The controller is used for capacity regulation of compressors or
condensers in small refrigerating systems.
There are eight outputs and up to 4 compressors and 4 fans can
be coupled.
Advantages
• Energy conservation during:
- Suction pressure optimisation (P0)
- Variable condensing pressure (Pc)
• Patented neutral zone regulation
• Many possible combinations for compressor constellations
• Sequential or cyclic operation
• Possibility of suction pressure optimisation via the data communication
Regulation
Regulation is based on signals from one pressure transmitter for
the compressor regulation and one pressure transmitter for the
condenser regulation plus one temperature sensor for the air
temperature before the condenser.
The two pressure transmitters can be replaced by two
temperature sensors when regulation has to be carried out on
brine systems.
• Pressure regulation P0 (pack)
• Temperature regulation Sx (chiller)
• Pressure regulation Pc (pack / chiller)
• Pressure regulation with variable reference Pc (Sc3)
Functions
• Relays for compressor and condenser regulation
• Voltage output for capacity regulation of condenser
• Status inputs. An interrupted signal indicates that the safety
circuit has been activated and the respective circuit stopped
• Contact inputs for indication of alarms
• Contact inputs for displacement of references or for indication of
alarms
• Alarm relay
• External start/stop of regulation
• Possibility of data communication
Operation
All operation takes place either via data communication or via
connection of a display type EKA 164 or EKA 165.
Combinations
The controller has ten relay outputs two of which have been
reserved for the alarm function and for the ”VLT start/stop”
function.
For a start relays are reserved for compressor capacities starting
from DO1, DO2, etc.
The next relay and the following will be for fans (max. 4 fans).
Another solution could be that the fan speed is controlled via the
analog output and a frequency converter.
Compressors and unloaders can
be combined in various ways. Cf.
survey on page 11.
The cut-in capacity is controlled by signals from the connected
pressure transmitter/temperature sensor and the set reference.
Outside the reference a neutral zone is set where the capacity will
neither be cut in nor out.
Outside the neutral zone (in the hatched areas named +zone and
-zone) the capacity will be cut in or out if the regulation registers a
change of pressure “away” from the neutral zone. Cutin and cutout
will take place with the set time delays.
If the pressure however “approaches” the neutral zone, the controller will make no changes of the cut-in capacity.
If regulation takes place outside the hatched area (named ++zone
and --zone), changes of the cut-in capacity will occur somewhat
faster than if it were in the hatched area.
Cutin of steps can be dened for either sequential or cyclic operation.
Sequential (rst in - last out)
The relays are here cut in in sequence – rst relay number 1, then
2, etc.
Cutout takes place in the opposite sequence, i.e. the last cut-in
relay will be cut out rst.
Cyclic (rst in - rst out)
The relays are coupled here so that the operating time of the
individual relays will become equalised.
At each cutin the regulation scans the individual relays’ timer,
cutting in the relay with least time on it.
At each cutout a similar thing happens. Here the relay is cut out
that has most hours on the timer.
Rx = random relay
h = number of hours
If capacity regulation is carried out on two compressors with one
unloader each, the following function can be used:
Relays 1 and 3 are connected to the compressor motor.
Relays 2 and 4 are connected to the unloaders.
Relays 1 and 3 will operate in such a way that the operating time
for the two relays will become equalised.
The total function content is shown below – not all functions are present at the same
time. The setting of o61 determines which functions are present.
The menu overview on page 14 shows the various functions and settings.
Para-
Function
Normal display
If the two displays are mounted:
P0 will be shown on EKA 165 (the one with buttons)
Pc will be shown on EKA 163. Both readouts will be in temperature or in bar.
Compressor regulation referenceCompressor control
P0 setpoint
Regulation is based on the set value plus an oset, if applicable. An oset can be created from night setback r13 and/or from a system units override function.
Oset
The set reference may be displaced with a xed value when a signal is received at the
DI4 input or from the function "Night setback" (r27).
(Cf. also Denition of DI4 input).
Night setback (Displacement of P0)
OFF: No change of the reference
ON: Oset value forms part of the reference
Reference
The regulation reference is shown here
Set point limitation
With these settings the setpoint can only be set between the two values.
(This also apply if regulation with displacements of the reference).
Max. permissible setpoint value.r25P0RefMax °C / P0RefMax b
Min. permissible setpoint value.r26P0RefMin °C / P0RefMin b
Neutral zone
There is a neutral zone around the reference. See also page 3.
Correction of pressure measurement
An oset adjustment of the registered pressure can be made.
Unit
Here you can select whether the display is to indicate in SI units or US units.
