Danfoss AK-PC 531B User guide

Design guide

Capacity controller

AK-PC 531B

ADAP-KOOL® Refrigeration control systems

Introduction

Application

The controller is used for capacity regulation of compressors and / or condensers in small refrigerating systems.

This controller can regulate up to ten compressors. The condenser capacity is step regulated via the remaining available digital outputs and external relay module or variable speed regulated via a frequency converter.

Advantages

Patented neutral zone regulation

Sequential or cyclic operation

Possibility of suction pressure optimisation via the data communication

Load shedding function

Regulation

Regulation is based on signals from one pressure transmitter for the compressor regulation and one pressure transmitter for the condenser regulation plus one temperature sensor for the air temperature before the condenser.

Functions

Relays for capacity regulation

Voltage output for capacity regulation

Status inputs. An interrupted signal indicates that the safety circuit has been activated and the respective circuit stopped

Contact inputs for indication of alarms

Contact inputs for displacement of references or for indication of alarms

Alarm relay

External start/stop of regulation

Possibility of data communication

Operation

All operation takes place either via data communication or via connection of a display type EKA 164. The display can be disconnected after the installation.

2

Manual  RS8HG102  ©  Danfoss  11-2015

AK-PC 531B

Danfoss AK-PC 531B User guide

Function

Capacity regulation

The cut-in capacity is controlled by signals from the connected pressure transmitter and the set reference.

Outside the reference a neutral zone is set where the capacity will neither be cut in nor out.

Outside the neutral zone (in the hatched areas named +zone and -zone) the capacity will be cut in or out if the regulation registers a change of pressure “away” from the neutral zone.

Cut in and cut out will take place with the set time delays. If the pressure however “approaches” the neutral zone, the controller will make no changes of the cut-in capacity.

If regulation takes place outside the hatched area (named ++zone and --zone), changes of the cut-in capacity will occur somewhat faster than if it were in the hatched area.

Cut in of steps can be defined for either sequential or cyclic operation.

Sequential (first in - last out)

The relays are here cut in in sequence – first relay number 1, then 2, etc.

Cutout takes place in the opposite sequence, i.e. the last cut-in relay will be cut out first.

Cyclic (first in - first out)

The relays are coupled here so that the operating time of the individual relays will become equalised.

At each cutin the regulation scans the individual relays’ timer, cutting in the relay with least time on it.

At each cutout a similar thing happens. Here the relay is cut out that has most hours on the timer.

Rx = random relay h = number of hours

AK-PC 531B

Manual  RS8HG102  ©  Danfoss  11-2015

3

Suvey of functions

Function

Para-

Parameter by operation via

 

meter

data communication

Normal display

 

 

If the two displays are mounted:

 

P0 b (bar)

P0 will be shown on EKA 165 / EKA 164 (the one with buttons)

 

Pc b (bar)

Pc will be shown on EKA 163

 

 

Compressor regulation reference

 

Compressor control

 

 

 

P0 setpoint

r23

Set Point b

Regulation is based on the set value plus an offset, if applicable. An offset can be

 

 

created from night setback r13 and/or from a master gateway’s override function.

 

 

Offset

r13

Night offset

The set reference may be displaced with a fixed value when a signal is received at

 

 

the DI4 input or from the function "Night setback" (r27).

 

 

(Cf. also Definition of DI4 input).

 

 

Night setback

r27

NightSetBack

OFF: No change of the reference

 

 

ON: Offset value forms part of the reference

 

 

Reference

r24

Comp ref. b

The regulation reference is shown here

 

 

Set point limitation

 

 

With these settings the setpoint can only be set between the two values.

 

 

(This also apply if regulation with "P0-optimisation function".)

 

 

 

 

 

Max. permissible setpoint value.

r25

P0RefMax b

 

 

 

Min. permissible setpoint value.

r26

P0RefMin b

 

 

 

Neutral zone

r01

Neutral zone

There is a neutral zone around the reference. See also page 3.

 

 

Correction of pressure measurement

r04

AdjustSensor

An offset adjustment of the registered pressure can be made.

 

 

Unit

r05

(In AKM only bar or °C is used,

Here you can select whether thedisplay is to indicate pressure in bar or in Psig.

 

whatever the setting)

And temperatures in °C or °F.

 

 

0: Will give bar and °C.

 

 

1: Will give Psig and °F.

 

 

Start/stop of refrigeration

r12

Main Switch

With this setting the refrigeration can be started and stopped. Start/stop of

 

 

refrigeration may also be performed with an external contact function connected

 

 

to the input named “ON input”.

 

 

 

 

 

Condenser regulation reference

 

Condenser control

Pc setpoint

r28

Set Point b

Regulation is based on the set value plus an offset, if applicable. An offset can be

 

 

created via the “r34” function and/or from a master gateway’s override function.

