The controller is used for capacity regulation of compressors
and / or condensers in small refrigerating systems.
This controller can regulate up to ten compressors. The condenser
capacity is step regulated via the remaining available digital
outputs and external relay module or variable speed regulated via
a frequency converter.
Advantages
• Patented neutral zone regulation
• Sequential or cyclic operation
• Possibility of suction pressure optimisation via the data
communication
• Load shedding function
Regulation
Regulation is based on signals from one pressure transmitter for
the compressor regulation and one pressure transmitter for the
condenser regulation plus one temperature sensor for the air
temperature before the condenser.
Functions
• Relays for capacity regulation
• Voltage output for capacity regulation
• Status inputs. An interrupted signal indicates that the
safety circuit has been activated and the respective
circuit stopped
• Contact inputs for indication of alarms
• Contact inputs for displacement of references or for
indication of alarms
• Alarm relay
• External start/stop of regulation
• Possibility of data communication
Operation
All operation takes place either via data communication or
via connection of a display type EKA 164. The display can be
disconnected after the installation.
The cut-in capacity is controlled by signals from the connected
pressure transmitter and the set reference.
Outside the reference a neutral zone is set where the capacity
will neither be cut in nor out.
Outside the neutral zone (in the hatched areas named +zone
and -zone) the capacity will be cut in or out if the regulation
registers a change of pressure “away” from the neutral zone.
Cut in and cut out will take place with the set time delays.
If the pressure however “approaches” the neutral zone, the
controller will make no changes of the cut-in capacity.
If regulation takes place outside the hatched area (named
++zone and --zone), changes of the cut-in capacity will occur
somewhat faster than if it were in the hatched area.
Cut in of steps can be dened for either sequential or cyclic
operation.
Sequential (rst in - last out)
The relays are here cut in in sequence – rst relay number 1,
then 2, etc.
Cutout takes place in the opposite sequence, i.e. the last
cut-in relay will be cut out rst.
Cyclic (rst in - rst out)
The relays are coupled here so that the operating time of
the individual relays will become equalised.
At each cutin the regulation scans the individual relays’
timer, cutting in the relay with least time on it.
At each cutout a similar thing happens. Here the relay is cut
out that has most hours on the timer.
If the two displays are mounted:
P0 will be shown on EKA 165 / EKA 164 (the one with buttons)
Pc will be shown on EKA 163
Compressor regulation referenceCompressor control
P0 setpoint
Regulation is based on the set value plus an oset, if applicable. An oset can be
created from night setback r13 and/or from a master gateway’s override function.
Oset
The set reference may be displaced with a xed value when a signal is received at
the DI4 input or from the function "Night setback" (r27).
(Cf. also Denition of DI4 input).
Night setback
OFF: No change of the reference
ON: Oset value forms part of the reference
Reference
The regulation reference is shown here
Set point limitation
With these settings the setpoint can only be set between the two values.
(This also apply if regulation with "P0-optimisation function".)
Max. permissible setpoint value.r25P0RefMax b
Min. permissible setpoint value.r26P0RefMin b
Neutral zone
There is a neutral zone around the reference. See also page 3.
Correction of pressure measurement
An oset adjustment of the registered pressure can be made.
Unit
Here you can select whether thedisplay is to indicate pressure in bar or in Psig.
And temperatures in °C or °F.
0: Will give bar and °C.
1: Will give Psig and °F.
Start/stop of refrigeration
With this setting the refrigeration can be started and stopped. Start/stop of
refrigeration may also be performed with an external contact function connected
to the input named “ON input”.
Condenser regulation referenceCondenser control
Pc setpoint
Regulation is based on the set value plus an oset, if applicable. An oset can be
created via the “r34” function and/or from a master gateway’s override function.
Oset
The set reference may be displaced with a xed value when a signal is received
at the DI5 input. (Cf. also Denition of DI5 input).
Pc reference variation
1: No change of the reference. Regulation based on set setpoint.
2: Outdoor temperature forms part of the reference. The outdoor temperature
is measured with Sc3. When the outdoor temperature drops one degree, the
reference is lowered one degree.
Setting 1 and 2 operate with a PI regulation.
If the system is unstable and the PI regulation not satisfactory the I element may
be left out, so there will be P regulation only.
3: As 1, but with P regulation
4: As 2, but with P regulation
The regulation reference is shown here.r29Cond ref. b
The mean temperature dierence across the condenser at maximum load (dim tm K)r35Dim.Tm K
The mean temperature dierence across the condenser at the lowest relevant compressor capacity (min tm K)
Set point limitation
With these settings the setpoint can only be set between the two values.
Max. permissible setpoint value.r30PcRefMax b
Min. permissible setpoint value.r31PcRefMin b
An oset adjustment of the registered pressure can be made.
Compressor capacityCompressor pack cong.
Running time
To prevent frequent start/stop, values have to be set for how the relays are to cut
in and out.
Min. ON time for relays.
(The time is not used if the relay cuts an unloader in or out).
Min. time period between cutin of same relay.c07MinRecyTime
Setting for neutral zone regulation
Regulation band over the neutral zonenc10+ Zone b
Time delay between step cut-ins in the regulation band over the neutral zonec11+ Zone m
Time delay between step cut-ins in the regulation band over the "+Zone band".c12+ + Zone m
Regulation band under the neutral zonec13- Zone b
Time delay between step cut-outs in the regulation band under the neutral zonec14- Zone m
Time delay between step cut-outs in the regulation band under the "-Zone band"c15- - Zone m
Compressor conguration
Here you set the combination of number of compressors and any unloaders.
1 = One compressor, 2 = two compressors, 3 = three, 4 = four....10 = ten.
See page 9.
Selection of coupling mode (See also the overview page 9)
1. Sequential: First relay 1 cuts in, then relay 2, etc. Cutout takes place in the opposite
sequence. (”First in, last out”).
2. Cyclic: An automatic operating time equalisation is arranged here, so that all steps
with motor connection will have the same operating time
r32AdjustSensor
c01Min.ON time
c16Compr mode
c08Step mode
Denition of condenser and number of fans
Here you set the number of fan steps with which regulation has to be carried out (but
max. eight).
1-8: All fans are cut in and out with relays. The rst vacant relay number is assigned to
fan 1, the next to number 2, etc. Steps after DO10 must be executed through connection of a relay module type EKC 331 to the analog output. Cf. drawing on page 9.
9: All fans are controlled via the analog output and a frequency converter.
10: Not used
11-18: Total number of fan relays which are to be connected with alternating start-up.
Read temperature at sensor Sc3u44Sc3 temp
Read temperature at sensor Sc4 (sensor is only used for monitoring)u45Sc4 temp
Read temperature at sensor "Saux"u03Saux temp
Status on DI3 inputu87 DI 3 status
Status on DI4 inputu88 DI 4 status
Status on DI5 inputu89 DI 5 status
Regulation parameters for the condenser regulation
P: Amplication factor Xp (P = 100/Xp)
If the Xp value is increased, the regulation becomes steadier
I: Integration time Tn
If the Tn value is increased, the regulation becomes steadier
Cutin condenser capacity with manual control. See also “n53”n52FanManCap%
Manual control of condenser capacity (when ON, the value in “n52” will be used)n53FanManCap
c29No. of Fans
-- - - Comp. Cap %
Read cut-in compressor capacity