vitesse minimum réglée.
Lors de la conguration des sorties du régulateur, le sortie « FanA1 » / « FanB1 » est destiné à enclencher et à déclencher le variateur de vitesse
Variation de vitesse commune
La tension de sortie analogique est raccordée à un variateur de vitesse. Tous les ventilateurs sont alors régulés entre 0 et leur capacité maximum. S’il y a besoin d’un signal tout/rien pour que le variateur de vitesse puisse mettre les ventilateurs à l’arrêt complet, une sortie à relais peut être dénie à cette fonction.
Start Min.
Le régulateur démarre le variateur de vitesse au moment ou le besoin en capacité correspond à la vitesse de démarrage réglée. Le régulateur arrête le variateur de vitesse lorsque le besoin en capacité est inférieur à la vitesse minimum réglée.
Variation de vitesse + enclenchement/déclenchement d’étages
Start Min.
Marche/arrêt des condenseurs
Enclenchement/déclenchement d’étages de condenseurs
En dehors de la temporisation comprise dans la régulation PI/P, il n’y a pas de retards s’appliquant aux enclenchements ou déclen­chements des étages de condenseurs.
Compteur horaire
Le temps de marche d’un moteur de ventilateur est enregistré en continu. Les achages informent sur :
- le temps de marche des dernières 24 heures
- le temps de marche totalisé depuis la dernière mise à zéro
Compteur de marche/arrêt
Le nombre de commutations des relais est enregistré en continu. Les achages informent sur :
- le nombre de temps de marche des dernières 24 heures
- le nombre de temps de marche totalisé depuis la dernière mise à zéro
Aptitude au fonctionnement des ventilateurs
Les derniers ventilateurs sont rarement activés au cours des mois d'hiver. Pour vérier que les ventilateurs sont « aptes au fonctionnement », toutes les 24 heures, il est réalisé un essai visant à garantir que tous les relais fonctionnent bien. Les relais inutilisés seront ensuite activés 30 secondes, avec une pause d'une heure entre les relais individuels. Une régulation de la vitesse est eectuée jusqu'à la « vitesse de départ ».
Le régulateur démarre le variateur de vitesse et le ventilateur n°
84 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 85
Sécurités du condenseur
Fonctions de surveillance - Sépa-
Signal émis par les sécurités du ventilateur
Le régulateur peut recevoir des signaux concernant l'état sur un circuit de sécurité commun. Le signal est relevé directement du circuit de sécurité et transmis à une entrée « DI7 ». Si le circuit de sécurité est coupé, le régulateur émet une alarme.
rées
Alarme du niveau de liquide
Une entrée peut assurer la surveillance d’un signal externe.
Si le signal est interrompu, une alarme se déclenche. Une temporisation de l’alarme est possible.
Alarme basse température
La fonction peut être utilisée pour la surveillance par alarme de la température
Les limites d'alarme peuvent être réglées pour une température élevée. Une temporisation de l’alarme est possible.
Alarme VSD safety
Une entrée peut assurer la surveillance de variateur de vitesse .
Si le signal est interrompu, une alarme se déclenche. Une temporisation de l’alarme est possible.
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 85
Page 86
Divers
Commutateur principal
Le commutateur principal est utilisé pour l’arrêt et le démarrage des fonctions de régulation.
L’échangeur a 2 positions :
- Etat de régulation normale . (Réglage = ON)
- Régulation stoppé. (Réglage = OFF)
Les limites d'alarme peuvent être réglées pour une température élevée.
Si le commutateur ou le commutateur principal externe est réglé sur OFF (arrêt), toutes les fonctions de régulateur sont inactives et une alarme sera déclenchée pour signaler ce fait – toutes les autres alarmes éteintes.
Réfrigérant
Avant de commencer la régulation, il faut choisir le réfrigérant. Les réfrigérants les plus courants sont choisis directement :
1 R12 11 R114 21 R407A 31 R422A 2 R22 12 R142b 22 R407B 32 R413A 3 R134a 13 Brugerdeneret 23 R410A 33 R422D 4 R502 14 R32 24 R170 34 R427A 5 R717 15 R227 25 R290 35 R438A 6 R13 16 R401A 26 R600 36 R513A 7 R13b1 17 R507 27 R600a 37 R407F 8 R23 18 R402A 28 R744 9 R500 19 R404A 29 R1270 10 R503 20 R407C 30 R417A
Le réglage du réfrigérant ne peut être modié que si ”le commuta­teur principal” est réglé sur ”régulation stoppée”.
