Design guide
Capacity controller
AK-PC 531B
ADAP-KOOL® Refrigeration control systems
Introduction
Application
The controller is used for capacity regulation of compressors and / or condensers in small refrigerating systems.
This controller can regulate up to ten compressors. The condenser capacity is step regulated via the remaining available digital outputs and external relay module or variable speed regulated via a frequency converter.
Advantages
•Patented neutral zone regulation
•Sequential or cyclic operation
•Possibility of suction pressure optimisation via the data communication
•Load shedding function
Regulation
Regulation is based on signals from one pressure transmitter for the compressor regulation and one pressure transmitter for the condenser regulation plus one temperature sensor for the air temperature before the condenser.
Functions
•Relays for capacity regulation
•Voltage output for capacity regulation
•Status inputs. An interrupted signal indicates that the safety circuit has been activated and the respective circuit stopped
•Contact inputs for indication of alarms
•Contact inputs for displacement of references or for indication of alarms
•Alarm relay
•External start/stop of regulation
•Possibility of data communication
Operation
All operation takes place either via data communication or via connection of a display type EKA 164. The display can be disconnected after the installation.
2 |
Manual RS8HG102 © Danfoss 11-2015 |
AK-PC 531B |
Function
Capacity regulation
The cut-in capacity is controlled by signals from the connected pressure transmitter and the set reference.
Outside the reference a neutral zone is set where the capacity will neither be cut in nor out.
Outside the neutral zone (in the hatched areas named +zone and -zone) the capacity will be cut in or out if the regulation registers a change of pressure “away” from the neutral zone.
Cut in and cut out will take place with the set time delays. If the pressure however “approaches” the neutral zone, the controller will make no changes of the cut-in capacity.
If regulation takes place outside the hatched area (named ++zone and --zone), changes of the cut-in capacity will occur somewhat faster than if it were in the hatched area.
Cut in of steps can be defined for either sequential or cyclic operation.
Sequential (first in - last out)
The relays are here cut in in sequence – first relay number 1, then 2, etc.
Cutout takes place in the opposite sequence, i.e. the last cut-in relay will be cut out first.
Cyclic (first in - first out)
The relays are coupled here so that the operating time of the individual relays will become equalised.
At each cutin the regulation scans the individual relays’ timer, cutting in the relay with least time on it.
At each cutout a similar thing happens. Here the relay is cut out that has most hours on the timer.
Rx = random relay h = number of hours
AK-PC 531B |
Manual RS8HG102 © Danfoss 11-2015 |
3 |
Suvey of functions
Function |
Para- |
Parameter by operation via |
|
meter |
data communication |
Normal display |
|
|
If the two displays are mounted: |
|
P0 b (bar) |
P0 will be shown on EKA 165 / EKA 164 (the one with buttons) |
|
Pc b (bar) |
Pc will be shown on EKA 163 |
|
|
Compressor regulation reference |
|
Compressor control |
|
|
|
P0 setpoint |
r23 |
Set Point b |
Regulation is based on the set value plus an offset, if applicable. An offset can be |
|
|
created from night setback r13 and/or from a master gateway’s override function. |
|
|
Offset |
r13 |
Night offset |
The set reference may be displaced with a fixed value when a signal is received at |
|
|
the DI4 input or from the function "Night setback" (r27). |
|
|
(Cf. also Definition of DI4 input). |
|
|
Night setback |
r27 |
NightSetBack |
OFF: No change of the reference |
|
|
ON: Offset value forms part of the reference |
|
|
Reference |
r24 |
Comp ref. b |
The regulation reference is shown here |
|
|
Set point limitation |
|
|
With these settings the setpoint can only be set between the two values. |
|
|
(This also apply if regulation with "P0-optimisation function".) |
|
|
|
|
|
Max. permissible setpoint value. |
r25 |
P0RefMax b |
|
|
|
Min. permissible setpoint value. |
r26 |
P0RefMin b |
|
|
|
Neutral zone |
r01 |
Neutral zone |
There is a neutral zone around the reference. See also page 3. |
|
|
Correction of pressure measurement |
r04 |
AdjustSensor |
An offset adjustment of the registered pressure can be made. |
|
|
Unit |
r05 |
(In AKM only bar or °C is used, |
Here you can select whether thedisplay is to indicate pressure in bar or in Psig. |
|
whatever the setting) |
And temperatures in °C or °F. |
|
|
0: Will give bar and °C. |
|
|
1: Will give Psig and °F. |
|
|
Start/stop of refrigeration |
r12 |
Main Switch |
With this setting the refrigeration can be started and stopped. Start/stop of |
|
|
refrigeration may also be performed with an external contact function connected |
