Danfoss AK-PC 520 User guide

User Guide

Capacity controller

AK-PC 520

ADAP-KOOL® Refrigeration control systems

Introduction

Application

The controller is used for capacity regulation of compressors or condensers in small refrigerating systems.

There are eight outputs and up to 4 compressors and 4 fans can be coupled.

Advantages

Energy conservation during:

-Suction pressure optimisation (P0)

-Variable condensing pressure (Pc)

Patented neutral zone regulation

Many possible combinations for compressor constellations

Sequential or cyclic operation

Possibility of suction pressure optimisation via the data communication

Regulation

Regulation is based on signals from one pressure transmitter for the compressor regulation and one pressure transmitter for the condenser regulation plus one temperature sensor for the air temperature before the condenser.

The two pressure transmitters can be replaced by two temperature sensors when regulation has to be carried out on brine systems.

Pressure regulation P0 (pack)

Temperature regulation Sx (chiller)

Pressure regulation Pc (pack / chiller)

Pressure regulation with variable reference Pc (Sc3)

Functions

Relays for compressor and condenser regulation

Voltage output for capacity regulation of condenser

Status inputs. An interrupted signal indicates that the safety circuit has been activated and the respective circuit stopped

Contact inputs for indication of alarms

Contact inputs for displacement of references or for indication of alarms

Alarm relay

External start/stop of regulation

Possibility of data communication

Operation

All operation takes place either via data communication or via connection of a display type EKA 164 or EKA 165.

Combinations

The controller has ten relay outputs two of which have been reserved for the alarm function and for the ”VLT start/stop” function.

For a start relays are reserved for compressor capacities starting from DO1, DO2, etc.

The next relay and the following will be for fans (max. 4 fans). Another solution could be that the fan speed is controlled via the analog output and a frequency converter.

Compressors and unloaders can be combined in various ways. Cf. survey on page 11.

Contents

 

Introduction........................................................................................................

2

Function...............................................................................................................

3

Survey of functions..........................................................................................

4

Operation...........................................................................................................

13

Menu survey.....................................................................................................

14

Connections......................................................................................................

18

Data......................................................................................................................

19

Ordering.............................................................................................................

19

Montage.............................................................................................................

19

Safety function.................................................................................................

20

Override..............................................................................................................

21

Appendix............................................................................................................

22

2

Manual  RS8FK202  ©  Danfoss  12-2009

AK-PC 520

Danfoss AK-PC 520 User guide

Function

Capacity regulation

The cut-in capacity is controlled by signals from the connected pressure transmitter/temperature sensor and the set reference. Outside the reference a neutral zone is set where the capacity will neither be cut in nor out.

Outside the neutral zone (in the hatched areas named +zone and -zone) the capacity will be cut in or out if the regulation registers a change of pressure “away” from the neutral zone. Cutin and cutout will take place with the set time delays.

If the pressure however “approaches” the neutral zone, the controller will make no changes of the cut-in capacity.

If regulation takes place outside the hatched area (named ++zone and --zone), changes of the cut-in capacity will occur somewhat faster than if it were in the hatched area.

Cutin of steps can be defined for either sequential or cyclic operation.

Sequential (first in - last out)

The relays are here cut in in sequence – first relay number 1, then 2, etc.

Cutout takes place in the opposite sequence, i.e. the last cut-in relay will be cut out first.

Cyclic (first in - first out)

The relays are coupled here so that the operating time of the individual relays will become equalised.

At each cutin the regulation scans the individual relays’ timer, cutting in the relay with least time on it.

At each cutout a similar thing happens. Here the relay is cut out that has most hours on the timer.

Rx = random relay h = number of hours

If capacity regulation is carried out on two compressors with one unloader each, the following function can be used:

Relays 1 and 3 are connected to the compressor motor. Relays 2 and 4 are connected to the unloaders.

Relays 1 and 3 will operate in such a way that the operating time for the two relays will become equalised.

C = compressor, L = Unloader

AK-PC 520

Manual  RS8FK202  ©  Danfoss  12-2009

3

Survey of functions

The total function content is shown below – not all functions are present at the same time. The setting of o61 determines which functions are present.

