AK-PC 710 is a complete regulating unit for capacity control of
compressors and condensers in refrigeration systems.
In addition to capacity control the controllers can give signals to
other controllers about the operating condition, e.g. forced closing of expansion valves, alarm signals and alarm messages.
Function overview
AK-PC 710
Application
Regulation of a compressor groupx
Both compressor group and condenser groupx
Regulation of compressor capacity
Regulation sensorP0
PI-regulation x
Max. number of compressor steps6
Identical compressor capacitiesx
Dierent compressor capacitiesx
Sequential operation (rst in / last out)x
Speed regulation of 1 compressorx
Run time equalisationx
Min. restart timex
Min. On-time/ Min O timex
Suction pressure reference
Override via P0 optimizationx
Override via “night setback”x
The controller’s main function is to control compressors and
condensers so that operation all the time takes place at the
energy-optimum pressure conditions. Both suction pressure
and condensing pressure are controlled by signals from pressure
transmitters.
Capacity control can be carried out by suction pressure P0.
Among the dierent functions are:
- Capacity control of up to 6 compressors
- Speed control of one compressor
- One safety input for each compressor
- Option for capacity limitation to minimize consumption peaks
- When the compressor stops, signals can be transmitted to appliance controllers so that the electronic expansion valves will be
closed (signal via data communication)
- Safety monitoring of high pressure / low pressure / discharge
temperature
- Capacity control of up to 6 fans
- Step coupling, speed regulation or a combination
- Floating reference with regard to outside temperature
- Safety monitoring of fans
- The status of the outputs and inputs is shown by means of lightemitting diodes on the front panel
- Alarm signals can be generated directly from the controller and
via data communication
- Alarms are shown with texts so that the cause of the alarm is
easy to see.
- Plus some completely separate functions that are totally independent of the regulation – such monitoring of liquid level and
room temperature.
The great advantage of this series of controllers is that it can
be extended as the size of the plant is increased. It has been
developed for refrigeration control systems, but not for any
specic application – variation is created through the read-in
software and extension with up to 3 modules.
It is the same modules that are used for each regulation and the
composition can be changed, as required. With these modules
(building blocks) there is up to 40 various kinds of regulations.
But it is you who must help adjusting the regulation to the actual
needs – these instructions will assist you to nd your way through
all the questions so that the regulation can be dened and the
connections made.
Controller
Top part
Advantages
• The controller’s size can “grow” as systems grow
• The software can be set for one or more regulations
• Several regulations with the same components
• Extension-friendly when systems requirements are changed
• Flexible concept:
- Controller series with common construction
- One principle – many regulation uses
- modules are selected for the actual connection requirements
- The same modules are used from regulation to regulation
Extension modules
Bottom part
The controller is the cornerstone of the regulation. The module has inputs and
outputs capable of handling small systems.
• The bottom part – and hence the terminals – are the same for all controller types.
• The top part contains the intelligence with software. This unit will vary according
to controller type. But it will always be supplied together with the bottom part.
• In addition to the software the top part is provided with connections for data
communication and address setting.
Examples
A regulation with few connections can
be performed with the controller module
alone
If the system grows and more functions have to be controlled, the regulation can be
extended.
With extra modules more signals can be received and more relays cut in and out
– how many of them – and which – is determined by the relevant application.
If there are many connections one or more
extension modules must be mounted
Setup and operation of an AK controller must be accomplished via
the “AK-Service Tool” software program.
The programme is installed on a PC, and setup and operation of
the various functions are carried out via the controller’s menu
displays.
Displays
The menu displays are dynamic, so that dierent settings in one
menu will result in dierent setting possibilities in other menus.
A simple application with few connections will give a setup with
few settings.
A corresponding application with many connections will give a
setup with many settings.
From the overview display there is access to further displays for
the compressor regulation and the condenser regulation.
At the bottom of the display there is access to a number of general
functions, such as “time table”, “manual operation”, “log function”,
“alarms”, and “service” (conguration).
Network linking
The controller can be linked up into a network together with other
controllers in an ADAP-KOOL® refrigeration control system. After
the setup operation can be performed at a distance with, say, our
software program type AKM.
Users
The controller comes supplied with several languages, one of
which can be selected and employed by the user. If there are
several users, they may each have their choice of language. All
users must be assigned a user prole which either gives access to
full operation or gradually limits the operation to the lowest level
that only allows you “to see”.
External display
An external display can be tted in order for P0 (Suction) and Pc
(Condensing) readings to be displayed.
The setup can be carried out on a display with control buttons.
The various functions are selected via a menu system.
If display of operational compressors, fans and functions is required, display type EKA 166 can be tted.
Med det graske display AK-MMI kan der både foretages opsætning og udlæsning.
A number of light-emitting diodes makes it possible to follow the
signals that are received and transmitted by the controller.
Log
From the log function you can dene the measurements you wish
to be shown.
The collected values can be printed, or you may export them to a
le. You can open the le in Excel.
If you are in a service situation you can show measurements in a
trend function. The measurements are then made real-time and
displayed instantly.
■ Power
■ Comm
■ DO1 ■ Status
■ DO2 ■ Service Tool
■ DO3 ■ LON
■ DO4
■ DO5 ■ Alarm
■ DO6
■ DO7
■ DO8 ■ Service Pin
Slow ash = OK
Quick ash = answer from gateway
Constantly ON = error
Constantly OFF = error
Flash = active alarm/not cancelled
Constant ON = Active alarm/cancelled
Alarm
The display gives you an overview of all active alarms. If you wish
to conrm that you have seen the alarm you can cross it o in the
acknowledge eld.
If you want to know more about a current alarm you can click on it
and obtain an information display on the screen.
A corresponding display exists for all earlier alarms. Here you can
upload information if you need further details about the alarm
history.
• Controller module – capable of handling minor plant requirements.
• Extension modules. When the complexity becomes greater
and additional inputs or outputs are required, modules can be
attached to the controller. A plug on the side of the module will
transmit the supply voltage and data communication between
the modules.
• Top part
The upper part of the controller module contains the
intelligence. This is the unit where the regulation is dened and
where data communication is connected to other controllers in a
bigger network.
Extension module with
additional analog inputs
External display for
suction pressure etc.
• Connection types
There are various types of inputs and outputs. One type may, for
example, receive signals from sensors and switches, another may
receive a voltage signal, and a third type may be outputs with
relays etc. The individual types are shown in the table below.
• Fixed connection
When a regulation is planned (set up) it will generate a need
for a number of connections distributed on the mentioned
types. This connection must be made as shown in the following
diagrams.
Extension module with additional
relay outputs and additional
analog inputs.
Controller with analog inputs and
relay outputs.
Top part
Extension module with
2x analog output signals
The module with additional relay outputs is
also available in a version where the top part
is provided with change-over switches so
that the relays can be overridden.
Pressure transmitter type AKS 32R /
AKS 32 (1-5 V)
Voltage signal 0-10 V
Contact function (On/O)On at R < 20 ohm
On/o supply voltage inputsLow voltage
Relay outputs
SPDT
Solid state outputsUsed for control of compressor relayMax. 240 V a.c. , Min. 48 V a.c.
Ambient temperatureDuring transport-40 to 70°C
0 / 80 V a.c./d.c.
High voltage
0 / 260 V a.c.
AC-1 (ohmic)4 A
AC-15 (inductive)3 A
UMin. 24 V
Accuracy: +/- 0.5°C
Resolution:1 mV
Accuracy +/- 10 mV
Max. connection of 5 pressure transmitters on one module
O at R > 2K ohm
(Gold -plated contacts not necessary)
O: U < 2 V
On: U > 10 V
O: U < 24 V
On: U > 80 V
Max. 230 V
Low and high voltage must not be connected to the same
output group
Max. 0.5 A,
Leak < 1 mA
During operation-20 to 55°C ,
0 to 95% RH (non condensing)
No shock inuences / vibrations
EnclosureMaterialPC / ABS
ClassIP10 , VBG 4
MountingFor mounting on panel wall or DIN rail
Weight with screw terminalsmodules in100- / 200- / controller-seriesCa. 200 g / 500 g / 600 g
ApprovalsEU low voltage directive and EMC require-
ments are complied with
UL 873,
The mentioned data applies to all modules.
If data is specic, this is mentioned together with the module in question.
Capacitive load
The relays cannot be used for the direct connection of capacitive loads such as LEDs
and on/o control of EC motors.
All loads with a switch mode power supply must be connected with a suitable contactor or similar.
LVD tested according to EN 60730
EMC tested
Immunity according to EN 61000-6-2
Emission according to EN 61000-6-3
UL le number: E166834 for XM
UL le number: E31024 for PC
There are several controllers in the series. The function is
determined by the programmed software, but outwardly the
controllers are identical – they all have the same connection
possibilities:
11 analog inputs for sensors, pressure transmitters, voltage signals
and contact signals.
8 digital outputs, with 4 Solid state outputs and 4 relay outputs
Supply voltage
24 V a.c. or d.c. to be connected to the controller.
The 24 V must not be retransmitted and used by other controllers
as it is not galvanically separated from inputs and outputs. In
other words, you must use a transformer for each controller. Class
II is required. The terminals must not be earthed.
The supply voltage to any extension modules is transmitted via
the plug on the right-hand side.
The size of the transformer is determined by the power
requirement of the total number of modules.
The supply voltage to a pressure transmitter can be taken either
from the 5 V output or from the 12 V output depending on
transmitter type.
PIN
Data communication
If the controller is to be included in a system, communication
must take place via the LON connection.
The installation has to be made as mentioned in the separate
instructions for LON communication.
Address setting
When the controller is connected to a gateway type AKA 245,
the controller’s address must be set between 1 and 119. (If it is a
system manager AK-SM .., then 1-999).
Service PIN
When the controller is connected to the data communication
cable the gateway must have knowledge of the new controller.
This is obtained by pushing the key PIN. The LED “Status” will ash
when the gateway sends an acceptance message.
Operation
The conguration operation of the controller must take place from
the software programme “Service Tool”. The program must be
installed on a PC, and the PC must be connected to the controller
via the network plug on the front of the unit.
Light-emitting diodes
There are two rows with LED’s. They mean:
Left row:
• Voltage supply to the controller
• Communication active with the bottom PC board (red = error)
• Status of outputs DO1 to DO8
Right row:
• Software status (slow ash = OK)
• Communication with Service Tool
• Communication on LON
• Alarm when LED ashes
- 3 LED’s that are not used
• “Service Pin” switch has been activated
Address
Keep the safety
distance!
Low and high
voltage must not
be connected to
the same output
group
■ Power
■ Comm
■ DO1 ■ Status
■ DO2 ■ Service Tool
■ DO3 ■ LON
■ DO4
■ DO5 ■ Alarm
■ DO6
■ DO7
■ DO8 ■ Service Pin
Slow ash = OK
Quick ash = answer from gateway
Constantly ON = error
Constantly OFF = error
Flash = active alarm/not cancelled
Constant ON = Active alarm/cancelled
A small module (option board) can be placed on the bottom part
of the controller. The module is described later in the document.
