Identication
Instructions
AK-PC 551
1.5 m: 080G0075
3.0 m: 080G0076
080G0281 = 230 V a.c. 20 VA
080G0283 = 24 V a.c. / d.c. 17 VA
Kit
080G0282 = 080G0321 + 080G0294 + 080G0075
(230 V)
080G0288 = 080G0326 + 080G0294 + 080G0075
(24 V)
Principle
080G0321 = 230 V a.c. 20 VA
080G0326 = 24 V a.c. / d.c. 17 VA
MMIGRS2: 080G0294
1,5 m
IP 20
-20 - 60°C
(0 - 140°F)
RH max. 90% non condensing
RI8PZ4ML 2015-06
ENGLISH
Connection, lower level
DO DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 Σ 1-8
I Max. 10 A
U All 24 V or all 230 V a.c.
(3,5)
10 A
(3,5)
6 A
(4)
6 A
(4)
0.5 A
min. 50 mA
Io < 1.5 mA
0.5 A
min. 50 mA
Io < 1.5 mA
6 A
(4)
6 A
(4)
Connection, upper level
Separate
supply!
32 A
Warning
The supply voltage of AI may not share
the signal with other controllers.
Electric noise
Signal cables for sensors, DI inputs, data communication
and display must be kept separate from high voltage
(230 V) electric cables:
- Use separate cable trays
- Keep a distance between high voltage and signal cables
of at least 10 cm
- Cables longer than 3 m at the DI input should be avoided
Supply Voltage.
The supply voltage is either 24 V or 110-230 V. See the label on
the reverse side of the controller.
÷ = Plugs normally not used
However, if connecting to an external display, a jumper must
be inserted between the connections "H" and "R".
Modbus
It is important that the installation of the data communication
cable be done correctly. Cf. separate literature No. RC8AC.
Remember termination at the bus termination.
DO - Digital outputs, 8 pcs. DO1 - DO8
DO5 and DO6 are solid state relays.
The relays are de-rated to the specied values.
If an alarm relay is dened, it will be driven under normal operation and it will drop in the event of alarms and insucient
power to the controller.
AKS 32R
AKS 32
AKS 33
10-90% ratiometric
1-5 V
0-20mA
4-20mA
AO - Analogue output, 2 pcs. AO3 - AO4
Must be used when using a frequency converter or EC motors.
Connect 24 V on N and L (separate supply). Avoid earth fault
current. Use double-insulated transformer. The secondary side
must not be earthed.
Obtain 0-10 volts from terminals N and AO3, respectively N and
AO4. PAY ATTENTION TO THE POLARITY of N.
AI - Analogue inputs, 4 pcs. AI1 - AI4
Pressure transmitters
• Ratiometric: 10-90% of supply, AKS 32R
• Signal: 1-5 V, AKS 32
• Power: 0-20 mA / 4-20 mA, AKS 33 (supply = 12 V)
Temperature sensor
• Pt 1000 ohm, AKS 11 or AKS 21.
• NTC 86K ohm @ 25°C, from digital scroll.
Factory settings
AI1=PoA, AI2=PoB, AI3=Pc, AI4=Outdoor temperature SC3.
DI - Digital switch inputs, 8 pcs. DI1 - DI8
The connection may be a shut-down or interruption function.
Select what is to be activated during conguration.
÷ = Plugs normally not used
AI - Analogue inputs, 4 pcs. AI5 - AI8
Pressure transmitters
• Ratiometric: 10-90% of supply, AKS 32R
• Signal: 1-5 V, AKS 32
Temperature sensor
• Pt 1000 ohm, AKS 11 or AKS 21.
• NTC 86K ohm @ 25°C, from digital scroll
2 Instructions RI8PZ4ML © Danfoss 06/2015 AK-PC 551
External display Dimensions
Termination
Connect H-R
Important!
Termination
Connect H-R
The capacity from the
digital scroll compressor
Only DO5 or DO6
The capacity is divided into period times as "PWM period time". 100% capacity is delivered when cooling takes place for the whole
period.
An o time is required by the capacity control valve within the period and an on time is also permitted. There is "no cooling" when the
valve is on.
The controller itself calculates the capacity needed and will then vary it according to the cut-in time of the capacity control valve.
A limit is introduced if low capacity is needed so that the cooling does not go below 10%. This is because the compressor can cool
itself. This value can be increased if necessary.