The menu overview on page 14 shows the various functions and settings.

 

Para-

Parameter by operation via

Function

meter

data communication

Normal display

 

 

If the two displays are mounted:

 

P0 °C or P0 b

P0 will be shown on EKA 165 (the one with buttons)

 

Pc °C or Pc b

Pc will be shown on EKA 163. Both readouts will be in temperature or in bar.

 

 

Compressor regulation reference

 

Compressor control

P0 setpoint

r23

P0Set Point °C / P0Set Point b

Regulation is based on the set value plus an offset, if applicable. An offset can be cre-

 

 

ated from night setback r13 and/or from a system units override function.

 

 

Offset

r13

Night offset

The set reference may be displaced with a fixed value when a signal is received at the

 

 

DI4 input or from the function "Night setback" (r27).

 

 

(Cf. also Definition of DI4 input).

 

 

Night setback (Displacement of P0)

r27

NightSetBack

OFF: No change of the reference

 

 

ON: Offset value forms part of the reference

 

 

Reference

r24

P0 ref. °C / P0 ref. b

The regulation reference is shown here

 

 

Set point limitation

 

 

With these settings the setpoint can only be set between the two values.

 

 

(This also apply if regulation with displacements of the reference).

 

 

Max. permissible setpoint value.

r25

P0RefMax °C / P0RefMax b

Min. permissible setpoint value.

r26

P0RefMin °C / P0RefMin b

Neutral zone

r01

Neutral zone

There is a neutral zone around the reference. See also page 3.

 

 

Correction of pressure measurement

r04

AdjustSensor

An offset adjustment of the registered pressure can be made.

 

 

Unit

r05

 

Here you can select whether the display is to indicate in SI units or US units.

 

 

0: SI (°C / bar)

 

(In AKM onlySI (bar and °C) is used,

1: US (°F / psig)

 

whatever the setting)

Start/stop of refrigeration

r12

Main Switch

With this setting the refrigeration can be started and stopped. Start/stop of refrigera-

 

 

tion may also be performed with an external contact function connected to the input

 

 

named “ON input”. (The input must be wired).

 

 

Condenser regulation reference

 

Condenser control

Pc setpoint

r28

PcSet Point °C / PcSet Point b

Regulation is based on the set value plus an offset, if applicable. An offset can be cre-

 

 

ated via the “r34” function and/or from a system units override function.

 

 

Offset

r34

PcRefOffset

The set reference may be displaced with a fixed value when a signal is received at the

 

 

DI5 input. (Cf. also Definition of DI5 input).

 

 

Pc reference variation. See also page 22

r33

Pc mode

Regulation with setting 1 (or 2 if the reference is to vary with the outdoor tempera-

 

 

ture) will give the best regulation if the system is in balance. But if a lot of condenser

 

 

steps are cut in and out and the compressor capacity often becomes low, it will be

 

 

necessary to select setting 3 instead (or 4, if there is regulation with the outdoor tem-

 

 

perature). (Settings 3 and 4 will generally be preferable if a Pc-offset at max. compres-

 

 

sor capacity can be accepted).

 

 

1: No change of the reference. Regulation based on set setpoint. And offset with the

 

 

DI5 function is allowed.

 

 

2: Outdoor temperature forms part of the reference. The outdoor temperature is

 

 

measured with Sc3. When the outdoor temperature drops one degree, the reference

 

 

is lowered one degree.

 

 

Here is offset with the DI5 function not allowed. At DI5 signal the reference will

 

 

change to the set setpoint.

 

 

Setting 1 and 2 operate with a PI regulation, but if the system is unstable and the PI

 

 

regulation not satisfactory the I element may be left out, so that the controller will be

 

 

with P regulation only.

 

 

3: As 1, but with P regulation (xp-band)

 

 

4: As 2, but with P regulation (xp-band)

 

 

4

Manual  RS8FK202  ©  Danfoss  12-2009

AK-PC 520

Condenser reference

r29

Pc ref. °C / Pc ref. b

 

The regulation reference is shown here.

 

 

 

Set point limitation

 

 

 

With these settings the setpoint can only be set between the two values.