The supply voltage to the module comes from the previous
module in the row.
AK-XM 204B only
Override of relay
Eight change-over switches at the front make it possible to
override the relay’s function.
Either to position OFF or ON.
In position Auto the controller carries out the control.
Light-emitting diodes
There are two rows with LED’s. They indicate the following:
Left row:
• Voltage supply to the controller
• Communication active with the bottom PC board (red = error)
• Status of outputs DO1 to DO8
Right row: (AK-XM 204B only):
• Override of relays
ON = override
OFF = no override
AK-XM 204A AK-XM 204B
Fuses
Behind the upper part there is a fuse for each output.
Max. 230 V
AC-1: max. 4 A (ohmic)
AC-15: max. 3 A (Inductive)
AK-XM 204B
Override of relay
Keep the safety distance!
Low and high voltage
must not be connected to
the same output group
The module is a real time clock module with battery backup.
The module can be used in controllers that are not linked up in
a data communication unit together with other controllers. The
module is used here if the controller needs battery backup for the
following functions
• Clock function
• Fixed times for day/night change-over
• Saving of alarm log in case of power failure
• Saving of temperature log in case of power failure
Connection
The module is provided with plug connection.
Placing
The module is placed on the PC board inside the top part.
Point
No point for a clock module to be dened – just connect it.
Working life of the battery
The working life of the battery is several years – even if there are
frequent power failures.
An alarm is generated when the battery has to be replaced.
After the alarm there are still several months of operating hours
left in the battery.
Display of important measurements from the controller, e.g.
suction pressure or condensing pressure.
Setting of the individual functions can be performed by using the
display with control buttons.
Connection
The extension module is connected to the controller module via
a cable with plug connections. You have to use one cable per
module. The cable is supplied in various lengths.
Both types of display (with or without control buttons) can be
connected to either display output A, and B.
A = P0 . Suction pressure in °C
B = Pc. Condensing pressure in °C
EKA 166 further includes a number of LEDs to make it possible to
follow individual functions.
When the controller starts up, the display will show which output
is connected. - - 1 = output A, - - 2 = output B, etc.
Placing
The extension module can be placed at a distance of up to 15 m
from the controller module.
EKA 163B EKA 164B
EKA 166
Module
Point--
Type--
1
Point
No point has to be dened for a display module – you simply
connect it.
Graphic display AK-MMI
Function
Setting and display of values in the controller.
Connection
The display connects to the controller via a cable with plug connections. Use plug RJ45 to connect to the controller; the same
plug is also used for service tool AK-ST 500.
Supply voltage
24 V a.c. / d.c. 1.5 VA.
Placing
The display can be placed at a distance of up to 3 m from the
controller.
Point
No point has to be dened for a display – you simply connect it.
Clock function and change-over between summer time and
winter time are contained in the controller.
The clock is zeroset when there is power failure.
The clock’s setting is maintained if the controller is linked up in a
network with a gateway, a system manager or a clock module can
be mounted in the controller.
Start/stop of regulation
Regulation can be started and stopped via the software or via an
input on the controller module
Application
40 examples of application are shown in the following: Select the
one that ts your system.
Wiring should be done as shown, and the controller should be
set for this application.
Regarding speed regulation
An option board has 2 outputs:
No. 1 is dedicated to the compressor
No. 2 is dedicated to the condenser fans
If you do not use speed control, disregard the shown 0-10 V
outputs.
It is only the compressor connection that is shown in all examples,
but output 2 can be used for condenser fans at will.
If the speed control needs a start/stop signal, this should be taken
from output "Compressor 1" or from "Fan 1".
Forced control
The software contains a forced control option. If an extension
module with relay outputs is used, the module’s top part can
be with change-over switches – switches that can override the
individual relays into either OFF or ON position.
Data communication
The controller module has terminals for LON data communication.
The requirements to the installation are described in a separate
document.
The basic module must not be connected to voltage.
Press in the plate on the left-hand side of the light-emitting
diodes and the plate on the right-hand side for the red address
changers.
Lift the top part o the basic module.
The analog extension module will supply a signal to the variable frequency drive.
Remove the protective cap from the connection plug on the
right-hand side of the basic module.
Place the cap on the connection plug to the right of the extension module that is to be mounted on the extreme right-hand
side of the AK assembly.
2. Assemble the extension module and the basic
module
The basic module must not be connected to voltage.
When the two snap catches for the DIN rail mounting are in the open
position, the module can be pushed into place on the DIN rail – regardless of where the module is on the row.
Disassembly is thus done with the two snap catches in the open position.
The sequence is determined by the shown electrical diagram
Decide during planning which function is to be connected and
where this will be.
1. Connect inputs and outputs
See the earlier selected electrical diagram:
2. Connect LON communication network
The installation of the data communication must comply with
the requirements set out in document RC8AC.
3. Connect supply voltage
Is 24 V, and the supply must not be used by other controllers or
devices. The terminals must not be earthed.
4. Follow light-emitting diodes
When the supply voltage is connected the controller will go
through an internal check. The controller will be ready in just
under one minute when the light-emitting diode ”Status” starts
ashing slowly.
5. When there is a network
Set the address and activate the Service Pin.
6. The controller is now ready to be congured.
Example
The screen on the pressure transmitter
cables must only be connected at the
end of the controller.
Internal communication
between the modules:
Quick ash = error
Constantly On = error
■ Power
■ Comm
■ DO1 ■ Status
■ DO2 ■ Service Tool
■ DO3 ■ LON
■ DO4
■ DO5 ■ Alarm
■ DO6
■ DO7
■ DO8 ■ Service Pin
Status on output 1-8
Slow ash = OK
Quick ash = answer from gateway
in 10 min. after network
installation
Constantly ON = error
Constantly OFF = error
External communication
Flash = active alarm/not cancelled
Constant ON = Active alarm/cancelled
Network installation
Warning
Keep signal cables separate from
cables with high voltage.
We have decided to work on the basis of application no. 16, i.e.
compressor control with 5 compressors and condenser control
with 6 fans.
The example is shown overleaf.
We have decided to describe the setup by means of an example
comprising a compressor group and a condenser.
The example is the same as the one given in the "Application no.
16", i.e. the controller is an AK-PC 710 + 3 extension modules.
Compressor pack:
• Refrigerant R134a
• 1 only speed-regulated compressor (30 kW, 30-60 Hz)
• 4 only compressors (15 kW) with working-hour equalisation
• Safety monitoring of each compressor
• Common high-pressure monitoring
• Common low-pressure monitoring
• Po setting -15°C, night displacement 5 K
Condenser:
• 6 fans, step regulation
• Pc regulates based on outdoor temperature Sc3
Receiver:
• Monitoring of liquid level in receiver
Plant room
• Monitoring of temperature in plant room
Safety functions:
• Monitoring of Po, Pc, Sd and superheat on suction line
• Po max = -5°C, Po min = -35°C
• Pc max = 50 °C
• Sd max = 120°C
• SH min = 5 °C, SH max = 35 °C
Other:
• Alarm output used
• External main switch used
• Monitoring of frequency converter (VSD)
For the example shown we use the following modules:
• AK-PC 710 basic module
• AK-XM 204B relay module
• AK-XM 102B digital input module
• AK-OB 110 analog output module
NB!
The capacity of the compressor with speed adjustment should be
greater than that of the other compressors.
This ensures that there are no "gaps" in the cut in capacity.
See chapter 5, Adjustment functions.
There is also an internal main switch as a setting. Both must be “ON”
before any adjustment is made.
PC with the program “Service Tool” is connected to the controller.
The controller must be switched on rst and the LED “Status” must
ash before the Service Tool programme is started.
Start Service Tool programme
For connecting and operating the "AK service tool" software,
please see the manual for the software.
The rst time the Service Tool is connected to a new version of a controller the start-up of the Service Tool will take longer than usual while
information is retrieved from the controller.
Time can be followed on the bar at the bottom of the display.
Login with user name SUPV
Select the name SUPV and key in the access code.
When the controller is supplied the SUPV access code is 123.
When you are logged into the controller an overview of it will always
appear.
In this case the overview is empty. This is because the controller has not
yet been set up.
The red alarm bell at the bottom right tells you that there is an active
alarm in the controller. In our case the alarm is due to the fact that the
time in the controller has not yet been set.
Press the orange setup button with the spanner at the bottom
of the display.
2. Select Authorization
3. Change setting for the user ‘SUPV‘
When the controller is supplied it has been set with standard authorization for dierent user interfaces. This setting should be changed and
adapted to the plant. The changes can be made now or later.
You will use this button again and again whenever you want to get to
this display.
On the left-hand side are all the functions not shown yet. There will be
more here the further into the setup we go.
Press the line Authorization to get to the user setup display.
4. Select username and access code
5. Carry out a new login with the user name and the
new access code
Mark the line with the user name SUPV.
Press the button Change
This is where you can select the supervisor for the specic system and a
corresponding access code for this person.
In earlier versions of the service tool AK-ST 500 it was possible to select
the language in this menu.
An updated version of the service tool will be released in the spring of
2009. If the controller is operated with the new version, language selection will happen automatically in connection with the conguration of
the service tool.
The controller will utilize the same language that is selected in the
service tool but only if the controller contains this language. If the
language is not contained in the controller, the settings and readings
will be shown in English.
To activate the new settings you must carry out a new login to the controller with the new user name and the relevant access code.
You will access the login display by pressing the padlock at the top left
corner of the display.
All system settings can be changed by pressing in the blue eld with the
setting and then indicating the value of the required setting.
In the rst eld you enter a name for what the controller will be controlling.
When the time is set the PC’s time can be transferred to the controller.
When the controller is connected to a network, date and time will
automatically be set by the system unit in the network. This also applies
to change-over Daylight saving.
If the controller is installed in a network, "automatic acknowledgement
of alarms" should be set to "disable" - Hereby the alarm processing and
acknowledgement is transferred to the system unit.
If the controller is installed without a network, "automatic acknowledgement of alarms" should be set to "enable" - Hereby the controller
acknowledges the alarms itself.
After conguration of this function, the controller will shut down
and restart. After the restart, a large number of settings will have
been made. These include the connection points. Continue with the
settings and check the values. If you change some of the settings,
the new values will.
The conguration menu in the Service
Tool has changed now. It shows the pos-
sible settings for the selected plant type.
In our example we select the settings:
- Suction set point = -15°C
- Night oset value = 5 K.
The settings are shown here in the display.
There are several pages, one after the
other.
The black bar in this eld tells you which
of the pages is currently displayed.
Move between the pages using the +
and - buttons.
In our example we select:
- Refrigerant = R134a
- Equalisation of working hours
- Value for speed regulation
Speed regulation can always only be on
compressor number 1.
The settings are shown here in the
display.
Not all compressors can have their speed
adjusted. If there is any doubt, contact your
compressor supplier.
If you want to know more about the dierent conguration options, they are listed below.