0: SI (°C / bar)
1: US (°F / psig)
Start/stop of refrigeration
With this setting the refrigeration can be started and stopped. Start/stop of refrigeration may also be performed with an external contact function connected to the input
named “ON input”. (The input must be wired).
Condenser regulation referenceCondenser control
Pc setpoint
Regulation is based on the set value plus an oset, if applicable. An oset can be created via the “r34” function and/or from a system units override function.
Oset
The set reference may be displaced with a xed value when a signal is received at the
DI5 input. (Cf. also Denition of DI5 input).
Pc reference variation. See also page 22
Regulation with setting 1 (or 2 if the reference is to vary with the outdoor temperature) will give the best regulation if the system is in balance. But if a lot of condenser
steps are cut in and out and the compressor capacity often becomes low, it will be
necessary to select setting 3 instead (or 4, if there is regulation with the outdoor temperature). (Settings 3 and 4 will generally be preferable if a Pc-oset at max. compressor capacity can be accepted).
1: No change of the reference. Regulation based on set setpoint. And oset with the
DI5 function is allowed.
2: Outdoor temperature forms part of the reference. The outdoor temperature is
measured with Sc3. When the outdoor temperature drops one degree, the reference
is lowered one degree.
Here is oset with the DI5 function not allowed. At DI5 signal the reference will
change to the set setpoint.
Setting 1 and 2 operate with a PI regulation, but if the system is unstable and the PI
regulation not satisfactory the I element may be left out, so that the controller will be
with P regulation only.
3: As 1, but with P regulation (xp-band)
4: As 2, but with P regulation (xp-band)
meter
Parameter by operation via
data communication
P0 °C or P0 b
Pc °C or Pc b
r23P0Set Point °C / P0Set Point b
r13Night oset
r27NightSetBack
r24P0 ref. °C / P0 ref. b
r01Neutral zone
r04AdjustSensor
r05
(In AKM onlySI (bar and °C) is used,
whatever the setting)
With these settings the setpoint can only be set between the two values.
(This also applies to regulations where the Xp band lies above the reference).
Max. permissible setpoint value.r30PcRefMax °C / PcRefMax b
Min. permissible setpoint value.r31PcRefMin °C / PcRefMin b
Correction of pressure measurement
An oset adjustment of the registered pressure can be made.
Dimensioning temperature Dim tm
The mean temperature dierence across the condenser at maximum load (tm dierence at max. load). This is the temperature dierence between the air and condensing
temperature.
Dimensioning temperature Min tm
The mean temperature dierence across the condenser at the lowest relevant
compressor capacity (tm dierence at min. load). This is the temperature dierence
between the air and condensing temperature.
Reading your P0
This is where you can see the actual pressure that is being measured by the pressure
transmitter.
The value is part of the regulation, since the regulation signal for capacity regulation
originates from the pressure transmitter.
The value is part of the frost protection regulation, since the regulation signal for
capacity regulation originates from the temperature sensor.
Reading your T0
This is where you can see the actual pressure being measured by the sensor chosen
for capacity regulation (the sensor is dened in o81). The value is displayed in °C.
Compressor capacityCompressor pack cong.
Running time
To prevent frequent start/stop, values have to be set for how the relays are to cut in
and out.
Min. ON time for relays.
(The time is not used if the relay cuts an unloader in or out).
Min. time period between cutin of same relay.
(The time is not used if the relay cuts an unloader in or out).
Setting for neutral zone regulation
Regulation band over the neutral zonec10+ Zone k / + Zone b
Time delay between step cut-ins in the regulation band over the neutral zonec11+ Zone m
Time delay between step cut-ins in the regulation band over the "+Zone band".c12+ + Zone m
Regulation band under the neutral zonec13- Zone k / - Zone b
Time delay between step cut-outs in the regulation band under the neutral zonec14- Zone m
Time delay between step cut-outs in the regulation band under the "-Zone band"c15- - Zone m
Pump down limit
The factory setting for this function is OFF.
Activate by setting a value corresponding to pressure under the zone and over the P0
min. limit.
The function keeps the last capacity step going until the pressure comes down to the
pump down limit. When this value is reached the last compressor will cut out.
Do not reconnect capacity until the pressure is once more above the neutral zone.
Compressor conguration
Here you set the predened combination of number of compressors and any unloaders.
1 = One compressor, 2 = two compressors, 3 = three, 4 = four.
5 = One compressor + one unloader. 6 = One compressor + two unloaders.For 7 to 8: See survey on page 11
Selection of coupling mode
1. Sequential: First relay 1 cuts in, then relay 2, etc. Cutout takes place in the opposite
sequence. (”First in, last out”).