 

 

Offset

r34

Press.offset

The set reference may be displaced with a fixed value when a signal is received

 

 

at the DI5 input. (Cf. also Definition of DI5 input).

 

 

Pc reference variation

r33

Pc mode

1: No change of the reference. Regulation based on set setpoint.

 

 

2: Outdoor temperature forms part of the reference. The outdoor temperature

 

 

is measured with Sc3. When the outdoor temperature drops one degree, the

 

 

reference is lowered one degree.

 

 

Setting 1 and 2 operate with a PI regulation.

 

 

If the system is unstable and the PI regulation not satisfactory the I element may

 

 

be left out, so there will be P regulation only.

 

 

3: As 1, but with P regulation

 

 

4: As 2, but with P regulation

 

 

The regulation reference is shown here.

r29

Cond ref. b

 

 

 

The mean temperature difference across the condenser at maximum load (dim tm K)

r35

Dim.Tm K

 

 

 

The mean temperature difference across the condenser at the lowest relevant com-

r56

Min tm K

pressor capacity (min tm K)

 

 

Set point limitation

 

 

With these settings the setpoint can only be set between the two values.

 

 

 

 

 

Max. permissible setpoint value.

r30

PcRefMax b

Min. permissible setpoint value.

r31

PcRefMin b

4

Manual  RS8HG102  ©  Danfoss  11-2015

AK-PC 531B

Correction of pressure measurement

r32

AdjustSensor

An offset adjustment of the registered pressure can be made.

 

 

 

 

 

Compressor capacity

 

Compressor pack config.

 

 

 

Running time

 

 

To prevent frequent start/stop, values have to be set for how the relays are to cut

 

 

in and out.

 

 

Min. ON time for relays.

c01

Min.ON time

(The time is not used if the relay cuts an unloader in or out).

 

 

Min. time period between cutin of same relay.

c07

MinRecyTime

 

 

 

Setting for neutral zone regulation

 

 

 

 

 

Regulation band over the neutral zonen

c10

+ Zone b

 

 

 

Time delay between step cut-ins in the regulation band over the neutral zone

c11

+ Zone m

 

 

 

Time delay between step cut-ins in the regulation band over the "+Zone band".

c12

+ + Zone m

 

 

 

Regulation band under the neutral zone

c13

- Zone b

 

 

 

Time delay between step cut-outs in the regulation band under the neutral zone

c14

- Zone m

 

 

 

Time delay between step cut-outs in the regulation band under the "-Zone band"

c15

- - Zone m

 

 

 

Compressor configuration

c16

Compr mode

Here you set the combination of number of compressors and any unloaders.

 

 

1 = One compressor, 2 = two compressors, 3 = three, 4 = four....10 = ten.

 

 

See page 9.

 

 

Selection of coupling mode (See also the overview page 9)

c08

Step mode

1.Sequential: First relay 1 cuts in, then relay 2, etc. Cutout takes place in the opposite sequence. (”First in, last out”).

2.Cyclic: An automatic operating time equalisation is arranged here, so that all steps with motor connection will have the same operating time

Definition of condenser and number of fans

c29

No. of Fans

Here you set the number of fan steps with which regulation has to be carried out (but

 

 

max. eight).

 

 

1-8: All fans are cut in and out with relays. The first vacant relay number is assigned to

 

 

fan 1, the next to number 2, etc. Steps after DO10 must be executed through connec-

 

 

tion of a relay module type EKC 331 to the analog output. Cf. drawing on page 9.

 

 

9: All fans are controlled via the analog output and a frequency converter.

 

 

10: Not used

 

 

11-18: Total number of fan relays which are to be connected with alternating start-up.

 

 

Read temperature at sensor Sc3

u44

Sc3 temp

Read temperature at sensor Sc4 (sensor is only used for monitoring)

u45

Sc4 temp

Read temperature at sensor "Saux"

u03

Saux temp

Status on DI3 input

u87

DI 3 status

Status on DI4 input

u88

DI 4 status

Status on DI5 input

u89

DI 5 status

 

-

- - - Comp. Cap %

 

 

Read cut-in compressor capacity

 

-

- - - Cond. Cap %

 

 

Read cut-in condenser capacity

Regulation parameters for the condenser regulation

 

 

P: Amplification factor Xp (P = 100/Xp)

n04

Xp b

If the Xp value is increased, the regulation becomes steadier

 

 

I: Integration time Tn

n05

Tn s

If the Tn value is increased, the regulation becomes steadier

 

 

Cutin condenser capacity with manual control. See also “n53”

n52

FanManCap%

Manual control of condenser capacity (when ON, the value in “n52” will be used)

n53

FanManCap

AK-PC 531B

Manual  RS8HG102  ©  Danfoss  11-2015

5

Loading...
+ 11 hidden pages