The number refers to the number and picture in the
column on the left.
The screen only shows the settings and readings that
are required for a given set-up.
3 - Po-Reference
Reference = set reference + night oset + oset
from P0 optimization
Setpoint ( -80 to +30°C)
Setting of required suction pressure in °C
Night Oset (-25 to +25 K)
Displacement value for suction pressure in connection with an active night setback signal (set in
Kelvin)
Changing to night-time operation can be carried
out with a signal sent via the data communication,
with a signal on the input "night" or via the weekly
schedule in the controller.
Max reference (-50 to +80 °C)
Max. permissible suction pressure reference
Min reference (-80 to +25 °C)
Min. permissible suction pressure reference
4 - Compressor application
Po refrigerant type
Select refrigerant type
Po refrigerant factors K1, K2, K3
Only used if “Po refrigerant type” is set to custom
(contact Danfoss for information)
Step control mode
Select coupling pattern for compressors
Sequential: Compressors are cut in/out in strict accordance with compressor number (FILO)
Cyclic: Runtime equalisation between compressors
(FIFO) (same sized compressors)
Best t: Compressors are cut in/out in order to
make the best possible t to actual load (dierent
sized compressors)
Pump down
Select whether a pump down function is required
on the last running compressor
Pump down limit (-80 to +30 °C)
Set the actual pump down limit for the last compressor
VSD min speed (0.5 – 60.0 Hz)
Min. speed where the compressor must cutout
VSD start speed (20.0 – 60.0 Hz)
Minimum speed for start of Variable speed drive
(Must be set higher than “VSD Min. Speed Hz”)
VSD max speed (40.0 – 120.0 Hz)
Highest permissible speed for the compressor
motor
Load shed limit
Set max capacity limit for load shed Load Shed"
Override limit Po
If the P0 exceeds the value, a time delay is started. If
the time delay runs out, the load limit is cancelled
Override delay
Max. time for capacity limit, if P0 is too high
Kp Po (0.1 – 10.0)
Amplication factor for P0 regulation
Advanced control settings
Select whether the adv. settings must be visible
Min. capacity change (0 – 100 %)
Set the minimum capacity change needed before
the capacity distributor connects or disconnects
compressors
Minimize cycling
The control zone may vary for connections and
disconnections. See Section 5.
Initial start time (15 – 900 s)
The time after start-up where the cut-in capacity is
limited to the rst compressor step.
- Speed-controlled compressor
of 30 kW (compressor 1)
- Four compressors of 25 kW
The example settings are shown
here in the display.
(For cyclic operation, all one-step
compressors have the same size.
This is why there is only one setting, but it covers all 4.)
In our example we select:
- Safety limit for discharge
temperature = 120°C
- Safety limit for high condensing
pressure = 50°C
- Safety limit for low suction
pressure = -35°C
- Alarm limit for high suction
pressure = -5°C
- Alarm limit for min. and max.
superheat, respectively = 5 and
35 K.
5 - Compressors
In this screen the capacity distribution between the compressors is dened.
Capacities that need to be set depend upon the “compressor
application” and “Step control mode” that has been selected.
Nominal capacity (0.0 – 99.9 kW)
Set the nominal capacity for the compressor in question.
For compressors with variable speed drive the nominal
capacity must be set for the mains frequency (50/60 Hz)
6 - Safety
Delay time for liquid level alarm
Set the delay time (from the time the signal is lost on the
input to the time when the alarm is sent)
Delay time for VSD-alarm
Set the delay time
Temperature alarm limit
Set the threshold value for the temperature alarm
Delay time for the temperature alarm
Set the delay time
Emergency cap. day
The desired cut-in capacity for daily use in the case of emergency operations resulting from error in the suction pressure
sensor/ media temperature sensor.
Emergency cap. night
The desired cut-in capacity for night operations in the case
of emergency operations resulting from error in the suction
pressure sensor/ media temperature sensor.
Sd max limit
Max. value for discharge gas temperature
10 K below the limit, the compressor capacity should be
reduced and the entire condenser capacity will be cutin.
If the limit is exceeded, the entire compressor capacity will
be cutout
Pc Max limit
Maximum value for the condenser pressure in °C
3 K below the limit, the entire condenser capacity will be
cutin and the compressor capacity reduced.
If the limit is exceeded, the entire compressor capacity will
be cutout.
Pc Max delay
Time delay for the alarm Pc max
P0 Min limit
Minimum value for the suction pressure in °C
If the limit is reduced, the entire compressor capacity will be
cutout.
P0 Max alarm
Alarm limit for high suction pressure P0
P0 Max delay
Time delay before alarm for high suction pressure P0.
Safety restart time
Common time delay before restarting the compressor.
(Applicable to the functions: "Sd max. limit", Pc max. limit"
and "P0 min. limit).
SH Min alarm
Alarm limit for min. superheat in suction line.
SH Max alarm
Alarm limit for max. superheat in suction line.
SH alarm delay
Time delay before alarm for min./max. superheat in suction
line.
Set min. OFF-time for the compressor relay
Set min. ON-time for the compressor relay
Set how often the compressor is
allowed to start
If the restrictions overlap, the
controller will use the longest
restriction time.
7 - Minimum operation times
Congure the operation times here so "unnecessary operation" can be avoided.
Min. OFF time
The time the compressor should be idle before it should start
again.
Min. ON time
The time the compressor should operate before it should
stop.
Restart time
The lowest time interval between two consecutive starts.
8 - Safety timer
Cutout delay
The time delay resulting from drop-out of automated safety
measures and until the compressor-error is reported.
Restart delay
Minimum time that a compressor should be OK after a safety
cut-out. After this interval it can start again.
(An alarm which is triggered by the automatic safety function
will be maintained until the restart delay has expired.)
In our example the condenser
pressure is controlled on the
basis of the outdoor temperature
(oating reference).
The settings shown here in the
display.
3 - PC reference
Reference Mode
Choice of condenser pressure reference
Fixed setting: Used if a permanent reference is required =
“Setting”
Floating: Used if the reference is changed as a function of Sc3
the external temperature signal, the congured "Dimensioning tm K"/"Minimum tm K" and the actual cut in compressor
capacity.
Setpoint
Setting of desired condensing pressure in °C. It should also be
set when oating references are used. The value is used as a
reference if the Sc3 sensor becomes defective.
Min. tm
Minimum average temperature dierence between Sc3 air
and Pc condensing temperature when no compressors are in
operation.
Dimensioning tm
Dimensioning average temperature dierential between Sc3
air and Pc condensing temperature at maximum load (tm
dierence at max load, typically 8-15 K).
Min reference
Min. permitted condenser pressure reference
Max reference
Max. permitted condenser pressure reference
Press the +-button to go on to the
next page
4. Set values for capacity regulation
Used in our example are six stepcontrolled fans.
The settings shown here in the
display.
4 - Capacity control
Capacity control mode
Select control mode for condenser
Step: Fans are step-connected via relay outputs
Step/speed: The fan capacity is controlled via a combination
of speed control and step coupling
Speed: The fan capacity is controlled via speed control (frequency converter)
Control type
Choice of control strategy
P-band: The fan capacity is regulated via P-band control. The
P band is congured as "Proportional band Xp"
PI-Control: The fan capacity is regulated by the PI controller.
Capacity curve
Choice of capacity curve type
Linear: The same amplication in the entire area
Square: Square curve shape, which gives higher amplication
at higher loads.
VSD start speed
Minimum speed for start of speed control (Must be congured higher than "VSD Min. Speed %")
VSD min Speed
Minimum speed whereby speed control is cut-out (low load).
!!! The alarm is inverted so that there will be an alarm if the supply
voltage to the controller fails.
Select for each input whether the function is to be active when the
input is in pos. Closed or Open.
Open has been selected here for all the safety circuits. This means
that the controller will receive signal under normal operation and
register it as a fault if the signal is interrupted.
The setup of the controller has now been locked. If you subsequently
want to make any changes in the controller’s setup, remember rst to
unlock the conguration.
The controller will now make a comparison of selected functions and dene inputs and outputs. The result can be seen in
the next section where the setup is controlled.
Before the control starts, we check that all the settings are as they should
be.
The overview display will now show one line for each of the general
functions. Behind each icon there is a number of displays with the
dierent settings. It is all these settings that have to be checked.
3. Move on through all the individual displays for the
suction group
Change displays with the +- button. Remember the settings at
the bottom of the pages – the ones that can only be seen via
the ”Scroll bar”.
4. Safety limits
5. Go back to the overview
The last page contains safety limits and restart times.
For your information
This setting is not necessary in the example. The signal comes in via DI8.
In other cases where the controller is installed in a network with one
system unit, this setting may be made in the system unit which will then
transmit a day/night signal to the controller.
This setting can only be used, if the controller stands alone and is tted
with a clock module.
Press a weekday and set the time for the day period.
Continue with the other days.
A complete weekly sequence is shown in the display.
Turn the right-hand address switch so that the arrow will point
at 3.
The arrow of the two other address switches must point at 0.
2. Push the Service Pin
Press down the service pin and keep it down until the Service
Pin LED lights up.
The controller has to be remote-monitored via a network. In this net-
work we assign address number 3 to the controller.
The same address must not be used by more than one controller in the
same network.
Requirement to the system unit
The system unit must be a gateway type AKA 245 with software version
6.0 or higher. It is capable of handling up to 119 AK controllers.
3. Wait for answer from the system unit
Depending on the size of the network it may be up to one
minute before the controller receives an answer as to whether
it has been installed in the network.
When it has been installed the Status LED will start to ash
faster than normal (once every half second). It will continue
with this for about 10 minutes
4. Carry out new login via Service Tool
If the Service Tool was connected to the controller while you
installed it in the network, you must carry out a new login to
the controller via the Service Tool.
Alternatively, it can be an AK-SM 720. It is capable of handling up to 200
AK controllers.
If there is no answer from the system unit
If the Status LED does not start ashing faster than normal, the controller has not been installed in the network. The reason for this may be
one of the following:
The controller has been assigned an address out of range
Address 0 cannot be used.
If the system unit in the network is an AKA 243B Gateway only the addresses between 1 and 10 can be used.
The selected address is already being used by another controller or
unit in the network:
The address setting must be changed to another (vacant) address.
The wiring has not been carried out correctly.
The termination has not been carried out correctly.
The data communication requirements are described in the document:
”Data communication connections to ADAP-KOOL® Refrigeration Controls” RC8AC.
Press the blue overview button with the compressor and condenser at the bottom left of the display.
2. Go to the Alarm list
Press the blue button with the alarm bell at the bottom of the
display.
3. Check active alarms
In our case, we have a series of alarms. We will tidy them up so that we
only have those that are relevant.
4. Remove cancelled alarm from the alarm list
Press the red cross to remove cancelled alarms from the alarm
list.
5. Check active alarm again
In our case an active alarm remains because the control has stopped.
This alarm must be active when control has not started. We are now
ready for the startup of control.