|
|
to the input named “ON input”. |
|
|
|
|
|
Condenser regulation reference |
|
Condenser control |
Pc setpoint |
r28 |
Set Point b |
Regulation is based on the set value plus an offset, if applicable. An offset can be |
|
|
created via the “r34” function and/or from a master gateway’s override function. |
|
|
Offset |
r34 |
Press.offset |
The set reference may be displaced with a fixed value when a signal is received |
|
|
at the DI5 input. (Cf. also Definition of DI5 input). |
|
|
Pc reference variation |
r33 |
Pc mode |
1: No change of the reference. Regulation based on set setpoint. |
|
|
2: Outdoor temperature forms part of the reference. The outdoor temperature |
|
|
is measured with Sc3. When the outdoor temperature drops one degree, the |
|
|
reference is lowered one degree. |
|
|
Setting 1 and 2 operate with a PI regulation. |
|
|
If the system is unstable and the PI regulation not satisfactory the I element may |
|
|
be left out, so there will be P regulation only. |
|
|
3: As 1, but with P regulation |
|
|
4: As 2, but with P regulation |
|
|
The regulation reference is shown here. |
r29 |
Cond ref. b |
|
|
|
The mean temperature difference across the condenser at maximum load (dim tm K) |
r35 |
Dim.Tm K |
|
|
|
The mean temperature difference across the condenser at the lowest relevant com- |
r56 |
Min tm K |
pressor capacity (min tm K) |
|
|
Set point limitation |
|
|
With these settings the setpoint can only be set between the two values. |
|
|
|
|
|
Max. permissible setpoint value. |
r30 |
PcRefMax b |
Min. permissible setpoint value. |
r31 |
PcRefMin b |
4 |
Manual RS8HG102 © Danfoss 11-2015 |
AK-PC 531B |
Correction of pressure measurement |
r32 |
AdjustSensor |
An offset adjustment of the registered pressure can be made. |
|
|
|
|
|
Compressor capacity |
|
Compressor pack config. |
|
|
|
Running time |
|
|
To prevent frequent start/stop, values have to be set for how the relays are to cut |
|
|
in and out. |
|
|
Min. ON time for relays. |
c01 |
Min.ON time |
(The time is not used if the relay cuts an unloader in or out). |
|
|
Min. time period between cutin of same relay. |
c07 |
MinRecyTime |
|
|
|
Setting for neutral zone regulation |
|
|
|
|
|
Regulation band over the neutral zonen |
c10 |
+ Zone b |
|
|
|
Time delay between step cut-ins in the regulation band over the neutral zone |
c11 |
+ Zone m |
|
|
|
Time delay between step cut-ins in the regulation band over the "+Zone band". |
c12 |
+ + Zone m |
|
|
|
Regulation band under the neutral zone |
c13 |
- Zone b |
|
|
|
Time delay between step cut-outs in the regulation band under the neutral zone |
c14 |
- Zone m |
|
|
|
Time delay between step cut-outs in the regulation band under the "-Zone band" |
c15 |
- - Zone m |
|
|
|
Compressor configuration |
c16 |
Compr mode |
Here you set the combination of number of compressors and any unloaders. |
|
|
1 = One compressor, 2 = two compressors, 3 = three, 4 = four....10 = ten. |
|
|
See page 9. |
|
|
Selection of coupling mode (See also the overview page 9) |
c08 |
Step mode |
1.Sequential: First relay 1 cuts in, then relay 2, etc. Cutout takes place in the opposite sequence. (”First in, last out”).
2.Cyclic: An automatic operating time equalisation is arranged here, so that all steps with motor connection will have the same operating time
Definition of condenser and number of fans |
c29 |
No. of Fans |
Here you set the number of fan steps with which regulation has to be carried out (but |
|
|
max. eight). |
|
|
1-8: All fans are cut in and out with relays. The first vacant relay number is assigned to |
|
|
fan 1, the next to number 2, etc. Steps after DO10 must be executed through connec- |
|
|
tion of a relay module type EKC 331 to the analog output. Cf. drawing on page 9. |
|
|
9: All fans are controlled via the analog output and a frequency converter. |
|
|
10: Not used |
|
|
11-18: Total number of fan relays which are to be connected with alternating start-up. |
|
|
Read temperature at sensor Sc3 |
u44 |
Sc3 temp |
Read temperature at sensor Sc4 (sensor is only used for monitoring) |
u45 |
Sc4 temp |
Read temperature at sensor "Saux" |
u03 |
Saux temp |
Status on DI3 input |
u87 |
DI 3 status |
Status on DI4 input |
u88 |
DI 4 status |
Status on DI5 input |
u89 |
DI 5 status |
|
- |
- - - Comp. Cap % |
|
|
Read cut-in compressor capacity |
|
- |
- - - Cond. Cap % |
|
|
Read cut-in condenser capacity |
Regulation parameters for the condenser regulation |
|
|
P: Amplification factor Xp (P = 100/Xp) |
n04 |
Xp b |
If the Xp value is increased, the regulation becomes steadier |
|
|
I: Integration time Tn |
n05 |
Tn s |
If the Tn value is increased, the regulation becomes steadier |
|
|
Cutin condenser capacity with manual control. See also “n53” |
n52 |
FanManCap% |
Manual control of condenser capacity (when ON, the value in “n52” will be used) |
n53 |
FanManCap |
AK-PC 531B |
Manual RS8HG102 © Danfoss 11-2015 |
5 |