2. Cyclic: An automatic operating time equalisation is arranged here, so that all steps
with motor connection will have the same operating time
Unloaders’ cutin and cutout mode
The relays for unloaders can be set to switch on when more capacity is required (setting = 0), or they can switch o when more capacity is called for (setting = 1).
Manual control of compressor capacity
This sets the capacity that is to be cut in when switching to manual control.
(c01 and c07 will still apply)
Manual control
Manual control of the compressor capacity is enabled here.
When set to ON, the capacity that is set in “c31” is cut in.
-- - - Comp. Cap %
Read cut-in compressor capacity
Actuel zone state:
0=o. 1= --zone. 2=-zone. 3=Neutralzone. 4=+zone. 5=++zone
Condenser capacity
Denition of condenser and number of fans
Here you set the number of fan steps with which regulation has to be carried out (but
max. four).
1-4: All fans are cut in and out with relays. The rst vacant relay number is assigned to
fan 1, the next to number 2, etc.
5-8: Not used
9: All fans controlled via the analog output and a frequency converter.
10: Not used
11-14: Total number of fan relays (as 1-4), but here the starting sequence is altered
after each time all fans are stopped.
Read temperature at sensor Sc3u44Sc3 temp
Read temperature at sensor Sc4 (sensor is only used for monitoring)u45Sc4 temp
Regulation parameters for the condenser regulation
Proportional band xp (P = 100/Xp)
If the Xp value is increased, the regulation becomes steadier
I: Integration time Tn
If the Tn value is increased, the regulation becomes steadier
Manual control of condenser capacity
This sets the capacity that is to be cut in when switching to manual control.
Manual control
Manual control of the condenser capacity is enabled here.
When set to ON, the capacity that is specied in “n52” is cut in.
Speed control start value
Speed control will only be activated when the capacity requirement reaches this
value.
Speed control stop value
Speed control will be stopped when the capacity requirement falls below this value.
AlarmAlarm settings
The controller can give alarm in dierent situations. When there is an alarm the lightemitting diodes (LED) will ash on the display and the alarm relay will cut in.
P0 min. (Alarm and safety function, see also page 20.)
Here you set when the alarm at too low suction pressure is to enter into eect. The
value is set as an absolute value.
Alarm delay P0 alarm
The time delay is set in minutes. At min. setting the alarm is cancelled.
Pc max. (Alarm and safety function, see also page 20.)
Here you set when the alarm at too high condensing pressure is to enter into eect.
The value is set as an absolute value.
Alarm delay Pc alarm
The time delay is set in minutes. At min. setting the alarm is cancelled.
Alarm delay DI1 (an interrupted input will give alarm).
The time delay is set in minutes. At max. setting the alarm is cancelled.
Alarm delay DI2 (an interrupted input will give alarm).
The time delay is set in minutes. At max. setting the alarm is cancelled.
Alarm delay DI3 (an interrupted input will give alarm).
The time delay is set in minutes. At max. setting the alarm is cancelled.
Alarm limit for high temperature of the “Saux1” sensor
With setting = O the alarm has been opted out.
Alarm delay from "Saux1" (A32)
If the limit value is exceeded, a timer function will commence. The alarm will not become active until the set time delay has been passed. The time delay is set in minutes.
Give the top button a brief push to zeroset the alarm and to have the message shown
on the display.
c29Fan mode
-- - - Fan Cap %
Read cut-in condenser capacity
n04Xp K
n05Tn s
n52FanManCap%
n53FanManCap
n54StartSpeed
n55MinSpeed
A11Min. P0. b
A44P0AlrmDelay
A30Max. Pc. b
A45PcAlrmDelay
A27DI1AlrmDelay
A28DI2AlrmDelay
A29DI3AlrmDelay
A32Saux1 high
A03Alarm delay
Reset alarm
The function zerosets all alarms when
set in pos. ON.
With data communication the importance of the individual alarms can be
dened. Setting is carried out in the
“Alarm destinations” menu.
The regulator can be congured in various ways. The use that is required out of the
two uses available is set here. The functions for the two uses can be viewed on page
14. This menu must be set as the rst of all menus, as it enables the associated settings to
be set.
1. Show temperature
2: Show pressure
Sensor type (Sc3, Sc4 and "Saux1") (see also overview page 21)
Normally a Pt1000 sensor with great signal accuracy is used for temperature measurement and AKS 32R for pressure measurement. But a PTC sensor may also be used (r25
= 1000) in special situations.
All temperature sensors must be of the same kind.