Please note that active plant alarms are automatically cancelled when the
main switch is in pos. OFF.
If active alarms appear when the control is started the reason for these
should be found and remedied.
The controller's functions as can be seen via display EKA 164, EKA
166 and via system software type AKM are shown on the following
pages.
For access to parameters, press and hold the top button.
r25Max reference °CWMax. permissible suction pressure reference-50,0 °C - 80,0 °C80,0 °C
r26Min Reference °CWMin. permissible suction pressure reference-80,0 °C - 25,0 °C-80,0 °C
r27Night setbackRActual status of night setbackON/OFF
r28Pc setpoint °CWSetting of desired condensing pressure in °C-25,0 °C - 90,0 °C35,0 °C
r29Cond. ctrl. Ref. °CRReference for condenser in °C
r30Min Reference °CWMin. permitted condenser pressure reference-25,0 °C - 100,0 °C10,0 °C
r31Max Reference °CWMax. permitted condenser pressure reference-25,0 °C - 100,0 °C50,0 °C
r32Pc sensor adjustWCalibration of Pc sensor-10,0 - 10,0 Bar0,0 bar
r33Pc Reference modeW"Choice of condenser pressure reference
0: Reference = Pc setpoint
1: The reference is changed as a function of Sc3 the external temperature
signal"
r35Dimensioning tm KWDimensioning mean temperature dierential between Sc3 air and Pc
condensing temperature at maximum load (compressor capacity = 100%).
Dimensioning temp dierence at max load, typically 8-15 K).
r56Min tm KWMinimum mean temperature dierence between Sc3 air and Pc condens-
ing temperature at no load (Compressor capacity = 0%)
r57Po °CRSuction pressure in °C. (Measured with the Po pressure transmitter)
Capacity control
c08Step modeW"Select coupling pattern for compressors
0: Sequential: Compressors are cut in/out in strict ac¬cordance with compressor number (FILO)
2: Cyclic: Runtime equalisation between compressors (FIFO)
3: Best t: Compressors are cut in/out in order to make the best possible t
to actual load"
c10+ Zone band KWWidth of “+ Zone” above neutral zone0,1 – 20,0 K4,0 K
c11+ Zone delay sWIntegrationtime in ”+ Zone” 10,0 – 900,0 s300 s
c12++ Zone delay sWIntegrationtime in ”++ Zone” 10,0 – 900,0 s300 s
c13- Zone band KWWidth of “- Zone” below neutral zone0,1 – 20,0 K3,0 K
c14- Zone delay sWIntegrationtime in ”- Zone” 10,0 – 900,0 s150 s
c15-- Zone delay sWIntegrationtime in ”-- Zone” 1,0 – 300,0 s30 s
c16Comp. applicationRReadout compressor combinations0: Single step only
c29No. of fansRRead out number of fans0 - 60
c31Manual capacity %W"Manual setting of compressor capacity
The value is in % of total capacity controlled by the controller"
c32Cap. control modeWSelect whether capacity control is stopped, in manual control or controlled
via PI controller
c33Po pump down limit°CWSet the actual pump down limit for the last compressor-80,0 °C - 30,0 °C-40,0 °C
c35Load shed limit 1WSet max compressor capacity limit for load shed input0 - 100%100%
c36Override limit PoWAny load below the limit value is freely permitted. If the suction pressure
Po exceeds the value, a time delay is started. If the time delay runs out, the
load limit is cancelled
c37Override delay 1 minWMax. time for capacity limit, if Po is too high0 - 240 min10 min
c38Pump downWSelect whether a pump down function is required on the last running
compressor
c39Initial start timeWThe time after start-up where the cut-in capacity is limited to the rst
compressor step.
c40Compressor 1 sizeW"Set the nominal capacity for the compressor in question.
For compressors with variable speed drive the nominal capacity must be
set for the mains frequency (50/60 Hz)
Set the nominal capacity for the compressor in question."
c41Compressor 2 sizeWSet the nominal capacity for the compressor in question.0,0 - 99,9 kW0 kW
c42Compressor 3 sizeWSet the nominal capacity for the compressor in question.0,0 - 99,9 kW0 kW
c43Compressor 4 sizeWSet the nominal capacity for the compressor in question.0,0 - 99,9 kW0 kW
c44Compressor 5 sizeWSet the nominal capacity for the compressor in question.0,0 - 99,9 kW0 kW
c45Compressor 6 sizeWSet the nominal capacity for the compressor in question.0,0 - 99,9 kW0 kW
c46VSD Min speed HzWMin. speed where the compressor must cutout0,5 Hz60,0 Hz
c47VSD Start speed HzWMinimum speed for start of Variable speed drive (Must be set higher than
“VSD Min. Speed Hz”)
c48VSD Max speed HzWHighest permissible speed for the compressor motor40,0 Hz120,0 Hz
c49Emergency cap day%WThe desired cut-in capacity for daily use in the case of emergency opera-
tions resulting from error in the suction pressure sensor/ media temperature sensor
c50Emergency cap. night%WThe desired cut-in capacity for night operations in the case of emergency
operations resulting from error in the suction pressure sensor/ media
temperature sensor.
Compressor timers
c51Comp. 1 Min. ON-timeWMinimum duration of ON period0 - 60 min0 min
c52Comp. 2 Min. ON-timeWMinimum duration of ON period0 - 60 min0 min
c53Comp. 3 Min. ON-timeWMinimum duration of ON period0 - 60 min0 min
c54Comp. 4 Min. ON-timeWMinimum duration of ON period0 - 60 min0 min
c55Comp. 5 Min. ON-timeWMinimum duration of ON period0 - 60 min0 min
c56Comp. 6 Min. ON-timeWMinimum duration of ON period0 - 60 min0 min
c57Comp. 1 Min. OFF-timeWMinimum duration of OFF periode0 - 30 min0 min
c58Comp. 2 Min. OFF-timeWMinimum duration of OFF periode0 - 30 min0 min
c59Comp. 3 Min. OFF-timeWMinimum duration of OFF periode0 - 30 min0 min
c60Comp. 4 Min. OFF-timeWMinimum duration of OFF periode0 - 30 min0 min
c61Comp. 5 Min. OFF-timeWMinimum duration of OFF periode0 - 30 min0 min
c62Comp. 6 Min. OFF-timeWMinimum duration of OFF periode0 - 30 min0 min
c63Comp. 1 Recycle timeWMinimum period between two successive compressor starts1 - 60 min6 min
c64Comp. 2 Recycle timeWMinimum period between two successive compressor starts1 - 60 min6 min
c65Comp. 3 Recycle timeWMinimum period between two successive compressor starts1 - 60 min6 min
c66Comp. 4 Recycle timeWMinimum period between two successive compressor starts1 - 60 min6 min
c67Comp. 5 Recycle timeWMinimum period between two successive compressor starts1 - 60 min6 min
c68Comp. 6 Recycle timeWMinimum period between two successive compressor starts1 - 60 min6 min
Neutral zone control
n04Xp P-band KWProportional band for condenser P/PI controller0,0 - 100,0 K10,0 K
n05Tn Integr. time sWIntegration time for condenser PI controller30 - 600 sec180 sec
n20Kp PoWAmplication factor for compressor capacity control0,1 - 10,02
n52Control modeW"0: MAN (The condenser capacity will be controlled manually)
1: OFF (The capacity control will be stopped)
2: AUTO (The capacity is controlled by the PI controller)"
n53Manual capacity %WManual setting of condenser capacity0 - 100%0%
n54VSD Start speed %WCondenser minimum speed for start of speed control (Must be congured
higher than "VSD Min. Speed %")
n55VSD Min. speed %WCondenser minimum speed whereby speed control is cut-out (low load).0,0 - 40,0 %10,0%
0: Step: Fans are step-connected via relay outputs
1: Step/speed: The fan capacity is controlled via a combination of speed
control and step coupling
2: Speed: The fan capacity is controlled via speed control (frequency
converter)"
n95Control typeW"Choice of control strategy for condenser
0: P-band: The fan capacity is regulated via P-band control. The P band is
congured as ""Proportional band Xp""
1: PI-Control: The fan capacity is regulated by the PI controller"
Alarm/Safety Settings
A03Saux 1 High alarm delWAlarm delay for high Saux temperature0 - 360 min5 min
A10Po Max alarm °CWAlarm limit for high suction pressure Po-30,0 °C - 100,0 °C100,0 °C
A11Po Min limit °CW"Minimum value for the suction pressure in °C
If the limit is reduced, the entire compressor capacity will be cutout."
A28Low liquid level delayWTime delay for the low liquid level alarm0 - 360 min5 min
A30Pc Max limit °CW"Maximum value for the condenser pressure in °C
3 K below the limit, the entire condenser capacity will be cutin and the
compressor capacity reduced.
If the limit is exceeded, the entire compressor capacity will be cutout."
A35Saux 1 High alarm °CWHigh temp. alarm limit for Saux sensor-80,0 °C - 120,0 °C120,0 °C
A44Po Max delay mWTime delay before alarm for high suction pressure P0.0 - 240 min5 min
A45Pc Max alarm delay mWTime delay for the alarm Pc max0 - 240 min0 min
A58Sd max limit°CW"Max. value for discharge gas temperature
10 K below the limit, the compressor capacity should be reduced and the
entire condenser capacity will be cutin.
If the limit is exceeded, the entire compressor capacity will be cutout"
A59SH min alarm KWAlarm limit for min. superheat in suction line.0,0 - 20,0 K0,0 K
A60SH max alarm KWAlarm limit for max. superheat in suction line.20,0 - 80,0 K80,0 K
A61SH alarm delayWTime delay before alarm for min./max. superheat in suction line.0 - 60 min5 min
A62Safety restart time mW"Common time delay before restarting the compressor.
(Applicable to the functions: ""Sd max. limit"", Pc max. limit"" and ""P0 min.
limit)."
A64VSDcutoutDelWTime delay before VSD alarm0-360 min5 min
Misceallanous
o12Mains frequencyWSelect frequency of the power supply0: 50 Hz
o19No. of compressorsRReadout number of compressors0 - 60
o50Comp. 5 RuntimeWCompressor’s total run time in hours0 - 999999 h0 h
o51Comp. 6 RuntimeWCompressor’s total run time in hours0 - 999999 h0 h
o61Quick setup selectW"Select a predened application.
Gives a choice between a number of prede¬ned applicatons, which at the
same time determine the wiring connection points.
