Danfoss AK-PC 531B User guide

Design guide
Capacity controller
AK-PC 531B
ADAP-KOOL® Refrigeration control systems
Introduction
Application
The controller is used for capacity regulation of compressors and / or condensers in small refrigerating systems. This controller can regulate up to ten compressors. The condenser capacity is step regulated via the remaining available digital outputs and external relay module or variable speed regulated via a frequency converter.
Advantages
• Patented neutral zone regulation
• Sequential or cyclic operation
• Possibility of suction pressure optimisation via the data communication
• Load shedding function
Regulation
Regulation is based on signals from one pressure transmitter for the compressor regulation and one pressure transmitter for the condenser regulation plus one temperature sensor for the air temperature before the condenser.
Functions
• Relays for capacity regulation
• Voltage output for capacity regulation
• Status inputs. An interrupted signal indicates that the safety circuit has been activated and the respective circuit stopped
• Contact inputs for indication of alarms
• Contact inputs for displacement of references or for indication of alarms
• Alarm relay
• External start/stop of regulation
• Possibility of data communication
Operation
All operation takes place either via data communication or via connection of a display type EKA 164. The display can be disconnected after the installation.
2 Manual RS8HG102 © Danfoss 11-2015 AK-PC 531B
Function
Capacity regulation
The cut-in capacity is controlled by signals from the connected pressure transmitter and the set reference. Outside the reference a neutral zone is set where the capacity will neither be cut in nor out. Outside the neutral zone (in the hatched areas named +zone and -zone) the capacity will be cut in or out if the regulation registers a change of pressure “away” from the neutral zone. Cut in and cut out will take place with the set time delays. If the pressure however “approaches” the neutral zone, the controller will make no changes of the cut-in capacity. If regulation takes place outside the hatched area (named ++zone and --zone), changes of the cut-in capacity will occur somewhat faster than if it were in the hatched area. Cut in of steps can be dened for either sequential or cyclic operation.
Sequential (rst in - last out) The relays are here cut in in sequence – rst relay number 1, then 2, etc. Cutout takes place in the opposite sequence, i.e. the last cut-in relay will be cut out rst.
Cyclic (rst in - rst out) The relays are coupled here so that the operating time of the individual relays will become equalised. At each cutin the regulation scans the individual relays’ timer, cutting in the relay with least time on it. At each cutout a similar thing happens. Here the relay is cut out that has most hours on the timer.
Rx = random relay h = number of hours
AK-PC 531B Manual RS8HG102 © Danfoss 11-2015 3
Suvey of functions
Function Para-
meter
Normal display
If the two displays are mounted: P0 will be shown on EKA 165 / EKA 164 (the one with buttons) Pc will be shown on EKA 163
Compressor regulation reference Compressor control
P0 setpoint
Regulation is based on the set value plus an oset, if applicable. An oset can be created from night setback r13 and/or from a master gateway’s override function.
Oset
The set reference may be displaced with a xed value when a signal is received at the DI4 input or from the function "Night setback" (r27). (Cf. also Denition of DI4 input).
Night setback OFF: No change of the reference ON: Oset value forms part of the reference
Reference
The regulation reference is shown here
Set point limitation
With these settings the setpoint can only be set between the two values. (This also apply if regulation with "P0-optimisation function".)
Max. permissible setpoint value. r25 P0RefMax b
Min. permissible setpoint value. r26 P0RefMin b
Neutral zone
There is a neutral zone around the reference. See also page 3.
Correction of pressure measurement
An oset adjustment of the registered pressure can be made.
Unit
Here you can select whether thedisplay is to indicate pressure in bar or in Psig. And temperatures in °C or °F.
0: Will give bar and °C. 1: Will give Psig and °F.
Start/stop of refrigeration
With this setting the refrigeration can be started and stopped. Start/stop of refrigeration may also be performed with an external contact function connected to the input named “ON input”.
Condenser regulation reference Condenser control Pc setpoint
Regulation is based on the set value plus an oset, if applicable. An oset can be created via the “r34” function and/or from a master gateway’s override function.
Oset
The set reference may be displaced with a xed value when a signal is received at the DI5 input. (Cf. also Denition of DI5 input).