 

 

 

(This also applies to regulations where the Xp band lies above the reference).

 

 

 

Max. permissible setpoint value.

r30

PcRefMax °C / PcRefMax b

 

 

 

 

 

Min. permissible setpoint value.

r31

PcRefMin °C / PcRefMin b

 

 

 

 

Correction of pressure measurement

r32

AdjustSensor

An offset adjustment of the registered pressure can be made.

 

 

 

Dimensioning temperature Dim tm

r35

Dim tm K

 

The mean temperature difference across the condenser at maximum load (tm differ-

 

 

 

ence at max. load). This is the temperature difference between the air and condensing

 

 

 

temperature.

 

 

 

Dimensioning temperature Min tm

r56

Min tm K

 

The mean temperature difference across the condenser at the lowest relevant

 

 

 

compressor capacity (tm difference at min. load). This is the temperature difference

 

 

 

between the air and condensing temperature.

 

 

 

Reading your P0

r57 P0°C / P0 b

This is where you can see the actual pressure that is being measured by the pressure

 

 

 

transmitter.

 

 

 

The value is part of the regulation, since the regulation signal for capacity regulation

 

 

 

originates from the pressure transmitter.

 

 

 

The value is part of the frost protection regulation, since the regulation signal for

 

 

 

capacity regulation originates from the temperature sensor.

 

 

 

Reading your T0

r58

Cmp.CtrlSens

This is where you can see the actual pressure being measured by the sensor chosen

 

 

 

for capacity regulation (the sensor is defined in o81). The value is displayed in °C.

 

 

 

Compressor capacity

 

Compressor pack config.

 

Running time

 

 

 

To prevent frequent start/stop, values have to be set for how the relays are to cut in

 

 

 

and out.

 

 

 

Min. ON time for relays.

c01

Min.ON time

 

(The time is not used if the relay cuts an unloader in or out).

 

 

 

Min. time period between cutin of same relay.

c07

MinRecyTime

 

(The time is not used if the relay cuts an unloader in or out).

 

 

 

Setting for neutral zone regulation

 

 

 

Regulation band over the neutral zone

c10

+ Zone k / + Zone b

 

 

 

 

 

Time delay between step cut-ins in the regulation band over the neutral zone

c11

+ Zone m

Time delay between step cut-ins in the regulation band over the "+Zone band".

c12 + + Zone m

 

 

 

 

 

Regulation band under the neutral zone

c13

- Zone k / - Zone b

 

 

 

 

Time delay between step cut-outs in the regulation band under the neutral zone

c14

- Zone m

 

 

 

 

Time delay between step cut-outs in the regulation band under the "-Zone band"

c15

- - Zone m

Pump down limit

c33

PumpDownLim.

The factory setting for this function is OFF.

 

 

 

Activate by setting a value corresponding to pressure under the zone and over the P0

 

 

 

min. limit.

 

 

 

The function keeps the last capacity step going until the pressure comes down to the

 

 

 

pump down limit. When this value is reached the last compressor will cut out.

 

 

 

Do not reconnect capacity until the pressure is once more above the neutral zone.

 

 

 

Compressor configuration

c16

Compr mode

 

Here you set the predefined combination of number of compressors and any unload-

 

 

 

ers.

 

 

 

1 = One compressor, 2 = two compressors, 3 = three, 4 = four.

 

 

 

5 = One compressor + one unloader. 6 = One compressor + two unloaders.

 

 

 

For 7 to 8: See survey on page 11

 

 

 

Selection of coupling mode

c08

Step mode

 

1.Sequential: First relay 1 cuts in, then relay 2, etc. Cutout takes place in the opposite sequence. (”First in, last out”).

2.Cyclic: An automatic operating time equalisation is arranged here, so that all steps with motor connection will have the same operating time

Unloaders’ cutin and cutout mode

c09

Unloader

The relays for unloaders can be set to switch on when more capacity is required (set-

 

(switch on = 0)

ting = 0), or they can switch off when more capacity is called for (setting = 1).

 

(switch off = 1)

Manual control of compressor capacity

c31

CmpManCap%

This sets the capacity that is to be cut in when switching to manual control.