(see manual for further details)"
o93Conguration lockWThe controller can only be congured when it is unlocked.0: Unlocked
P40Auto ack alarmsWSelect whether the controller should auto acknowledge alarms. In stand
A02Low suction pressure PoMinimum safety limit for suction pressore Po has been violated
A11Refrigerant A not selectedRefrigerant has not been selected
A17High Cond. pressure PcHigh safety limit for condensing pressure Pc has been violated
A19Comp. 1 safety cutoutCompressor no. 1 has been cut out on safety input
A20Comp. 2 safety cutoutCompressor no. 2 has been cut out on safety input
A21Comp. 3 safety cutoutCompressor no. 3 has been cut out on safety input
A22Comp. 4 safety cutoutCompressor no. 4 has been cut out on safety input
A23Comp. 5 safety cutoutCompressor no. 5 has been cut out on safety input
A24Comp. 6 safety cutoutCompressor no. 6 has been cut out on safety input
A28Low liquid levelLow liquid level alarm input has been activated
A31LP common safetyCompressors have been cut out on common LP safety input
A32HP common safetyCompressors have been cut out on common HP safety input
A34Common fan safetyCommon fan safety input has been activated
A35Air room High temp.The temperature measured by Saux 1 sensor is too high
A45Main switchControl has been stopped via the setting ”Main Switch” = OFF or via the
A85High discharge temp. SdSafety limit for discharge temperature has been exceeded
A86High superheat SsSuperheat in suction line too high
A87Low superheat SsSuperheat in suction line too low
A88System Critical excep-
tion #1
A89Manual DI………. An input has been set in manual control mode via the service tool software
A93VSD safety cutoutVSD alarm input has been activated
E02Po sensor errorPressure transmitter signal from Po defective
Ss sensor errorTemperature signal from Ss suction gas temp. defective
Sd sensor errorTemperature signal from Sd discharge gas temp. Sd defective
Pc sensor errorPressure transmitter signal from Pc defective
Sc3 sensor errorTemperature signal from Sc3 air on condenser defective
Saux1 sensor errorSignal from extra temp. sensor Saux1 defective
System alarm exception #1
Alarm Destination
disabled
Alarm Route failureAlarms can not be send to the alarm receiver – check the communication
Alarm Router fullThe internal buer for alarm has been exceeded. This can happen if the
Device is restartingRestart of controller after a ash update of the software
Common IO AlarmA communication problem has arised between the controller and the
Manual DO………An output has been set in manual control mode via the service tool
- - 1Initiation. Display is connected to output A. (- - 2 = output B, etc.)
external main switch input
A critical system fault has arisen – the controller needs to be exchanged
A minor system fault has arisen – power OFF/ON the controller
When this alarm is active the alarm transmission to the alarm receiver
has been disabled. When the alarm is cancelled the alarm transmission is
enabled
to controller/alarm receiver
alarm transmission to the alarm receiver is interrupted – see above.
extension modules – the problem should be checked immediately
The capacity distributor can regulate according to the suction
pressure P0.
Night displacement
The function is used to change the suction pressure reference for
night time operation as an energy saving function.
With this function the reference can be displaced by up to 25 K
in positive or negative direction. (When you displace to a higher
suction pressure, a positive value is set).
Displacement can be activated in three ways:
• Signal on an input
• From a master gateway’s override function
• Internal time schedule
The “night displacement” function should not be used when
regulation with the override function “P0-optimisation” is performed.
(Here the override function will itself adapt the suction pressure to the
max. permissible).
If a short change in the suction pressure is needed (for example,
up to 15 minutes in connection with defrosting) the functions
can be applied. Here the PO-optimisation will not have time to
compensate for the change.
Handling of sensor error
An error in the sensor will mean that regulation continues with
50% cutin in daily operation and 25% cut-in at night, but for a
minimum of one step.
Reference
P0Ref = P0 setting + P0 optimization + night displacement
P0 setting
A basic value for the suction pressure is set.
P0 optimization
This function displaces the reference so that regulation will not
take place with a lower suction pressure than required.
The function cooperates with controllers on the individual
refrigeration appliances and a system manager. The system
manager obtains data from the individual regulations and adapts
the suction pressure to the optimum energy level. The function is
described in the manual for the System manager.
With this function you can read which appliance is most heavily
loaded at the moment as well as the displacement allowed for the
suction pressure reference.
Limitation of reference
To safeguard yourself against a too high or too low regulation
reference, a limitation of the reference must be set.
P0 ref
Max.
Min.
Forced operation of the compressor capacity in the suction
group
A forced operation of the capacity can be carried out which
disregards the normal regulation.
Depending on the selected form of forced operation, the safety
functions will be cancelled.
Forced operation via overload of requested capacity
The control is set to manual and the desired capacity is set in % of
the possible compressor capacity.
Forced operation via overload of digital outlets
The individual outputs can be set to MAN ON or MAN OFF in the
software. The control function disregards this but an alarm is sent
out that the outlet is being overridden.
Forced operation via change-over switches
If the forced operation is done with the switch-over on the front of
an expansion model, this is not registered by the control function and no alarm is sounded. The controller continues to run and
couples with the other relays.
AK-PC 710 can control up to 6 compressors.
One of the compressors can be equipped with speed regulation.
In the “- Zone” and “-- Zone” the controller will normally decrease
the requested capacity as the suction pressure is below the
set point. But if the suction pressure is increasing very fast the
requested capacity might increase also in these zones.
The calculation of the requested compressor capacity takes place
on the basis of a PI control, but the set up is carried out in the
same way as for a neutral zone which is divided into 5 dierent
control zones as shown in below sketch.
Suction pressure P0
The width of some of the zones can be set via the settings “+ Zone
K”, “NZ K” and “- Zone K”.
Furthermore it is possible to adjust zone timers which is equal to
the Tn integration time for the PI controller whenever the suction
pressure is in the zone in question (please see sketch above).
By setting a zone timer to a higher value will make the PI controller
slower in this zone and by setting the zone timer lower will make
the PI controller faster in this zone.
Change capacity
The controller will cutin or cutout capacity based on these basic
rules:
Increase capacity:
The capacity distributor will start extra compressor capacity as
soon as the requested capacity has increased to a value, which
allows the next compressor step to start. Referring to below
example - a compressor step is added as soon as there is “Room”
for this compressor step below the requested capacity curve.
Decrease capacity:
The capacity distributor will stop compressor capacity as soon
as the requested capacity has decreased to a value, which allows
the next compressor to stop. Referring to below example - a
compressor step is stopped as soon as there is no more “Room” for
this compressor step above the requested capacity curve.
Example:
4 compressor of equal size - The capacity curve will look like this
The amplication factor Kp is adjusted as parameter ”Kp Po”
In the neutral zone the controller is only allowed to increase or
decrease the capacity by means of speed control and/or switching
of unloader valves.
In the other zones the controller is also allowed to increase/
decrease capacity by means of starting and stopping compressors.
Operation time rst step
At start-up the refrigeration system must have time to be stable
before the PI controller takes over the control. For this purpose
at start-up of a plant a limitation is made of the capacity so that
only the rst capacity step will cutin after a set period (to be set via
"runtime rst step").
Requested capacity
The readout “Requested capacity” is the output from the PI
controller and it shows the actual requested compressor capacity
by the PI controller. The rate of change in the requested capacity
depends upon in which zone the pressure is and whether the
pressure is stable or whether it is constantly changing.
The Integrator is looking at the deviation between the set point
and the current pressure only and increases/reduces the requested
capacity correspondingly. The amplication factor Kp on the other
hand only looks at the temporary pressure changes.
Cut-out of the last compressor stage:
Normally, the last compressor step will only be cut-out when the
required capacity is 0% and the suction pressure is at "-Zone" or in
"—Zone"
Pump down function:
To avoid too many compressor starts/stops with low load, it is possible to dene a pump down function for the last compressor.
If the pump down function is used, the compressors will be cutout when the actual suction pressure is down to the congured
pump down limit.
Note that the congured pump down limit should be set higher
than the congured safety limit for low suction pressure "Min Po".
In the “+ Zone” and “++ Zone” the controller will normally increase
the requested capacity as the suction pressure is above the
set point. But if the suction pressure is decreasing very fast the
requested capacity might decrease also in these zones.
All refrigeration systems have a dynamic response time when
starting and stopping compressors. In order to avoid that the
controller will start/stop compressors shortly after each other, the
controller must be allowed some extra time after a compressor
start/stop to see the eect of the previous change in running
capacity.
In order to achieve this, a dynamic extension of the zones is
added.
Capacity distribution methods
The capacity distributor can work based on 3 distribution
principles.
Coupling pattern – sequential operation:
The compressors are cut in and cut-out following the “First in, Last
out” (FILO) principle in accordance with the sequence dened in
the set-up.
Any speed-regulated compressors are used to close capacity gaps.
The zones will be extended for a short period of time when
starting or stopping a compressor. By extending the zones the
PI controller will be slowed down in a short period of time after a
change in compressor capacity.
The amplitude of the zone extension depends upon the actual
running compressor capacity and upon the size of the compressor
step which is being stopped/started. The amplitude of the zone
extension is bigger when running with low compressor capacity
and when starting/stopping big compressor capacity steps.
However the time period for the zone extension is constant – after
a xed time period after a compressor start/stop the dynamic
zone extension is reduced to 0.
Via the “Minimize number of couplings” setting it is possible to
inuence how big the amplitude of the dynamic zone extension
should be in order to minimize the cycling of the compressors.
By setting “Minimize number of couplings” to “No reduction” there
will be no dynamic extension of the zones.
By setting “Minimize number of couplings” to “Low”, “Medium” or
“High” the dynamic extension of the zones will be activated. The
amplitude of the zone extension will be highest when “Minimize
number of couplings” is set to “High”. Please refer to the next
sketch which shows an example with 6 compressor steps and with
“Minimize number of couplings” set to “High”. Please also note that
the dynamic extension of the zones is highest at low compressor
capacity.
“Minimize number of couplings” = “High”
Timer restrictions
If a compressor is prevented from starting because it “hangs” on
the re-start timer, this step is not replaced by another compressor
but the step switch waits until the timer has lapsed.
Safety cutout
If on the other hand there is a safety switch on this compressor,
this is excluded and the step switch immediately selects the
following step in the sequence.
Coupling pattern – Cyclical operation:
This principle is used if all compressors are of the same type and
size.
The compressor cuts-in and cuts-out in accordance with the "First
In First Out" principle (FIFO) to equalise operating hours between
the compressors.
Speed-regulated compressors will always be cut in rst, and the
variable capacity is used to ll capacity gaps between the subsequent steps.
Timer restrictions and safety cut outs
If a compressor is prevented from starting because it is “hanging”
on the restart timer or is safety cut out, this step is replaced by
another compressor.
Operating time equalisation
The operating hour equalizing is carried out between compressors
of the same type with the same total capacity.
-At the dierent startups the compressor with the lowest number
of operating hours will be started rst.
- At the dierent stops the compressor with the highest number of
operating hours will be stopped rst.
- For compressors with several steps, the operating time equalizing
is carried out between the compressors’ main steps.
Coupling pattern – Best t operation
This principle is used if the compressors are of dierent sizes.
The capacity distributor will cut-in or cut-out the compressor
capacity in order to ensure the least possible capacity jump.
Speed-regulated compressors will always be cut in rst, and the
variable capacity will be used to ll capacity gaps between the
subsequent steps.