Correction des signaux
Quel que soit le capteur d’émission, le signal d’entrée peut être corrigé. Seul un câble long à faible section nécessite une telle correction. La valeur corrigée est alors utilisée par tous les achages et fonctions
Fonction d’horloge
Le régulateur comprend une fonction d’horloge. La fonction d’horloge ne s’utilise que pour le passage du jour/nuit. Il faut programmer l’année, la date, l’horaire et les minutes.
Remarque : Si jamais le régulateur n’est pas équipé du Module RTC (AK-OB 101A) alors l’horloge doit être reprogrammée chaque fois qu’il y a eu une coupure de courant du secteur. Si le régulateur est branché à une installation dotée d’une pas­serelle AKA ou d’un système manager AK , ces derniers feront automatiquement en sorte que la fonction d’horloge soit repro­grammée.
Alarmes et messages
En relation avec les fonctions du régulateur, il y a toute une série d’alarmes et de messages qui seront visibles en cas de pannes ou d’erreurs de commande.
Historique d’alarme (Seul Service Tool)
Le régulateur comprend un historique d’alarme (journal) qui contient toutes les alarmes actives ainsi que les 40 dernières alarmes répertoriées par l’historique. Dans l’historique de l’alarme on peut voir quand l’alarme s’est déclenchée et quand elle a été neutralisée. En outre, on peut aussi voir la priorité de chaque alarme ainsi que quand l’alarme a été enregistrée et par quel utilisateur.
Attention ! Un choix incorrect met le compresseur en risque.
Défaut de capteur
S’il y enregistrement d’un défaut de signal d’un capteur de tempé-
rature ou d’un transmetteur de pression, une alarme est émise.
• En cas de défaut d’un capteur P0, la régulation continue avec une capacité enclenchée de 50% pendant la journée et de 25% pendant la nuit – et un étage au moins.
• En cas de défaut d’un capteur Pc, la capacité de condensation est enclenchée à 100% tandis que la régulation des compresseurs reste normale.
• En cas de défaut d’un capteur Sd, la surveillance par les sécurités
de la température de refoulement disparaît.
• En cas de défaut d’un capteur Ss, la surveillance de la surchaue
dans la conduite d’aspiration disparaît.
• En cas de défaut du capteur de la température extérieure Sc3.
La régulation selon une référence ottante de la pression de condensation n’est plus possible. La référence utilisée à la place est la valeur « PC-ref Min ».
NB: Un capteur stigmatisé comme défectueux se doit d’être OK
pendant 10 minutes avant que l’alarme lui correspondant soit neutralisée.
Alarme, priorité
On distingue entre des informations importantes et d’autres moins importantes. L’importance – ou la priorité - de certaines alarmes sont préétablies, tandis que d’autres peuvent être mo­diées à volonté (ce changement ne peut être eectué que par branchement du logiciel d’outils de service tool AK-ST au AKM logiciel.
Le réglage détermine quelle sélection/réaction doit être retenue pour réagir en cas de déclenchement d’alarmes.
• “Haute” est la plus importante
• “Seul journal” est la plus basse
• “Interrompu” n’implique aucune action
Relais alarme
Il existe une sortie d'alarme sur le régulateur comme indication d'alarme locale.
86 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 87
Les rapports entre les priorités d’alarmes et les réactions ressor­tent du schéma ci-dessous.
Réglage Enreg. Relais
d'alarme Elevée X X X 1 Moyenne X X 2 Basse X X 3 Enreg.Seulement X 4 Supprimée
Réseau Destination
AKM
Alarme conrmée : Si le régulateur est branché à un réseau doté d’une passerelle AKA ou un système AK de manager en tant que destinataire de l’alarme, ces derniers conrmeront l’enregistrement automatique d’alarmes qui leur sont adressés.
Forçage via le réseau
Le régulateur contient des réglages utilisables à partir de la fonc­tion de forçage de la passerelle via la transmission des données. Quand cette fonction requiert un changement, tous les régula­teurs en connexion sur ce réseau seront réglés simultanément. Il y a les possibilités suivantes :
- Passage au régime de nuit
- Asservissement de la vanne d’injection (Injection ON)
- Optimisation de la pression d’aspiration (Po)
Utilisation AKM / Service Tool / Display
La conguration elle-même du régulateur peut être eectuée via le logiciel service Tool AK-ST 500, AKM logiciel, acheur gra­phique AK-MMi ou avec acheur EKA 164.
Si le régulateur est utilisé en autonomie sans connexion réseau, il peut reconnaître automatiquement les alarmes. Les alarmes s'éteignent alors automatiquement lorsque la cause de l'alarme disparaît. (Régler « Auto act. alarm » (Reconnaissance automatique de l'alarme) sur « Enabled » (Activée)/P40 sur 0).