 

 

(c01 and c07 will still apply)

 

 

Manual control

c32

CmpManCap

Manual control of the compressor capacity is enabled here.

 

 

When set to ON, the capacity that is set in “c31” is cut in.

 

 

AK-PC 520

Manual  RS8FK202  ©  Danfoss  12-2009

5

 

-

- - - Comp. Cap %

 

 

Read cut-in compressor capacity

 

 

Actuel zone state:

 

 

0=off. 1= --zone. 2=-zone. 3=Neutral-

 

 

zone. 4=+zone. 5=++zone

Condenser capacity

 

 

Definition of condenser and number of fans

c29

Fan mode

Here you set the number of fan steps with which regulation has to be carried out (but

 

 

max. four).

 

 

1-4: All fans are cut in and out with relays. The first vacant relay number is assigned to

 

 

fan 1, the next to number 2, etc.

 

 

5-8: Not used

 

 

9: All fans controlled via the analog output and a frequency converter.

 

 

10: Not used

 

 

11-14: Total number of fan relays (as 1-4), but here the starting sequence is altered

 

 

after each time all fans are stopped.

 

 

Read temperature at sensor Sc3

u44

Sc3 temp

 

 

 

Read temperature at sensor Sc4 (sensor is only used for monitoring)

u45

Sc4 temp

 

 

 

 

-

- - - Fan Cap %

 

 

Read cut-in condenser capacity

Regulation parameters for the condenser regulation

 

 

Proportional band xp (P = 100/Xp)

n04

Xp K

If the Xp value is increased, the regulation becomes steadier

 

 

 

 

 

I: Integration time Tn

n05

Tn s

If the Tn value is increased, the regulation becomes steadier

 

 

Manual control of condenser capacity

n52

FanManCap%

This sets the capacity that is to be cut in when switching to manual control.

 

 

Manual control

n53

FanManCap

Manual control of the condenser capacity is enabled here.

 

 

When set to ON, the capacity that is specified in “n52” is cut in.

 

 

Speed control start value

n54

StartSpeed

Speed control will only be activated when the capacity requirement reaches this

 

 

value.

 

 

Speed control stop value

n55

MinSpeed

Speed control will be stopped when the capacity requirement falls below this value.

 

 

Alarm

 

Alarm settings

The controller can give alarm in different situations. When there is an alarm the light-

 

 

emitting diodes (LED) will flash on the display and the alarm relay will cut in.

 

 

P0 min. (Alarm and safety function, see also page 20.)

A11

Min. P0. b

Here you set when the alarm at too low suction pressure is to enter into effect. The

 

 

value is set as an absolute value.

 

 

Alarm delay P0 alarm

A44

P0AlrmDelay

The time delay is set in minutes. At min. setting the alarm is cancelled.

 

 

Pc max. (Alarm and safety function, see also page 20.)

A30

Max. Pc. b

Here you set when the alarm at too high condensing pressure is to enter into effect.

 

 

The value is set as an absolute value.

 

 

 

 

 

Alarm delay Pc alarm

A45

PcAlrmDelay

The time delay is set in minutes. At min. setting the alarm is cancelled.

 

 

Alarm delay DI1 (an interrupted input will give alarm).

A27

DI1AlrmDelay

The time delay is set in minutes. At max. setting the alarm is cancelled.

 

 

Alarm delay DI2 (an interrupted input will give alarm).

A28

DI2AlrmDelay

The time delay is set in minutes. At max. setting the alarm is cancelled.

 

 

Alarm delay DI3 (an interrupted input will give alarm).

A29

DI3AlrmDelay

The time delay is set in minutes. At max. setting the alarm is cancelled.

 

 

Alarm limit for high temperature of the “Saux1” sensor

A32

Saux1 high

With setting = Off the alarm has been opted out.

 

 

Alarm delay from "Saux1" (A32)

A03

Alarm delay

If the limit value is exceeded, a timer function will commence. The alarm will not be-

 

 

come active until the set time delay has been passed. The time delay is set in minutes.