Timer restrictions and safety cut outs
Actual band
As a consequence of the dynamic extension of the zones the
suction pressure might very well change zone for a period of
time when the controller is starting/stopping a compressor i.e.
the suction pressure is in the +Zone, but as the controller starts
a compressor, the zones are extended for a period of time and
during this period of time the suction pressure will be in the NZ.
In the controller the readout “Actual band” will show in which zone
the PI controller is operating – this includes the extension of the
zones.
If a compressor is prevented from starting because it is “hanging”
on the restart timer or is safety-cut out, this step is replaced by
another compressor or another combination.
Minimum capacity change
To prevent the capacity distributor from selecting a new compressor combination (cut-out and cut-in compressors) due to a small
change in capacity requirements, it is possible to set a minimum
change in capacity requirement that will operate before the capacity distributor changes to a new compressor combination.
Power pack types – compressor combinations
The controller is able to control power packs with up to 6
compressors of various types:
- One speed controlled compressor
- Single step compressors – piston or scroll
The chart below shows the compressor combination which the
controller is capable of controlling. The chart also shows which
coupling pattern can be set for the individual compressor combinations.
CombinationDescriptionCoupling
One-step compressors. *1xxx21-40
pattern
Sequence
Cyclical
Application
Best t
*1) For a cyclical coupling pattern, the one-step compressors must be the same size.
*2) Speed-regulated compressors can have dierent sizes in relation to subsequent
compressors.
A speed-regulated compressor combined with
one-step compressors. *1
and *2
xxx1-20
In appendix A there is a more detailed description of the coupling
patterns for the individual compressor applications with associated examples.
The following is a description of some general rules for handling
speed-regulated compressor.
The controller is able to use speed control on the leading
compressor in dierent compressor combinations. The variable
part of the speed controlled compressor is used to ll in capacity
gaps of the following compressor steps.
General regarding handling:
One of the dened capacity steps for the compressor regulation
may be connected to a speed control unit that may be a
frequency converter type VLT, for example.
An output is connected to the frequency converter’s ON/OFF
input and at the same time an analog output ”AO” is connected to
the frequency converter’s analog input.
The ON/OFF signal will start and stop the frequency converter and
the analog signal will indicate the speed.
It is only the compressor dened as compressor 1 that can be
speed controlled.
When the step is in operation it will consist of a xed capacity
and a variable capacity. The xed capacity will be the one that
corresponding to the mentioned min. speed and the variable
one will lie between the min. and max. speed. To obtain the
best regulation the variable capacity must be bigger than the
subsequent capacity steps it has to cover during the regulation.
If there are major short-term variations in the plant’s capacity
requirement it will increase the demand for variable capacity.
This is how you cut the step in and out:
Controlling – increasing capacity
If the need for capacity becomes larger than “Max. Speed” then
the subsequent compressor step will be cut-in. At the same time,
the speed on the capacity step will be reduced so the capacity
is reduced with a size that corresponds to exactly the cut-in
compressor step. Thereby a completely "frictionless" transition is
achieved without capacity holes (refer also to sketch).
Controlling – decreasing capacity
If the capacity requirement becomes less than “Min. speed” then
the subsequent compressor step will be cut-out. At the same
time, the speed on the capacity step is increased so the capacity
is increased with a size that corresponds to exactly the cut-out
compressor step.
Cut-out
The capacity step will be cut-out when the compressor has
reached “Min. Speed” and the requested capacity has dropped to
1%.
Timer restriction on speed controlled compressor
If a speed controlled compressor is not allowed to start due to a
timer restriction, no other compressor is allowed to start. When
the timer restriction has expired the speed controlled compressor
will start.
Cutin
The speed-controlled compressor will always be the rst to start
and the last to stop. The frequency converter will be started when
a capacity requirement corresponding to the mentioned ”Start
speed” arises (the relay output changes to ON and the analog
output is supplied with a voltage corresponding to this speed).
It is now up to the frequency converter to bring the speed up to
”Start speed”.
The capacity step will now be cut in and the required capacity
determined by the controller.
The start speed always ought to be set so high that a fast
lubrication of the compressor is obtained during the start.
Safety cutout on speed controlled compressor
If the speed controlled compressor is cutout on safety other
compressors are allowed to start. As soon as the speed controlled
compressor is ready to start it will be the rst compressor to start.
As mentioned before the variable part of the speed capacity
should be bigger than the capacity of the following compressor
steps in order to achieve a capacity curve without “holes”. In order
to illustrate how the speed control will react at dierent pack
combinations a couple of examples will be given here:
a) Variable capacity bigger than following compressor steps:
When the variable part of the speed controlled compressor is
bigger than the following compressors there will be no “holes” in
the capacity curve.
Example:
1 speed controlled compressor with a nominal capacity at 50Hz of
10kw - Variable speed range 30 – 90Hz
2 one step compressors of 10 kW
As the variable part of the speed controlled compressor is bigger
than the following compressor steps, the capacity curve will be
without holes.
1) The speed controlled compressor will be cutin when the
requested capacity has reached the start speed capacity.
2) The speed controlled compressor will increase speed until it
reaches max speed at a capacity of 18 kw.
3) The one step compressor C2 of 10 kW is cut in and the speed on
C1 is reduced too so that it corresponds to 8kW (40Hz)
4) The speed controlled compressor will increase speed until the
total capacity reaches 28 kw at max speed
5) The one step compressor C3 of 10kW is cut in and the speed on
C1 is reduced too so that it corresponds to 8kW (40Hz)
6) The speed controlled compressor will increase speed until the
total capacity reaches 38 kw at max speed
7) When reducing capacity the one step compressors will be cut
out when the speed on C1 is at minimum
As the variable part of the speed controlled compressor is smaller
than the following compressor steps the capacity curve will have
some holes that can not be lled out by the variable capacity.
1) The speed controlled compressor will be cutin when the
requested capacity has reached the start speed capacity.
2) The speed controlled compressor will increase speed until it
reaches max speed at a capacity of 20 kw.
3) The speed controlled compressor will stay at max speed until
the requested capacity has increased to 30 kW.
4) The one step compressor C2 of 20 kW is cut in and the speed
on C1 is reduced to min. so that it corresponds to 10kW (25Hz).
Total capacity = 30 kW.
5) The speed controlled compressor will increase speed until the
total capacity reaches 40 kW at max speed
6) The speed controlled compressor will stay at max speed until
the requested capacity has increased to 50 kW.
7) The one step compressor C3 of 20kW is cut in and the speed
on C1 is reduced to min. so that it corresponds to 10kW (25Hz).
Total capacity = 50 kW
8) The speed controlled compressor will increase speed until the
total capacity reaches 60 kw at max speed
9) When reducing capacity the one step compressors will be cut
out when the speed on C1 is at minimum speed.
Compressor timers
Time delays for cutins and cutouts
To protect the compressor against frequent restarts three time
delays can be put in.
- A minimum time to run from a compressor’s startup and until it
may be restarted.
- A minimum time (ON-time) for the compressor to operate before
it may be stopped again.
- A minimum OFF time to run from a compressor stops and until it
may be restarted
When unloaders are cut in and out, the time delays will not be
used.
b) Variable part smaller than following compressor steps:
If the variable part of the speed controlled compressor is smaller
than the following compressors there will be “holes” in the
capacity curve.
Example:
1 speed controlled compressor with a nominal capacity at 50Hz of
20kw - Variable speed range 25 – 50Hz
2 one step compressors of 20 kW
Fixed capacity = 25 HZ / 50 HZ x 20 kW = 10 kW
Variable capacity = 25 HZ / 50Hz x 20 kW = 10 kW
The operating time of a compressor motor is registered continuously. You can read out:
- operating time for the previous 24-hour period
- total operating time since the timer was last set to zero-set.
Coupling counter
The number of relay cutins and cutouts is registered continuously.
The number of starts can be read out here:
- Number during the previous 24-hour period
- Total number since the counter was last set to zero-set.
Load shedding
On some installations there is the desire to limit the cut-in compressor capacity so that one can limit the total electrical load in
the store for periods.
There is 1 digital inlet available for this purpose.
For digital inlet a limit value is attached for the maximum allowable cut-in compressor capacity.
When a inlet is activated, the maximum allowable compressor
capacity is limited to the set limit. This means that if the actual
compressor capacity upon activation of the digital inlet is higher
than this limit, then so much compressor capacity is cut-out that
it will then be on or under the set maximum limit value for this
digital inlet.
Overriding of load shedding:
To avoid load shedding leading to temperature problems for the
chilled products, an overriding function is tted.
A overriding limit is set for the suction pressure as well as a delay
time for the digital inlet.
Injection ON
The electronic expansion valves in the refrigeration appliances
must be closed when all the compressors are stopped and a
restart is blocked. In this way the evaporators will not be lled with
liquid which is subsequently passed on to a compressor when
regulation is restarted.
The function can be attained via data communication.
The function is described based on the sequence of events below:
T1) The last compressor is cut-out
T2) The suction pressure has increased to a value corresponding
to Po Ref + NZ + “+Zone K” but no compressor can start due to
re-start timers or safety cut-out
T3) The time delay “Injection OFF delay” elapses and the injection
valves are forced to close via network signal.
T4) The rst compressor is now ready to start. The forced closure
signal via the network is now cancelled.
T5) The time delay “Comp. Start delay” expires and the rst
compressor being allowed to start.
The reason why the forced closure signal via the network is
cancelled before the rst compressor starts, is that it will take
some time to distribute the signal to all appliance controllers via
the network.
If the suction pressure during load shedding exceeds the set overriding limit and delay times expire then load shedding overrides
the signals so that the compressor capacity can be increased until
the suction pressure is again under the normal reference value.
The load shedding can then be activated again.
Alarm:
When load shedding inlet is activated, an alarm will be activated
to inform that the normal control has been bypassed. This alarm
can however be suppressed if so desired.
The controller can monitor the status of each compressor’s safety
circuit. The signal is taken directly from the safety circuit and
connected to an input.
(The safety circuit must stop the compressor without involving the
controller).
If the safety circuit is cut out the controller will cut out the relay
for the compressor in question and give an alarm. Regulation will
continue with the other compressors.
Common safety circuit
A common safety signal can also be received from the whole suction group. All compressors will be cut out when the safety signal
cuts out.
The alarm is cancelled and renewed cutin of compressor steps is
permitted when the following conditions are met:
- the temperature has dropped to 10 K below the limit value
- the time delay prior to restart has been passed. (see later)
Normal condenser control is permitted again when the
temperature has dropped to 10 K below the limit value.
Monitoring of min. suction pressure (P0)
The function promptly cuts out all compressor steps if the suction
pressure becomes lower than the permitted value.
The cutout limit can be dened in the range from -120 to +30°C.
The suction is measured with pressure transmitter P0.
At cutout the the alarm function is activated:
The alarm is cancelled and renewed cutin of compressor steps is
permitted when the following conditions are met:
- the pressure (temperature) is above the cutout limit
- the time delay has elapsed (see later).
Monitoring of max. condensing pressure (Pc)
The function cuts in all condenser steps and cuts out compressor
steps one by one if the condensing pressure becomes higher than
permitted. The cutout limit can be dened in the range from –30
to +100°C.