LED d’alarme Le LED d’alarme sur la face du régulateur indique l’état d’alarme du régulateur :
Clignote : Il y a une alarme active ou une alarme non conrmée. Lumière xe : Il y a une alarme active qui a été conrmée. Eteint : Il y a aucune alarme active et aucune alarme non conr­mée.
IO Statut et manuel
On utilise cette fonction pour l’installation, la maintenance et recherche de défauts sur l’installation. A l’aide de cette fonction les autres fonctions rattachées peuvent être contrôlées.
Prises de mesures Là, tout peut être de l’état de toutes les sorties/entrées consultées et contrôlées.
Commande forcée (seul Service tool) Là on peut exercer une commande forcée de toutes les sorties pour s’assurer qu’elles sont bien toutes correctement raccordées.
Remarque : Il n'y a aucune surveillance quand les sorties sont sujettes à commande forcée.
Mémorisation/enregistrement des paramètres
Comme outil irremplaçable pour la documentation et la recherche de défauts le régulateur donne la possibilité de mémoriser les pa­ramètres et données ainsi que de les enregistrer dans sa mémoire interne.
Via AK-ST 500 logiciel d’outil de service on peut : a) sélectionner jusqu’à 10 paramètres des valeurs que le régula-
teur doit régulièrement enregistrer
b) indiquer la fréquence des enregistrements
Le régulateur a une mémoire limitée mais en gros on peut comp­ter enregistrer 10 paramètres, qui sont enregistrés à chaque 10 minutes pendant 48 heures.
Via AK-ST 500 on peut après coup lire les valeurs historiques en forme de courbes. Le log fonctionne uniquement lorsque l'horloge a été dénie.
Remarque : Le logiciel AKM est un système qui n’a pas accès aux réglages de congurations de tous les régulateurs. Quels sont les réglages/lectures qui sont réalisables ? Cela ressort du menu d’utilisation de l’AKM (voir le sommaire bibliographique).
Autorisation / Code d’accès
Le régulateur peut être dirigé via le logiciel de type AKM et service Tool AK-ST 500 et acheur.
Les tout modes d’emploi donnent la possibilité d’accéder à dié­rents niveaux, le tout dépendant de la connaissance de l’utilisa­teur dans les diérentes fonctions.
Logiciel type AKM : Là, on dénit les diérents utilisateurs avec des initiales et les mots clés. Ensuite, l’accès est donné précisément aux fonctions que l’utilisateur peut utiliser. Le maniement est décrit dans le manuel AKM.
Logiciel d’outil de service AK-ST 500 : Son utilisation est décrite dans le tters on site guide.
Quand un utilisateur doit s’enregistrer, il faut indiquer les éléments suivants : a) Renseigner un nom d’utilisateur b) Renseigner un code d’accès c) Sélectionner le niveau d’utilisation d) Choisir l’unité de mesure – soit US (par ex. °F et PSI) soit Danfoss
SI (°C et Bar)
e) Choisir la langue
L’accès est donné à quatre niveaux d’utilisateur.
1) DFLT – Utilisateur par défaut – Accès sans usage de mot de passe Voir les réglages et lectures quotidiens.
2) Quotidien – utilisateur quotidien Programmer les fonctions choisies et entreprendre la conrmation d’alarmes.
3) SERV – utilisateur de service Tous les réglages entrés dans la systématique du menu à l’excep­tion de l’établissement de nouveaux utilisateurs.
4) SUPV – Utilisateur superviseur Tous les réglages entrés y compris l’établissement de nouveaux utilisateurs
Achage Un code d'accès peut être déni dans l'un des menus. Toutes les fonctions sont accessibles lorsque le code a été saisi.
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 87
Page 88
Achage des pressions d’aspiration et de condensation
Diodes luminescentes du régulateur
Communication interne entre les Modules : Clignotement rapide = erreur Allumée en permanence = erreur
Le régulateur est prévu pour le raccordement d’un seul ou de deux acheurs séparés. Le raccordement se fait par des câbles avec connecteurs. On peut placer l’acheur en façade d’un pan­neau, par exemple. Si un acheur avec boutons de réglage est installé, on obtient, en plus de l’achage des pressions d’aspiration et de condensation, la possibilité d’une commande simpliée au moyen d’un système de menus. Voir plus haut dans le manuel.