 

 

Give the top button a brief push to zeroset the alarm and to have the message shown

 

Reset alarm

on the display.

 

The function zerosets all alarms when

 

 

set in pos. ON.

 

 

With data communication the impor-

 

 

tance of the individual alarms can be

 

 

defined. Setting is carried out in the

 

 

Alarm destinations” menu.

6

Manual  RS8FK202  ©  Danfoss  12-2009

AK-PC 520

Miscellaneous

 

Miscellaneous

 

 

 

Choice of application

o61

This setting cannot be made via data

The regulator can be configured in various ways. The use that is required out of the

 

communication. It must be set directly

two uses available is set here. The functions for the two uses can be viewed on page

 

on the controller.

14. This menu must be set as the first of all menus, as it enables the associated settings to

 

 

be set.

 

 

1. Show temperature

 

 

2: Show pressure

 

 

 

 

 

Sensor type (Sc3, Sc4 and "Saux1") (see also overview page 21)

o06

Sensor type

Normally a Pt1000 sensor with great signal accuracy is used for temperature measure-

 

 

ment and AKS 32R for pressure measurement. But a PTC sensor may also be used (r25

 

 

= 1000) in special situations.

 

 

All temperature sensors must be of the same kind.

 

 

In brine cooling the pressure measurements are replaced by temperature measure-

 

 

ments.

 

 

The following settings are possible:

 

 

0=PT1000. 1=PTC1000. 2=PT1000 on sensors and on Po. 3=PTC1000 on sensors and

 

 

on Po. 4=PT1000 on sensors and on Pc. 5=PTC1000 on sensors and on Pc. 6=PT1000

 

 

on sensors, on Po and on Pc. 7=PTC1000 on sensors, on Po and on Pc.

 

 

(If a temperature sensor is mounted on P0 or Pc, the respective settings in o20, 21, 47

 

 

and 48 will not be required).

 

 

Settings at water cooler application

o81

Ctrl.Sensor

Definition of the signal inlet when compressor regulation is controlled with signal

 

 

from a temperature sensor:

 

 

0. Temperature signal on terminal 57-58 (P0 inlet)

 

 

1. Temperature signal on Saux inlet

 

 

2. Temperature signal on Sc4 inlet

 

 

(P0 min. function (A11) will not be affected by the definition)

 

 

If frost protection is required, you must connect a pressure transmitter on P0 and the

 

 

temperature sensor must be connected to the Saux or Sc4 input.

 

 

Display connection

o82

 

This is where you define the type of display that is connected to the controller

 

 

Off: EKA 164

 

 

On: EKA 165. The extended display with LEDs.

 

 

Read temperature at sensor "Saux1"

o49

Saux1 temp

Pressure transmitter’s working range

 

 

Depending on the pressure, a pressure transmitter with a given working range is

 

If the values are to be set from the

used. This working range must be set in the controller (e.g.: -1 to 12 bar

 

AKM programme, they must be set in

The values must be set in bar if display in °C has been selected. And in psig, if °F has

 

bar.

been selected.

 

 

P0-Min. value

o20

P0MinTrsPres

P0-Max. value

o21

P0MaxTrsPres

Pc-Min. value

o47

PcMinTrsPres

Pc-Max. value

o48

PcMaxTrsPres

Use of DI1 input

o78

Di1 control

The digital input can be connected to a contact function, and the contact can now be

 

 

used for one of the following functions:

 

 

Setting / function:

 

 

0: DI input not used

 

 

1: Fan alarm when contact cuts out. Alarm "A34" is given.

 

 

2: Alarm function when the contact cuts out. Alarm “A28” is given.

 

 

There is time delay for the alarm. Setting in "A27".

 

 

Use of DI4 input

o22

Di4 control

The digital input can be connected to a contact function, and the contact can now be

 

 

used for one of the following functions:

 

 

Setting / function:

 

 

0: DI input not used

 

 

1: Regulation reference P0 displaced when contact is cut in

 

 

2: Alarm function when the contact cuts out. Alarm “A31” is given. There is no time

 

 

delay.