The condensing pressure is measured with pressure transmitter
Pc.
Time delays with safety cut-out:
In connection with safety monitoring of a compressor it is possible
to dene two delay times:
• Cut-out delay time: Delay time from alarm signal from the safety
circuit until the compressor outlet cuts out (note that the delay
time is common to all security inlets)
• Safety re-start time: The minimum time a compressor must be OK
after a safety cut-out until it may start again.
Monitoring of superheat
This function is an alarm function which continuously receives
measured data from suction pressure P0 and suction gas Ss.
If superheat is registered which is lower or higher than the set limit
values, an alarm will be given when the time delay has passed.
Monitoring of max. discharge gas temperature (Sd)
The function gradually cuts out compressor steps if the discharge
temperature becomes higher than permitted. The cutout limit can
be dened in the range from 0 to +150°C.
The function is started at a value that is 10 K below the set value.
At this point the entire condenser capacity is cut in at the same
time as 33% of the compressor capacity is cut out (but minimum
one step). This is repeated every 30 seconds. The alarm function is
activated.
If the temperature rises to the set limit value all compressor steps
are immediately cut out.
The function takes eect at a value which is 3 K below the set
value. At this time the entire condenser capacity is cut in at the
same time as 33% of the compressor capacity is cut out (but min.
one step). This is repeated every 30 seconds. The alarm function is
activated.
If the temperature (pressure) rises to the set limit value, the
following will happen:
- all compressor steps will immediately be cut out
- the condenser capacity will remain cut in
The alarm will be cancelled and renewed cutin of compressor
steps is permitted when the following conditions are met:
- the temperature (pressure) falls to 3 K below the limit value
- the time delay for restart has been passed.
Delay of Pc max alarms
It is possible to delay the “Pc max alarm" message.
The controller will still disconnect the compressors, but the sending of the alarm itself is delayed.
Time delay
There is a joint time delay for “Monitoring of max. discharge gas
temperature” and “Min. suction pressure” and monitoring of max
condensing pressure Pc.
Alarm for too high suction pressure
An alarm limit can be set which will become eective when the
suction pressure becomes too high. An alarm will be transmitted
when the set time delay has been passed. The regulation
continues unchanged.
Capacity control of the condenser can be accomplished via step
regulation or speed control of the fans.
• Step regulation
The controller can control up to 6 condenser steps that are cut in
and out sequentially.
• Speed control
The analog output voltage is connected to a speed control. All
fans will now be controlled from 0 to max. capacity. If an ON/OFF
signal is required it can be obtained from fan 1 relay.
Regulation can be carried out based on one of the following two
principles:
- all fans operate at the same speed
- Only the necessary number of fans is cut in.
Capacity control of condenser
The cut-in condenser capacity is controlled by the condenser pressure’s actual value and depends on whether the pressure is rising
or falling. Regulation is performed by a PI controller which may
however be changed into a P controller if the design of the plant
necessitates this.
On some units, compensation is already made for the "problem"
described above, by binary connection of the condenser fans: i.e.
a few fans are connected at low capacity and many fans at high
capacity, for example 1-2-4-8 etc. In this case, the non-linear amplication is already compensated for, and there is no need for an
arc-shaped capacity curve.
It is therefore possible to choose on the controller whether you
require an arc-shaped or a linear capacity curve to manage the
condenser capacity.
Capacity curve = Linear / Power
Requested capacity Requested capacity
Capacity curve = Power Capacity curve = Linear
Regulating sensor
The capacity distributor regulates from the condenser pressure PC.
Handling sensor errors:
An error in the signal will result in a cut-in of 100% condenser
capacity, but the compressor regulation will remain normal.
PI regulation
The controller cuts in capacity in such a way that the deviation
between the actual condensing pressure and the reference value
becomes as small as possible.
P regulation
The controller cuts in capacity that depends on the deviation
between the actual condensing pressure and the reference value.
The proportional band Xp indicates the deviation at 100%
condenser capacity.
Capacity curve
On air-cooled condensers, the rst capacity step will always give
comparatively more capacity than the subsequent capacity steps.
The increase in capacity produced by each extra step decreases
gradually as more and more steps are cut in.
This means that the capacity controller requires more amplication at high capacities than at low capacities. Consequently, the
capacity controller for condenser regulation functions with an
arc-shaped capacity curve so that amplication is optimal at both
high and low capacities.
Reference for condensing pressure
The reference for the regulation can be dened in two ways. Either
as a xed reference or as a reference that varies according to the
outdoor temperature.
Fixed reference
The reference for the condensing pressure is set in °C.
Floating reference
This function allows the condensing pressure’s reference value to
vary according to the outdoor temperature within a dened area.
By combining oating condensing pressure with electronic
expansion valves a lot of energy saving can be achieved. The
electronic expansion valves enables the controller to decrease
the condensing pressure according to outdoor temperature
and thereby reduce energy consumption by around 2% for each
degree the temperature can be decreased.
- the outdoor temperature measured with Sc3 sensor
- The minimum temperature dierence between the air
temperature and the condensing temperature at 0% compressor
capacity.
- the condenser’s dimensioned temperature dierence between
the air temperature and the condensing temperature at 100%
compressor capacity (Dim tmK)
- how large a part of the compressor capacity has been cut in.
The minimum temperature dierence (min tm) at low load should
be set at approximately 6 K as this will eliminate the risk that all
fans will be running when no compressors are running.
Set the dimensioned dierence (dim tm) at max. load (e.g. 15 K).
The controller will now contribute with a value to the reference
which depends on how large a part of the compressor capacity
has been cut in.
P-regulation
With P regulation the reference will be three degrees above
the measured outdoor temperature. The proportional band
Xp indicates the deviation with 100% condenser capacity.
Forced operation of condenser capacity
Forced operation of the capacity can be arranged where the normal regulation is ignored.
The safety functions are cancelled during forced operation.
Forced operation via setting
The regulation is set to Manual.
The capacity is set in percent of the regulated capacity.
Forced operation of relays
If the forced operation is carried out with the switches at the
front of an extension module, the safety function will register
any exceeding of values and transmit alarms, if required, but the
controller cannot cut the relays in or out in this situation.
Limitation of the reference
To safeguard yourself against a too high or too low regulation
reference, a limitation of the reference must be set.
Cut-ins and cutouts are carried out sequentially. The last cut-in
unit will be cut out rst.
Speed regulation
When an analog output is used the fans can be speed regulated,
e.g. with a frequency converter type VLT.
when the capacity requirement corresponds to the set starting
speed.
The controller cuts in several fans step by step as the capacity
requirement grows and then adapts the speed to the new
situation.
The controller cuts out fans when the capacity requirement
becomes lower than the set minimum speed.
In the conguration of the controller’s outputs it will be the output “FanA1”” that will start and
stop the frequency converter.
Joint speed regulation
The analog output voltage is connected to the speed regulation.
All fans will now be regulated from 0 to max. capacity. If an ON/
OFF signal is required for the frequency converter, so that the fans
can be stopped completely, relay output "Fan 1" is used.
Start
Min.
The controller starts the frequency converter when the capacity
requirement corresponds to the set starting speed. The controller
stops the frequency converter when the capacity requirement
becomes lower than the set minimum speed.
Speed regulation + step regulation
Condenser couplings
Coupling of condenser steps
There are no time delays in connection with cutin and cutout
of condenser steps beyond the time delay inherent in the PI/Pregulation.
Timer
The operating time of a fan motor is registered continuously. You
can read out:
- operating time for the previous 24-hour period
- total operating time since the timer was last set to zero-set.
Coupling counter
The number of couplings is registered continuously. Here the
number of starts can be read out:
- number during the previous 24-hour period
- total number since the counter was last set to zero-set.
Motion af ventilatorer
De sidste ventilatorer bliver næppe aktiveret i vinterhalvåret.
For at sikre, at ventilatorerne bliver motioneret, vil der for hver 24
timer, blive kontrolleret om alle relæer har været i drift.
De relæer, der ikke har været i drift, vil nu blive aktiveret i et halvt
minut, men dog med en pause på en time imellem de enkelte
relæer.
En hastighedstyring køres op til "Start speed".
Start
Min.
The controller starts the frequency converter and the rst fan
The controller can receive signals on the status on a common
safety circuit.
The signal is obtained directly from the safety circuit and
connected to a “DI7” input.
If the safety circuit is cut out the controller will give alarm.
Liquid level alarm
An input can be used for monitoring an external signal.
If the signal is interrupted, an alarm will be triggered.
A time delay can be set for the alarm.
Room temperature alarm
The function may be used for alarm monitoring of the temperature
Alarm limits can be set for high temperature.
Time delays can be set for the alarm,
VSD safety alarm
An input can be used for monitoring frequency converter.
If the signal is interrupted, an alarm will be triggered.
A time delay can be set for the alarm.
The main switch is used to stop and start the controlling function.
The switch-over has 2 positions:
- Normal controlling state (Setting = ON)
- Control stopped. (Setting = OFF)
In addition, there is also a input which is used as an external main
switch.
If the switch-over or the external main switch is set at OFF, all the
control’s functions are inactive and an alarm is generated to draw
attention to this – all other alarms cease.
Refrigerant
Before regulation can be commenced, the refrigerant must be
dened.
You can select one of the following refrigerants:
1 R12 11 R11421 R407A31 R422A
2 R22 12 R142b22 R407B32 R413A
3 R134a 13 Brugerdeneret23 R410A33 R422D
4 R502 14 R3224 R17034 R427A
5 R717 15 R22725 R29035 R438A
6 R13 16 R401A26 R60036 R513A
7 R13b1 17 R50727 R600a37 R407F
8 R23 18 R402A28 R744
9 R50019 R404A29 R1270
10 R50320 R407C30 R417A
The refrigerant can only be changed if the “Main switch” is set at
“stopped control” and the conguration lock is open.
Warning: Incorrect selection of refrigerant can cause damage to
the compressor.
Sensor failure
If lack of signal from one of the connected temperature sensors or
pressure transmitters is registered an alarm will be given.
• When there is a P0 error regulation will continue with 50% cut-in
capacity during day operation and 25% cut-in capacity during
night operation – but minimum one step.
• When there is a Pc error 100% condenser capacity will be cut in,
but the compressor regulation will remain normal.
• When there is an error on the Sd sensor the safety monitoring of
the discharge gas temperature will be discontinued.
• When there is an error on the Ss sensor the monitoring of the
superheat on the suction line will be discontinued.
• When there is an error on the outdoor temperature sensor
Sc3 regulation with variable condensing pressure reference
cannot be carried out. Instead you use the PC ref. min. value as
reference.
Note: An incorrect sensor must be in order for 10 minutes before
the sensor alarm deactivates.
Sensor calibration:
The input signal from all connected sensors can be corrected. A
correction will only be necessary if the sensor cable is long and
has a small cross-sectional area. All displays and functions will
reect the corrected value.
