Danfoss AK-PC 651 Installation guide [de]

Danfoss AK-PC 651 Installation guide

Instructions

AK-PC 651

Identification

IP 20

-20 - 60°C (0 - 140°F)

RH max. 90% non condensing

 

080G0312

External display

1,5 m: 080G0075

 

3,0 m: 080G0076

Termination!

H-R

MMIGRS2: 080G0294

Termination!

H-R

Principle

RI8RD4ML    2015-04

ENGLISH

Connection, lower level

 

 

 

 

 

 

 

 

 

Warning

 

 

 

 

 

 

 

 

 

 

The supply voltage of AI may not share the

 

 

 

 

 

 

 

 

 

 

signal with other controllers.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DO

DO1

DO2

DO3

DO4

DO5

 

DO6

DO7

DO8

DO9

DO10

 

DO11

 

DO12

DO13

DO14

DO15

Σ 1-15

I Max.

6 A

6 A

6 A

6 A

0.5 A

 

0.5 A

6 A

6 A

6 A

6 A

 

6 A

 

6 A

6 A

7 A

7 A

92 A

 

(4)

(4)

(4)

(4)

min. 50 mA

 

min. 50 mA

(4)

(4)

(4)

(4)

 

(4)

 

(4)

(4)

(3,5)

(3,5)

 

 

 

 

 

 

Ioff < 1,5 mA

 

Ioff < 1,5 mA

 

 

 

 

 

 

 

 

 

 

 

 

U

 

 

 

 

All 24 V or

 

 

 

 

 

All 24 V or

 

 

All 24 V or

 

 

 

 

 

 

all 230 V a.c.

 

 

 

 

all 230 V a.c.

 

all 230 V a.c.

 

DO - Digital outputs, 15 pcs. DO1 - DO15

 

 

Supply Voltage

DO5 and DO6 are solid state relays.

 

 

230 V a.c.

The relays are de-rated to the specified values.

 

 

AO - Analogue output, 4 pcs. AO1 - AO4

 

 

 

 

 

 

 

 

 

 

AI - Analogue inputs, 6 pcs. AI1 - AI6

 

 

Must be used when using a frequency converter or EC motors.

 

 

Connect 24 V on N and L. Avoid earth fault current. Use

Temperature sensor

 

 

 

 

 

 

double-insulated transformer. The secondary side must

• Pt 1000 ohm, AKS 11 or AKS 21.

 

 

not be earthed.

• NTC 86K ohm @ 25°C, from digital scroll.

 

 

Obtain 0-10 volts from terminals N and AO1, respectively N

Pressure transmitters

 

 

 

 

 

 

and AO2. PAY ATTENTION TO THE POLARITY of N.

• Current: 0-20 mA / 4-20 mA, AKS 33 (supply = 12 V)

AI - Analogue inputs, 4 pcs. AI7 - AI10

 

 

Modbus

 

 

It is important that the installation of the data communication

Pressure transmitters

 

 

 

 

 

 

cable be done correctly. Cf. separate literature No. RC8AC.

• Ratiometric: 10-90% of supply, AKS 32R

 

 

Remember termination at the bus termination.

• Signal: 1-5 V, AKS 32

 

 

 

 

 

 

Termination

Factory settings: AI7=Po, AI8=Pc

 

 

Temperature sensor

 

 

 

 

 

 

(Only if a remote display i connected)

See above

 

 

 

 

 

 

Insert a jumper between the two connections on the left

 

 

 

 

 

 

 

 

 

 

(R120-CANH).

 

 

 

 

 

 

 

 

 

 

AKS 32R

AKS 32

AKS 33

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

Instructions  RI8RD4ML  ©  Danfoss  2015-04

  AK-PC 651

Connection, upper level

DI - High or low voltage Digital Inputs, 4 pcs. DI1 - DI4

Terminals = DI1H, DI1, DI common ...

230 V signal: Connect to DI_H

24 V signal: Connect to DI_

The connection may be a shut-down or interruption function. Select what is to be activated during configuration.

DI - Low voltage Digital Inputs, 14 pcs. DI5 - DI18

All 24 V signal.

AK-PC 651

Instructions  RI8RD4ML  ©  Danfoss  2015-04

3

Loading...
+ 4 hidden pages