Terminals:
1-2 Supply voltage 24 V a.c.
4-5 Relay outputs for digital scroll compressor
6-7 Solid state relay for digital scroll compressor's unloader
8- 19 Relay outputs for either compressors or fan motors
22-24 Alarm relay *
There is connection between 22 and 24 in alarm situa tions
and when the controller is dead
27-28 4 V signal to start / stop of regulation
27-29 24 V signal from the safety circuit Digital scroll
30 No function
27-31 24 V signal from the safety circuit DO 3
27-32 24 V signal from the safety circuit DO 4
27-33 24 V signal from the safety circuit DO 5
27-34 24 V signal from the safety circuit DO 6
27-35 24 V signal from the safety circuit DO 7
27-36 24 V signal from the safety circuit DO 8
57-59 Suction pressure. Voltage signal from AKS 32R **
60-62 Condenser pressure. Voltage signal from AKS 32R **
P0/Pc: AKS 32R:
1 = Black = +
2 = Blue = 3 = Brown = s
(R=1680 ohm)
All inputs are low-voltage.
Relay output 1-8 are low voltage.
Relay output 9 and 10 may be
high voltage.
Data communication
Application dependent connections
20-21 AKD start/stop *
The relay cutin when the frequency converter have to
start.
37-38 Voltage signal to external condenser control
(see settings page 12)
39-41 Possibility of connecting an external display type EKA 163
or display of Pc
42-44 Possibility of connecting an external display type EKA 163
for display of P0, or EKA 165 for operation and display of
P0
45-46 DI1 - Contact function for alarm signal
45-47 DI2 - Contact function for alarm signal
48-49 DI3 - Contact function for alarm signal
48-50 DI4 - Contact function for displacement of the suction
pressure reference or for alarm signal.
51-52 DI5 - Contact function for displacement of the condenser
pressure reference or for alarm signal.
51-53 Separate sensor Saux. Discharge gas temperature.
Sensor signal from Pt 1000 (AKS 21) or Copeland-NTC and
with supplied resistor mounted.
54-55 Outdoor ambient temperature (Sc3). Sensor signal from Pt
1000, AKS 11 or AKS 21 (mounted if r33 = 2 or 4).
54-56 Air temperature at condenser outlet. Sensor signal from a
Pt 1000, AKS 11 or AKS 21.
Data communication
25-26 Mount only, if a data communication module has been
fitted.
For ethernet communication the plug connection RJ45
must be used. (LON FTT10 can also be connected in this
way.
It is important that the installation of the data communication cable be done correctly. Cf. separate literature No.
RC8AC.
*)
Relays DO9 and DO10 may in special cases be reconfigurated so that they can be
used as fan relays.
**)
If the controller has to control only the compressor or the fans, respectively Pc and P0
sensor can be dispensed
Compressor configuration when o61 =1 or 2 (This is where you can choose between the options
shown.)
Setting "c16" will define the configuration.
Setting "c08" will define coupling mode.
Compressor connections
Coupling
mode
Capacity step
All capacity steps are presumed to be identi-
cal.
Relay no.
Set
"c16"
to
Set
"c08"
to
Coupling mode
Coupling mode 1 = sequential operation.
Compressor 1 will be the first to start. Then
compressor 2 and so on.
Coupling mode 2 = cyclic operation.
Compressor 1 will always be in operation
when cooling is required. After this the compressor with the lowest number of operating
hours will be started.
The capacity from the digital scroll compressor
The capacity is divided into period times as "PWM per". 100% capacity is delivered when cooling takes place for the whole period.
An off time is required by the by-pass valve within the period and an on time is also permitted. There is "no cooling" when the
valve is on.
The controller itself calculates the capacity needed and will then vary it according to the cut-in time of the by-pass valve.
A limit is introduced if low capacity is needed so that the cooling does not go below 10%. This is because the compressor can
cool itself. This value can be increased if necessary.
The capacity can similarly be limited so that the compressor cannot deliver 100% capacity. It is not normally necessary to limit
this max. capacity.
When the compressor relays have been established the turn
comes to the fan relays.
The first vacant relay (DO3-DO8) will become the first fan relay.
It will be followed by the subsequent relays. If more relays are
required than the vacant DO relays, a relay module can be
connected to the analog output. The function is, as follows:
If there are up to four external fans on an EKC 331:
If there are more than four external fans on two EKC 331 units:
1.
2.
Output signal from AK-PC 560
In EKC 331 the voltage range must be set to 0-5 V (“o10” = 6).
In EKC 331 the number of steps must be set to 4 (“o19” = 4) (also when
fewer fans are connected).
Connection
Alternating start-up of fans (only if c29 is 11 to 18)
The fans can be defined to start alternately when they have all been
stopped.
The first time regulation is started, fan 1 will be started first – the regulation
determines whether additional fans will be started.
After the next time all fans are stopped, fan 2 will be the first to be started,
and so on.
Fan 1 will again be the first fan to be started when the rotation has been
through the total number of fans.
If there is more than one fan on an EKC 331, it will not be possible to start
the other fans first. Here, the fan with the lowest voltage step will always be
the one which is started first.
If the entire condenser capacity is to be controlled by a
frequency converter, AK-PC 560 must send an analog signal
about the required capacity (“c29” = 9).
The signal varies from 0 to 10 V. Signal and capacity have the
following context.
Output signal from AK-PC 560
In the first EKC 331, set 0-5 V (“o10” = 6).
In the second EKC 331, set 5-10 V (“o10” = 7).
In both EKC’s the number of steps must be set to 4 (“o19” = 4) (also when
fewer fans are connected to the second EKC).
If the controller is extended with data communication, the operation can be performed from a system unit.