Clock function
The controller contains a clock function.
The clock function is used only to change between day/night.
The year, month, date, hour and minutes must be set.
Note: If the controller is not equipped with a RTC module
(AK-OB 101A) the clock must be reset after each mains voltage
outage.
If the controller is connected to an installation with an AKAgateway or an AK system manager, this will automatically reset
the clock function.
Alarms and messages
In connection with the controller’s functions, there are a number
of alarms and messages that become visible in cases of fault or
erroneous operation.
Alarm history (service tool only)
The controller contains an alarm history (log) that contains all
active alarms as well as the last 40 historical alarms. In the alarm
history you can see when the alarm began and when it stopped.
In addition, one can see the priority of each alarm as well as when
the alarm has been acknowledged and by which user.
Alarm priority:
Dierentiation is made between important and not-so-important
information. The importance – or priority – is set for some alarms
whilst others can be changed voluntarily (this change can only be
done with attachment of AK-ST service tool or AKM software).
The setting decides which sorting / action must be carried out
when an alarm is sounded.
• “High” is the most important
• “Log only” is the lowest
• “Interrupted” results in no action
Alarm relay
There is an alarm output on the controller as a local alarm
indication.
Alarm acknowledgement
If the controller is connected to a network with an AKA gateway or
an AK system manager as alarm receiver, these will automatically
acknowledge the alarms that are sent to them.
If the controller is used as stand alone without a network connection, the controller can acknowledge the alarms automatically.
Then the alarms will automatically go o, when the cause of the
alarm dissappears.
(Set "Auto act. alarm" to "Enabled" / P40 to 0.)
Alarm LED
The alarm LED on the front of the controller indicates the controller’s alarm status.
Blinking: There is an active alarm or an unacknowledged alarm.
Fixed light: There is an active alarm that has been acknowledged.
Switched o: There are no active alarms and no unacknowledged
alarms.
Forced operation via network
The controller contains settings that can be operated from the
gateway’s forced operation function via data communication.
When the forced operation function asks about one change, all
the connected controllers on this network will be set simultaneously.
There are the following options:
- Change to night operation
- Forced closure of injection valves (Injection ON)
- Optimising of suction pressure (Po)
Operating AKM / Service tool / Display
The setup of the controller itself can be carried out via AK-ST 500
service tool software, AKM-software, graphic display AK-MMI or
with display EKA 164.
Note: AKM system software does not provide access to all conguration settings of the controller. The settings/read-outs that may
be made appear in the AKM menu operation (see also Literature
overview).
Authorisation / Passwords
The controller can be operated with System software type AKM
with service tool software AK-ST 500 and display.
All methods of operation provide the possibility for access to
several levels according to the user’s insight into the various functions.
IO Status and manual
The function is used in connection with installation, servicing and
fault-nding on the equipment.
With the help of the function, the connected outputs are controlled.
Measurements
The status of all inlets and outlets can be read and controlled here.
Forced operation (Service tool only)
One can carry out an override of all outlets here to control
whether these are correctly attached.
Note: There is no monitoring when the outlets are overridden.
Logging/registration of parameters
As a tool for documentation and fault-nding, the controller provides the possibility of logging of parameter data in the internal
memory.
Via AK-ST 500 service tool software one can:
a) Select up to 10 parameter values the controller will continu-
ously register
b) State how often they must be registered
The controller has a limited memory but as a rule of thumb, the 10
parameters can be saved, which are registered every 10 minutes
for 2 days.
System software type AKM:
The various users are dened here with initials and key word.
Access is then opened to exactly the functions that the user may
operate.
The operation is described in the AKM manual.
Service tool software AK-ST 500:
The operation is described in tters on site guide.
When a user is created, the following must be stated:
a) State a user name
b) State a password
c) Select user level
d) Select units – either US (e.g. °F and PSI) or Danfoss SI (°C and
Bar)
e) Select language
Access is given to four user levels.
1) DFLT – Default user – Access without use of password
See daily settings and read-outs.
2) Daily – Daily user
Set selected functions and carry out acknowledgement of alarms.
3) SERV – Service user
All settings in the menu system except for creation of new users
4) SUPV – Supervisor user
All settings including the creation of new users.
Display
An access code can be dened in one of the menus. You can access all function when the code has been entered.
Via AK-ST 500 one can subsequently read the historical values in
the form of graph presentations.
Display of suction pressure and condensing pressure
Light-emitting diodes on the controller
Internal communication
between the modules:
Quick ash = error
Constantly On = error
One or two separate displays can be connected to the controller.
Connection is accomplished by means of wires with plug
connections. The display may be placed in a control box front, for
example. When a display with control buttons is chosen, a simple
operation via a menu system can be performed in addition to the
display of suction pressure and condensing pressure. See earlier in
the manual.
When a display is connected, it will show the value for what is indicated in "Read out".
If you want to see one of the values for what is given under "function" you should use the buttons in the following way:
1. Press on the upper button until a parameter is shown
2. Press on the upper or lower button and nd the parameter you
want to read
3. Press on the middle button until the value of the parameter is
displayed.
After a short time, the display will return automatically to the
"Read out display".
If LED indication of compressor operation, fan operation and various functions is required, display type EKA 166 can be tted.
Status of output 1-8
■ Power
■ Comm
■ DO1 ■ Status
■ DO2 ■ Service Tool
■ DO3 ■ LON
■ DO4
■ DO5 ■ Alarm
■ DO6
■ DO7
■ DO8 ■ Service Pin
Slow ash = OK
Quick ash = answer from gateway
remains on for 10 mins after network
registration
Constantly ON = error
Constantly OFF = error
External communication
Flash = active alarm/not cancelled
Constant ON = Active alarm/cancelled
Network installation
(The LED for "Oil" and "Heat" is not active on this controller.)
Graphic display AK-MMI
With the display is access to most of the controller functions.
Appendix A – Compressor combinations and coupling patterns
In this section, there is a more detailed description of the compressor combinations and the associated coupling patterns.
Sequential operation is omitted from the examples since the compressors are only connected in accordance with their compressor
number (First In - Last Out principle) and only speed-regulated
compressors are used to ll capacity gaps.
Compressor application = single step
The capacity distributor is capable of managing up to 6 one-step
compressors according to the following coupling patterns:
• Sequential
• Cyclical
• Best t
Cyclical operation - example
Here, all compressors are of the same size and the compressors
are cut in and cut-out in accordance with the First-In-First-Out
(FIFO) principle, in order to equalise operating hours between the
compressors.
- There is operating time equalizing between all compressors
- The compressor with the fewest running hours starts rst
- The compressor with the most running hours stops rst.
Best t - example
Here are at least two compressors are of dierent sizes. The capacity distributor will cut in and cut-out the compressors to produce
the best possible capacity t (the least possible capacity jump).
Compressor application = 1 x Speed + single step
The controller is capable of controlling one speed-regulated
compressor combined with one-step compressors of the same or
dierent sizes.
Preconditions for using this compressor application are:
• A speed-regulated compressor that can be of a dierent size
than the following one-step compressors
• Up to 5 one-step compressors of the same or dierent capacity
(depending on coupling pattern)
This compressor combination can be handled in accordance with
the following coupling patterns:
• Sequential
• Cyclical
• Best t
Handling the speed-regulated compressor.
For more information on the general handling of the speed-regulated compressor, refer to section "Power pack types".
Cyclical operation - example
Here, the one-step compressors are of the same size.
The speed-regulated compressor is always the rst to start and the
last to stop.
One-step compressors should be cut in and cut out in accordance
with the First-In-First-out principle in order to equalise operating
hours.
The speed-regulated compressor is used to ll the capacity gaps
between the one-step compressors.
Example:
- There is operating time equalizing between the compressors 1
and 2 (same size in example).
- There is operating time equalizing between the compressors 3
and 4 (same size in example).
- The speed-regulated compressor starts when the desired
capacity equals the start speed
- The following one-step compressor with the smallest number
of operating hours cut in when the speed-regulated compressor is running at full speed (90 Hz)
-When a one-step compressor cuts in, the speed-regulated com-
pressor reduces speed (40 Hz) equivalent to the capacity of the
one-step compressor.
Decreasing capacity:
- The following one-step compressors with the most operating
hours should be cut out when the speed-regulated compressor
reaches minimum speed (30 Hz)
- When a one-step compressor is cut out, the speed- regulated
compressor’s speed increases (80 Hz), equivalent to the capacity of the one-step compressor
- The speed-regulated compressor is the last compressor to be
cut out when the preconditions for this are fullled.
Best t - example:
Here, at least two of the one-step compressors are of dierent
sizes.
The speed-regulated compressor is always the rst to start and
last to stop.
The capacity distributor cuts in and cuts out the one-step compressors in order to achieve the best possible capacity t (least
possible capacity jump)
The speed-regulated compressor is used to ll out the capacity
gaps between the one-step compressors.
Example:
Increasing capacity:
- The speed-regulated compressor starts when the desired
capacity matches the start speed
- The smallest one-step compressor is cut in when the speedregulated compressor runs at full-speed (90 Hz).
- When the speed-regulated compressor again reaches max.
speed (90 Hz), the smallest one-step compressor is cut out (C2)
and the big one-step compressor (C3) is cut in.
- When the speed-regulated compressor again reaches max
speed (90 Hz), the smallest one-step compressor (C2) is cut in
again.
- When the one-step compressor is cut in, the speed is reduced
on the speed-regulated compressor (40 Hz) equivalent to the
capacity of the cut in capacity
Decreasing capacity:
- The small one-step compressor is cut out when the speed-regulated compressor has reached minimum speed (30 Hz)
- When the speed-regulated compressor again reaches minimum
speed (30 Hz), the smallest one-step compressor (C2) is cut out
and the big one-step compressor (C3) is cut in.
- When the speed-regulated compressor again reaches min.
speed (30 Hz), the large one-step compressor (C3) is cut out
and the small one-step compressor (C2) is cut in again.
- When the speed-regulated compressor again reaches min.
speed (30 Hz), the small one-step compressor (C2) is cut in.
- The speed-regulated compressor is the last compressor to be
cut out when the requirements for this are fullled.
- When the one-step compressor’s capacity is cut out, the speedregulated compressor increases speed (80 Hz) equivalent to
the cut out capacity.
Accidental damage, poor installation, or site conditions, can give rise
to malfunctions of the control system, and ultimately lead to a plant
breakdown.
Every possible safeguard is incorporated into our products to prevent
this. However, a wrong installation, for example, could still present
problems. Electronic controls are no substitute for normal, good
engineering practice.
Danfoss wil not be responsible for any goods, or plant components,
damaged as a result of the above defects. It is the installer's responsibility to check the installation thoroughly, and to t the necessary
safety devices.
Special reference is made to the necessity of signals to the controller
when the compressor is stopped and to the need of liquid receivers
before the compressors.
Your local Danfoss agent will be pleased to assist with further advice,
etc.
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alternations can be made without subsequential changes being necessary in specications already agreed.
All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.