Si un écran est raccordé, il achera la valeur de ce qui est indiqué dans "Read out". Si vous souhaitez consulter une des valeurs de ce qui est indiqué sous « fonction », il convient de procéder de la façon suivante :
1. Appuyez sur le bouton supérieur jusqu’à ce qu’apparaisse un paramètre.
2. Appuyez sur le bouton supérieur ou inférieur pour trouver le paramètre que vous souhaitez acher.
3. Appuyez sur le bouton du milieu jusqu’à ce que la valeur du
paramètre apparaisse.
Après quelques instants, l’achage revient automatiquement à l’achage "Read out".
Si des voyants LED sont nécessaires pour indiquer le fonctionne­ment du compresseur, du ventilateur et de plusieurs fonctions, un écran de type EKA 166 peut être installé.
Etat de sortie 1-8
Power
Comm
DO1 Status
DO2 Service Tool
DO3 LON
DO4
DO5 Alarm
DO6
DO7
DO8 Service Pin
Clignotement lent = OK Clignotement rapide = réponse de la passerelle dans les 10 minutes suivant l’installation du réseau Allumée en permanence = erreur Eteinte en permanence = erreur
Communication externe
Clignotement = alarme active / non acquittée Allumée en permanence = alarme active / acquitée
Installation de reseau
(Le voyant LED correspondant à l'huile et à la chaleur n'est pas actif sur ce régulateur).
Acheur graphique AK-MMI
L'acheur permet un accès à la plupart des fonctions du régula­teur.
88 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 89
Annexe – Combinaisons de compresseurs et schémas d’enclenche­ment
Dans ce chapitre vous est présentée une description plus détaillée des combinaisons de compresseurs et des schémas d'enclenche­ment correspondants. Le régime séquentiel n’est pas repris dans les exemples puisque les compresseurs sont exclusivement enclenchés en fonction de leur numéro de compresseur (principe First in - Last out) et seule­ment des compresseurs à vitesse commandée sont utilisés pour combler les trous de capacité.
Application de compresseur = Compresseur sans étage
Le distributeur de capacité est en mesure de réguler jusqu’à 6 compresseurs d’un étage dans les schémas d’enclenchement suivants :
• séquentiel
• cyclique
• Best t
Régime cyclique - exemple Ici, tous les compresseurs sont de même puissance et ils s’enclen­chent et s’arrêtent selon le principe First In First Out (FIFO) pour atteindre une égalisation du temps de marche entre les compres­seurs.
- Une égalisation du temps de marche est opérée entre tous les compresseurs.
- Le compresseur présentant le moins de temps de marche dé­marre.
- Le compresseur présentant le plus de temps de marche s’arrête.
Application de compresseur = Un compresseur à régulation de vitesse et Compresseur sans étage
Le régulateur est en mesure de commander un seul compresseur à vitesse commandée combiné à des compresseurs d’un étage de puissances semblables ou diérentes.
Le point de départ pour utiliser cette application de compresseur est :
• Un seul compresseur à vitesse commandée qui peut avoir une puissance diérente de celle des compresseurs d’un étage suivants.
• Jusqu’à 5 compresseurs d’un étage de capacité égale ou dié­rente (en fonction du schéma d’enclenchement)
Cette combinaison de compresseurs peut être utilisée pour les schémas d’enclenchement suivants :
• séquentiel
• cyclique
• Best t
Utilisation de compresseur à vitesse commandée : Pour l’utilisation générale du compresseur à vitesse commandée, il convient de se référer au chapitre "Types de centrales à com­presseurs combinés".
Régime cyclique - exemple L’on est ici en présence de compresseurs d’un étage de même puissance. Le compresseur à vitesse commandée est toujours le premier à démarrer et le dernier à s’arrêter. Les compresseurs d’un étage s'enclenchent et s'arrêtent selon le principe First In First Out pour atteindre une égalisation du temps de marche. Le compresseur à vitesse commandée est utilisé pour combler les trous de capacité entre les compresseurs d’un étage.
Exemple :
Best t - exemple L’on compte ici au moins deux compresseurs de puissance dié­rente. Le distributeur de capacité démarre et arrête les compres­seurs pour atteindre la meilleure adaptation de capacité possible (le moins de sauts de capacité possible).
Capacité croissante :
- Le compresseur à vitesse commandée démarre lorsque la capa-
cité souhaitée correspond à la vitesse de démarrage.
- Le compresseur d’un étage suivant présentant le moins de
temps de marche s’enclenche lorsque le compresseur à vitesse commandée fonctionne à pleine vitesse (90 Hz).
- Une égalisation du temps de marche est opérée entre les com­presseurs1 et 2.
- Une égalisation du temps de marche est opérée entre les com­presseurs 3 et 4.
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 89
-Lorsque le compresseur d’un étage s’enclenche, le compresseur à vitesse commandée diminue la vitesse (40 Hz) correspondant à la capacité du compresseur d’un étage.