The importance of the alarms that are sent can be defined with
the setting: 1 (High), 2 (Medium), 3 (Low) or 0 (No alarm).
Operation via external display
The values will be shown with three digits, and with a setting you
can determine whether the pressures are to be shown in SI units
(°C / bar) or US units (°F / psig.).
There are three options for the display.
P0 is over the neutral zone
P0 is under the neutral zone
1: Relay digital scroll
2: Relay comp. 2
3: Relay comp. 3
.
.
.
10: Capacity form the
digital scroll
EKA 165
EKA 165
To operate the controller and view the evaporation pressure.
If the lowermost key is pressed, the condensation pressure will
be shown briefly in the display. (If regulation is based only on the
condensation pressure, the display will always show Pc).
During normal operation the light-emitting diodes in the display
will indicate where regulation is taking place.
Second highest : Over neutral zone
"None" : Neutral zone
Second lowest : Under neutral zone
The other LEDs on the display will show the functions that are
active:
• Relays for compressors
• The capacity can be read from the digital scroll compressor
• Relays for fans
• Input signals for the digital inputs
• The optimization LED will light up when the reference is 2 K or
more over the set point.
EKA 163
EKA 164
The buttons on the display
When you want to change a setting, the upper and the lower
buttons will give you a higher or lower value depending on the
button you are pushing. But before you change the value, you
must have access to the menu. You obtain this by pushing the
upper button for a couple of seconds - you will then enter the
column with parameter codes. Find the parameter code you want
to change and push the middle button. When you have changed
the value, save the new value by once more pushing the middle
button.
EKA 163
If the condensation pressure is to be shown constantly, a display
without operating keys can be connected.
EKA 164
To operate the controller and view the evaporation pressure.
If the lowermost key is pressed, the condensation pressure will be
shown briefly in the display.
Like the EKA 165, the LEDs in the display will show where the
regulation is located.
Or short:
1. Push the upper button (long push) until a parameter is shown
2. Push one of the buttons and find the parameter you want to
change
3. Push the middle button until the setting value is shown
4. Push one of the buttons and select the new value
5. Push the middle button again to conclude the setting
( A brief pushing will show the active alarm codes.)
1. o61 must be set as the first parameter. This parameter determines which of the four operating interfaces (application mode) are
activated. This must be set via the display keys. It cannot be set via data communication. (Active functions are shown below in shaded
fields.)
2. Quick- start
To get the system up and running quickly so that cooling can be commenced, start it by setting the following parameters (these parameters can only be set when the regulation is stopped, r12=0): r23, r28, c08, c16, c29, o06, o30, o75, o76 and finally r12=1.
3. Once the regulation is under way, you can go through the other parameters and adjust them in situ.
SW: 1.0x
Function
Normal display
Shows P0 in EKA 165 (display with buttons)-°CP°C / bar
Shows Pc in EKA 163-°CP°C / bar
P0 reference
Neutral zoner010.1°C / 0.1 bar20°C /5.0 bar4.0°C / 0.4 bar
Correction of signal from P0 sensorr04-50°C /-5.0 bar50°C / 5.0 bar0.0
Select view; SI or US. 0=SI (bar /°C), 1=US (Psig /°F)
Start/Stop of regulationr12OFFONOFF
Reference offset for P0 (see also r27)r13-50°C / -5.0 bar50°C / 5.0 bar0.0
Set regulation set point for P0r23-99°C / -1 bar30°C / 60.0 bar0.0°C / 3.5 bar
Shows total P0 reference
( r23 + various displacements)
Limitation: P0 reference max. value
(also applies to regulation with reference displacement)
Limitation: P0 reference min. value
(also applies to regulation with reference displacement)
Displacement of P0 (ON=active “r13”)r27OFFONOFF
Pc reference
Set regulation set point for Pcr28-25°C / 0.0 bar75°C / 110.0 bar 35°C / 15.0 bar
Shows total Pc referencer29°C / bar
Limitation: Pc reference max. valuer30-99.9°C / -0.0 bar 99.9°C/ 130.0bar 55.0°C / 60.0 bar
Limitation: Pc reference min. valuer31-99.9°C / 0.0 bar 99.9°C / 60.0 bar -99.9°C / 0.0 bar
Correction of signal from Pc sensorr32-50°C / -5.0 bar50°C / 5.0 bar0.0
Pc reference variation. 1 and 2 are PI-regulation
1: Fixed reference. “r28” is used
2: Variable reference. Outdoor temperature (Sc3) included in the reference
3: As 1, but with P-regulation (Xp-band)
4: As 2, but with P-regulation (Xp-band)
Reference offset for Pcr34-50°C / -5.0 bar50°C / 5.0 bar0.0
The mean temperature difference across the condenser at maximum
load (dim tm K)
The mean temperature difference across the condenser at the lowest
relevant compressor capacity (min tm K)
Capacity
Min. ON time for relaysc010 min30 min.0
Min. time period between cutins of same relayc072 min.60 min2
Definition of compressor connections.
See options on page 3.
Definition of condenser:
1-8: Total number of fan relays or voltage step on the voltage output
9: Only via analog output and start of frequency converter
10: Not used
11- 18: Total number of fan relays which are to be connected with alter-
nating start-up.
Cut in compressor capacity with manual control. See also “c32”c310%100%0
Manual control of compressor capacity (when ON, the value in “c31” will
be used)
Parameter
r05010
r24°C / bar
r25-99°C / -1.0 bar30°C / 60.0 bar30.0°C / 40.0 bar
r26-99°C / -1.0 bar30°C / 40.0 bar-99.9°C / -1.0 bar
The Product contains electrical components
And may not be disposed together with domestic waste.
Equipment must be separate collected with Electrical and Electronic waste. According to Local and currently valid legislation.
FC-SPMC
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.