Pc reference variation 1: No change of the reference. Regulation based on set setpoint. 2: Outdoor temperature forms part of the reference. The outdoor temperature
is measured with Sc3. When the outdoor temperature drops one degree, the reference is lowered one degree. Setting 1 and 2 operate with a PI regulation. If the system is unstable and the PI regulation not satisfactory the I element may be left out, so there will be P regulation only.
3: As 1, but with P regulation 4: As 2, but with P regulation
The regulation reference is shown here. r29 Cond ref. b
The mean temperature dierence across the condenser at maximum load (dim tm K) r35 Dim.Tm K
The mean temperature dierence across the condenser at the lowest relevant com­pressor capacity (min tm K)
Set point limitation
With these settings the setpoint can only be set between the two values.
Max. permissible setpoint value. r30 PcRefMax b Min. permissible setpoint value. r31 PcRefMin b
Parameter by operation via data communication
P0 b (bar) Pc b (bar)
r23 Set Point b
r13 Night oset
r27 NightSetBack
r24 Comp ref. b
r01 Neutral zone
r04 AdjustSensor
r05 (In AKM only bar or °C is used,
whatever the setting)
r12 Main Switch
r28 Set Point b
r34 Press.oset
r33 Pc mode
r56 Min tm K
4 Manual RS8HG102 © Danfoss 11-2015 AK-PC 531B
Correction of pressure measurement
An oset adjustment of the registered pressure can be made.
Compressor capacity Compressor pack cong.
Running time
To prevent frequent start/stop, values have to be set for how the relays are to cut in and out.
Min. ON time for relays. (The time is not used if the relay cuts an unloader in or out).
Min. time period between cutin of same relay. c07 MinRecyTime
Setting for neutral zone regulation
Regulation band over the neutral zonen c10 + Zone b
Time delay between step cut-ins in the regulation band over the neutral zone c11 + Zone m
Time delay between step cut-ins in the regulation band over the "+Zone band". c12 + + Zone m
Regulation band under the neutral zone c13 - Zone b
Time delay between step cut-outs in the regulation band under the neutral zone c14 - Zone m
Time delay between step cut-outs in the regulation band under the "-Zone band" c15 - - Zone m
Compressor conguration
Here you set the combination of number of compressors and any unloaders.
1 = One compressor, 2 = two compressors, 3 = three, 4 = four....10 = ten.
See page 9. Selection of coupling mode (See also the overview page 9)
1. Sequential: First relay 1 cuts in, then relay 2, etc. Cutout takes place in the opposite sequence. (”First in, last out”).
2. Cyclic: An automatic operating time equalisation is arranged here, so that all steps with motor connection will have the same operating time
r32 AdjustSensor
c01 Min.ON time
c16 Compr mode
c08 Step mode
Denition of condenser and number of fans
Here you set the number of fan steps with which regulation has to be carried out (but max. eight). 1-8: All fans are cut in and out with relays. The rst vacant relay number is assigned to fan 1, the next to number 2, etc. Steps after DO10 must be executed through connec­tion of a relay module type EKC 331 to the analog output. Cf. drawing on page 9.
9: All fans are controlled via the analog output and a frequency converter. 10: Not used 11-18: Total number of fan relays which are to be connected with alternating start-up.
Read temperature at sensor Sc3 u44 Sc3 temp Read temperature at sensor Sc4 (sensor is only used for monitoring) u45 Sc4 temp
Read temperature at sensor "Saux" u03 Saux temp Status on DI3 input u87 DI 3 status Status on DI4 input u88 DI 4 status Status on DI5 input u89 DI 5 status
Regulation parameters for the condenser regulation P: Amplication factor Xp (P = 100/Xp)
If the Xp value is increased, the regulation becomes steadier
I: Integration time Tn
If the Tn value is increased, the regulation becomes steadier Cutin condenser capacity with manual control. See also “n53” n52 FanManCap% Manual control of condenser capacity (when ON, the value in “n52” will be used) n53 FanManCap
c29 No. of Fans
- - - - Comp. Cap % Read cut-in compressor capacity
- - - - Cond. Cap % Read cut-in condenser capacity
n04 Xp b
n05 Tn s
AK-PC 531B Manual RS8HG102 © Danfoss 11-2015 5
Loading...
+ 11 hidden pages