 

 

Use of DI5 input

o37

Di5 control

The digital input can be connected to a contact function, and the contact can now be

 

 

used for one of the following functions:

 

 

Setting / function:

 

 

0: DI input not used

 

 

1: Regulation reference Pc displaced when contact is cut in

 

 

2: Alarm function when the contact cuts out. Alarm “A32” is given. There is no time

 

 

delay

 

 

AK-PC 520

Manual  RS8FK202  ©  Danfoss  12-2009

7

Operating hours

 

(In the AKM display the hour number

The operating hours for the compressor relays can be read and set in the follow-

 

has not been multiplied)

ing menus. The read value is multiplied by 1000 to obtain the number of hours (f.ex.

 

 

shows 2.1 for 2100 hours). On reaching 99.9 hours the counter stops and must now be

 

 

reset to, say, 0. There will be no alarm or error message for counter overflow.

 

 

Value for relay number 1 to 4

o23-

DO1 run hour.....

 

o26

DO4 run hour

Refrigerant setting

o30

Refrigerant

Before refrigeration is started, the refrigeration must be defined. You may choose

 

 

between the following refrigerants:

 

 

1=R12. 2=R22. 3=R134a. 4=R502. 5=R717. 6=R13. 7=R13b1. 8=R23. 9=R500.

 

 

10=R503. 11=R114. 12=R142b. 13=User defined. 14=R32. 15=R227. 16=R401A.

 

 

17=R507. 18=R402A. 19=R404A. 20=R407C. 21=R407A. 22=R407B. 23=R410A.

 

 

24=R170. 25=R290. 26=R600. 27=R600a. 28=R744. 29=R1270. 30=R417A.

 

 

31=R422A.

 

 

Warning: Wrong selection of refrigerant may cause damage to the compressor.

 

 

Other refrigerants: Select setting 13 here, and subsequently three factors have to be

 

 

set – fac1, fac2 and fac3 – via AKM.

 

 

Manual control (stopped regulation only)

o18

- - -

From this menu the relays can be cut in and out manually. 0 gives no override, but a

 

 

number between 1 and 10 will cut in a belonging relay. 1 will cut in relay number 1, 2

 

 

relay 2, etc.

 

 

11-18 will produce voltage on the analog output. Setting 11 will give a voltage of

 

 

1.25 V, setting 12 will give 2.5 V, etc.

 

 

 

 

 

Frequency

o12

50 / 60 Hz

Set the net frequency.

 

(50=0, 60=1)

Address

 

 

If the controller is built into a network with data communication, it must have an

 

Following installation of a data com-

address, and the master gateway of the data communication must then know this

 

munication module, the controller can

address.

 

be operated on a par with the other

These settings can only be made when a data communication module has been

 

controllers in ADAP-KOOL® refrigera-

mounted in the controller and the installation of the data communication cable has

 

tion controls.

been completed.

 

 

This installation is mentioned in a separate document “RC8AC”.

 

 

The address is set between 1 and 240 (gateway determined)

o03

 

The address is sent to the gateway when the menu is set in pos. ON

o04

 

Access code

o05

 

If the settings in the controller are to be protected by a numerical code, you can set a

 

 

numerical value between 0 and 100. If not, you can cancel the function with setting

 

 

OFF.

 

 

Special settings

 

 

Outputs DO9 and DO10 are normally used for the ”AKD start/stop” function and for the alarm

 

function, but they may be redefined in special cases.

 

 

DO9 function:

o75

DO9 function

0: AKD Start/stop

 

 

1: Inject-on function (see drawing below)

 

 

2: Boost ready function (see drawing below)

 

 

3: Not used

 

 

DO10 function:

o76

DO10 function

0: Alarm relay

 

 

1: Not used

 

 

Status on the digital inputs

 

 

The signal on the DI inputs can be read in the following menus:

 

 

Status on DI 1

u10

DI 1 Status

Status on DI 2

u37

DI 2 Status

Status on DI 3

u87

DI 3 Status

Status on DI 4

u88

DI 4 Status

Status on DI 5

u89

DI 5 Status

8

Manual  RS8FK202  ©  Danfoss  12-2009

AK-PC 520

Loading...
+ 16 hidden pages