Instructions
AK-PC 651
Identification
IP 20
-20 - 60°C (0 - 140°F)
RH max. 90% non condensing
|
080G0312 |
External display |
1,5 m: 080G0075 |
|
3,0 m: 080G0076 |
Termination!
H-R
MMIGRS2: 080G0294
Termination!
H-R
Principle
RI8RD4ML 2015-04
ENGLISH
Connection, lower level |
|
|
|
|
|
|
|
|
|
Warning |
||||
|
|
|
|
|
|
|
|
|
|
The supply voltage of AI may not share the |
||||
|
|
|
|
|
|
|
|
|
|
signal with other controllers. |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
DO |
DO1 |
DO2 |
DO3 |
DO4 |
DO5 |
|
DO6 |
DO7 |
DO8 |
DO9 |
DO10 |
|
DO11 |
|
DO12 |
DO13 |
DO14 |
DO15 |
Σ 1-15 |
I Max. |
6 A |
6 A |
6 A |
6 A |
0.5 A |
|
0.5 A |
6 A |
6 A |
6 A |
6 A |
|
6 A |
|
6 A |
6 A |
7 A |
7 A |
92 A |
|
(4) |
(4) |
(4) |
(4) |
min. 50 mA |
|
min. 50 mA |
(4) |
(4) |
(4) |
(4) |
|
(4) |
|
(4) |
(4) |
(3,5) |
(3,5) |
|
|
|
|
|
|
Ioff < 1,5 mA |
|
Ioff < 1,5 mA |
|
|
|
|
|
|
|
|
|
|
|
|
U |
|
|
|
|
All 24 V or |
|
|
|
|
|
All 24 V or |
|
|
All 24 V or |
|
||||
|
|
|
|
|
all 230 V a.c. |
|
|
|
|
all 230 V a.c. |
|
all 230 V a.c. |
|
DO - Digital outputs, 15 pcs. DO1 - DO15 |
|
|
Supply Voltage |
|||||||
DO5 and DO6 are solid state relays. |
|
|
230 V a.c. |
|||||||
The relays are de-rated to the specified values. |
|
|
AO - Analogue output, 4 pcs. AO1 - AO4 |
|||||||
|
|
|
|
|
|
|
|
|
|
|
AI - Analogue inputs, 6 pcs. AI1 - AI6 |
|
|
Must be used when using a frequency converter or EC motors. |
|||||||
|
|
Connect 24 V on N and L. Avoid earth fault current. Use |
||||||||
Temperature sensor |
|
|
|
|
|
|
double-insulated transformer. The secondary side must |
|||
• Pt 1000 ohm, AKS 11 or AKS 21. |
|
|
not be earthed. |
|||||||
• NTC 86K ohm @ 25°C, from digital scroll. |
|
|
Obtain 0-10 volts from terminals N and AO1, respectively N |
|||||||
Pressure transmitters |
|
|
|
|
|
|
and AO2. PAY ATTENTION TO THE POLARITY of N. |
|||
• Current: 0-20 mA / 4-20 mA, AKS 33 (supply = 12 V) |
||||||||||
AI - Analogue inputs, 4 pcs. AI7 - AI10 |
|
|
Modbus |
|||||||
|
|
It is important that the installation of the data communication |
||||||||
Pressure transmitters |
|
|
|
|
|
|
cable be done correctly. Cf. separate literature No. RC8AC. |
|||
• Ratiometric: 10-90% of supply, AKS 32R |
|
|
Remember termination at the bus termination. |
|||||||
• Signal: 1-5 V, AKS 32 |
|
|
|
|
|
|
Termination |
|||
Factory settings: AI7=Po, AI8=Pc |
|
|
||||||||
Temperature sensor |
|
|
|
|
|
|
(Only if a remote display i connected) |
|||
See above |
|
|
|
|
|
|
Insert a jumper between the two connections on the left |
|||
|
|
|
|
|
|
|
|
|
|
(R120-CANH). |
|
|
|
|
|
|
|
|
|
|
|
AKS 32R |
AKS 32 |
AKS 33 |
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2 |
Instructions RI8RD4ML © Danfoss 2015-04 |
AK-PC 651 |
Connection, upper level
DI - High or low voltage Digital Inputs, 4 pcs. DI1 - DI4
Terminals = DI1H, DI1, DI common ...
230 V signal: Connect to DI_H
24 V signal: Connect to DI_
The connection may be a shut-down or interruption function. Select what is to be activated during configuration.
DI - Low voltage Digital Inputs, 14 pcs. DI5 - DI18
All 24 V signal.
AK-PC 651 |
Instructions RI8RD4ML © Danfoss 2015-04 |
3 |