Capacité décroissante :
- Le compresseur d’un étage suivant présentant le plus de temps de marche s’arrête lorsque le compresseur à vitesse comman­dée atteint la vitesse minimum (30 Hz).
- Lorsqu’un compresseur d’un étage s’éteint, le compresseur à vitesse commandée augmente la vitesse (80 Hz) correspondant à la capacité du compresseur d’un étage.
Page 90
- Le compresseur à vitesse commandée est le dernier compres­seur qui s’arrête lorsque les conditions sont satisfaites.
Best t – exemple : L’on compte ici au moins deux compresseurs d’un étage de puis­sance diérente. Le compresseur à vitesse commandée est toujours le premier à démarrer et le dernier à s’arrêter. Le distributeur de capacité démarre et arrête les compresseurs d’un étage pour atteindre la meilleure adaptation de capacité possible (le moins de sauts de capacité possible).
Le compresseur à vitesse commandée est utilisé pour combler les trous de capacité entre les compresseurs d’un étage.
Exemple :
Capacité croissante :
- Le compresseur à vitesse commandée démarre lorsque la capa­cité souhaitée correspond à la vitesse de démarrage.
- Le plus petit compresseur d’un étage s’enclenche lorsque le compresseur à vitesse commandée fonctionne à pleine vitesse (90 Hz).
- Lorsque le compresseur à vitesse commandée atteint de nouveau la vitesse max. (90 Hz), le plus petit compresseur d’un étage (C2) s’arrête et le grand compresseur d’un étage (C3) s’enclenche.
- Lorsque le compresseur à vitesse commandée atteint de nouveau la vitesse max. (90 Hz), le plus petit compresseur d’un étage (C2) s’enclenche de nouveau.
- Lorsque les compresseurs d’un étage s’enclenchent, la vitesse du compresseur à vitesse commandée, correspondant à la capacité enclenchée, diminue (40 Hz).
Capacité décroissante :
- Le petit compresseur d’un étage s’arrête lorsque le compres­seur à vitesse commandée atteint la vitesse minimum (30 Hz).
- Lorsque le compresseur à vitesse commandée atteint de nouveau la vitesse min. (30 Hz), le plus petit compresseur d’un étage (C2) s’arrête et le grand compresseur d’un étage (C3) s’enclenche.
- Lorsque le compresseur à vitesse commandée atteint de nouveau la vitesse min. (30 Hz), le grand compresseur d’un étage (C2) s’arrête et le petit compresseur d’un étage (C3) se réenclenche.
- Lorsque le compresseur à vitesse commandée atteint de nou­veau la vitesse min. (30 Hz), le petit compresseur d’un étage (C2) s’arrête..
- Le compresseur à vitesse commandée est le dernier compres­seur qui s’arrête lorsque les conditions sont satisfaites.
- Lorsque la capacité du compresseur d’un étage s’arrête, le compresseur à vitesse commandée augmente la vitesse (80 Hz) correspondant à la capacité arrêtée.
90 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
Page 91
Réserves
Toute action non intentionnelle risque d’entraîner des défauts de capteur, de régulateur, de vanne ou de ligne série, d’où des pertur­bations du fonctionnement de l’installation frigorique (tempéra­ture élevée ou liquide dans l’évaporateur, par exemple).
Danfoss n’assume aucune responsabilité quant aux détériorations par suite de tels défauts, ni pour les denrées conservées ni pour les composants frigoriques. Il appartient au monteur de prendre les mesures qui s’imposent pour éviter ces défauts. La nécessité du signal au régulateur lors de l’arrêt du compresseur mérite une attention particulière ; il en est de même avec les accumulateurs de liquide à l’entrée des compresseurs.
AK-PC 710 Régulation de capacité RS8FT504 © Danfoss 08-2015 91
Page 92
Danfoss n’assume aucune responsabilité quant aux erreurs qui se seraient glissées dans les catalogues, brochures ou autres documentations écrites.Dans un souci constant d’amélioration, Danfoss se réserve le droit d’apporter sans préavis toutes modcations à ses produits, y compris ceux se trouvant déjà en commande, sous réserve, toutefois, que ces modications n’aectent pas les caractéristiques déjà arrêtées en accord avec le client. Toutes les marques de fabrique de cette documentation sont la propriété des sociétés correspondantes. Danfoss et le logotype Danfoss sont des marques de fabrique de Danfoss A/S. Tous droits réservés.
92 Régulation de capacité RS8FT504 © Danfoss 08-2015 AK-PC 710
ADAP-KOOL®
Loading...