Refrigeration / No refrigeration
Period time
Min. capacity
Copeland Stream compressor
The signal can also be used to control one stream compressor with one unloading valve (4 cylinders version).
The compressor capacity is distributed by up to 50% for one relay and the remaining 50-100% for the unloader. The unloader is connected to DO5 or DO6.
Bitzer CRII
The pulse signal can also be used to control one of the CRII with 2 unloaders (4 cylinders version).
Compressor capacity can be controlled from 10 to 100% depending on the pulsation of the unloaders. The unloader is connected to
DO5 or DO6.
Unloader 1
Unloader 2
Unloader 2 follows unloader 1
but is oset a ½ period.
AK-PC 551 Instructions RI8PZ4ML © Danfoss 06/2015 3
Português
Conexão, nível inferior
Separar
alimentação!
DO DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 Σ 1-8
I Max. 10 A
U Tudo 24 V ou tudo 230 V CA
Fonte de alimentação
(3,5)
10 A
(3,5)
6 A
(4)
6 A
(4)
0.5 A
min. 50 mA
Io < 1,5 mA
0.5 A
min. 50 mA
Io < 1,5 mA
6 A
(4)
6 A
32 A
(4)
AO - saída analógica, 2 pcs. AO3 - AO4
A tensão de alimentação é de 24 V ou de 110-230 V. Consulte a
etiqueta no reverso do controlador.
÷ = Plugues normalmente não utilizados
Entretanto, no caso de conectar com um display externo, um
jumper deverá ser inserido entre as duas conexões "H" e "R"
Modbus
É importante que a instalação do cabo de comunicação de
AI - entradas analógicas, 4 pcs. AI1 - AI4
dados seja feita corretamente.
Consulte a literatura separada nº RC8AC…
Lembre-se: terminação na terminação do barramento.
DO - saídas digitais, 8 pcs. DO1 - DO8
DO5 e DO6 são relés de estado sólido.
É feito derate dos relés para os valores especicados.
Caso um relé de alarme seja denido, ele será acionado
durante a operação normal e desarmará em caso de alarmes
e de tensão insuciente para o controlador.
Conexão, nível superior
Advertência
A tensão de alimentação do AI pode não compartilhar o sinal com outros controladores.
Ruído elétrico
Cabos de sinal para sensores, entradas DI, comunicação de
dados e display devem ser mantidos separados de outros
alta tensão (230 V) cabos elétricos:
- Use condutores de cabos separados
- Manter uma distância entre os cabos de alta tensão e de
sinal de pelo menos 10 cm
- Cabos de extensão superior a 3 m na entrada DI devem
ser evitados
Deverão ser utilizadas ao usar um conversor de frequência ou
motores EC.
24 V conectado no N e L (separar alimentação).. Evite corrente de falha do terra. Use um transformador com isolamento
duplo. O lado secundário não deve ser aterrado.
Obtenha 0-10 volts dos terminais N e AO3, respectivamente N
e AO4. PRESTE ATENÇÃO À POLARIDADE de N.
Transmissores de pressão
• Ratiometric: 10-90% do fornecimento, AKS 32R
• Sinal: 1-5 V, AKS 32
• fonte de alimentação: 0-20 mA / 4-20 mA, AKS 33 (fornecimento = 12 V)
Sensor de temperatura
• Pt 1000 ohm, AKS 11 ou AKS 21.
• NTC 86K ohm @ 25°C, a partir de digital scroll.
Congurações de fábrica
AI1=PoA, AI2=PoB, AI3=Pc, AI4=temperatura exterior SC3.
DI - Entradas digital chave, 8 pcs. DI1 - DI8
A conexão pode ser um desligamento ou função de interrupção.
Selecione o que deverá ser ativado durante a conguração.
AKS 32R
10-90% ratiometric
÷ = Plugues normalmente não utilizados
AI - entradas analógicas, 4 pcs. AI5 - AI8
Transmissores de pressão
AKS 32
1-5 V
• Ratiometric: 10-90% da alimentação, AKS 32R
• Sinal: 1-5 V, AKS 32
Sensor de temperatura
AKS 33
0-20mA
4-20mA
• Pt 1000 ohm, AKS 11 ou AKS 21.
• NTC 86K ohm @ 25°C, a partir de digital scroll.
4 Instructions RI8PZ4ML © Danfoss 06/2015 AK-PC 551