In brine cooling the pressure measurements are replaced by temperature measurements.
The following settings are possible:
0=PT1000. 1=PTC1000. 2=PT1000 on sensors and on Po. 3=PTC1000 on sensors and
on Po. 4=PT1000 on sensors and on Pc. 5=PTC1000 on sensors and on Pc. 6=PT1000
on sensors, on Po and on Pc. 7=PTC1000 on sensors, on Po and on Pc.
(If a temperature sensor is mounted on P0 or Pc, the respective settings in o20, 21, 47
and 48 will not be required).
Settings at water cooler application
Denition of the signal inlet when compressor regulation is controlled with signal
from a temperature sensor:
0. Temperature signal on terminal 57-58 (P0 inlet)
1. Temperature signal on Saux inlet
2. Temperature signal on Sc4 inlet
(P0 min. function (A11) will not be aected by the denition)
If frost protection is required, you must connect a pressure transmitter on P0 and the
temperature sensor must be connected to the Saux or Sc4 input.
Display connection
This is where you dene the type of display that is connected to the controller
O: EKA 164
On: EKA 165. The extended display with LEDs.
Read temperature at sensor "Saux1"o49Saux1 temp
Pressure transmitter’s working range
Depending on the pressure, a pressure transmitter with a given working range is
used. This working range must be set in the controller (e.g.: -1 to 12 bar
The values must be set in bar if display in °C has been selected. And in psig, if °F has
been selected.
The digital input can be connected to a contact function, and the contact can now be
used for one of the following functions:
Setting / function:
0: DI input not used
1: Fan alarm when contact cuts out. Alarm "A34" is given.
2: Alarm function when the contact cuts out. Alarm “A28” is given.
There is time delay for the alarm. Setting in "A27".
Use of DI4 input
The digital input can be connected to a contact function, and the contact can now be
used for one of the following functions:
Setting / function:
0: DI input not used
1: Regulation reference P0 displaced when contact is cut in
2: Alarm function when the contact cuts out. Alarm “A31” is given. There is no time
delay.
Use of DI5 input
The digital input can be connected to a contact function, and the contact can now be
used for one of the following functions:
Setting / function:
0: DI input not used
1: Regulation reference Pc displaced when contact is cut in
2: Alarm function when the contact cuts out. Alarm “A32” is given. There is no time
delay
o61This setting cannot be made via data
communication. It must be set directly
on the controller.
o06Sensor type
o81Ctrl.Sensor
o82
If the values are to be set from the
AKM programme, they must be set in
bar.
The operating hours for the compressor relays can be read and set in the following menus. The read value is multiplied by 1000 to obtain the number of hours (f.ex.
shows 2.1 for 2100 hours). On reaching 99.9 hours the counter stops and must now be
reset to, say, 0. There will be no alarm or error message for counter overow.
Value for relay number 1 to 4o23-
o26
Refrigerant setting
o30Refrigerant
Before refrigeration is started, the refrigeration must be dened. You may choose
between the following refrigerants:
1=R12. 2=R22. 3=R134a. 4=R502. 5=R717. 6=R13. 7=R13b1. 8=R23. 9=R500.
10=R503. 11=R114. 12=R142b. 13=User dened. 14=R32. 15=R227. 16=R401A.
17=R507. 18=R402A. 19=R404A. 20=R407C. 21=R407A. 22=R407B. 23=R410A.
24=R170. 25=R290. 26=R600. 27=R600a. 28=R744. 29=R1270. 30=R417A.
31=R422A.
Warning: Wrong selection of refrigerant may cause damage to the compressor.
Other refrigerants: Select setting 13 here, and subsequently three factors have to be
set – fac1, fac2 and fac3 – via AKM.
Manual control (stopped regulation only)
o18- - From this menu the relays can be cut in and out manually.0 gives no override, but a
number between 1 and 10 will cut in a belonging relay. 1 will cut in relay number 1, 2
relay 2, etc.
11-18 will produce voltage on the analog output. Setting 11 will give a voltage of
1.25 V, setting 12 will give 2.5 V, etc.
(In the AKM display the hour number
has not been multiplied)
DO1 run hour.....
DO4 run hour
Frequency
o1250 / 60 Hz
Set the net frequency.
Address
If the controller is built into a network with data communication, it must have an
address, and the master gateway of the data communication must then know this
address.
These settings can only be made when a data communication module has been
mounted in the controller and the installation of the data communication cable has
been completed.
This installation is mentioned in a separate document “RC8AC”.
The address is set between 1 and 240 (gateway determined)o03
The address is sent to the gateway when the menu is set in pos. ONo04
Access code
o05
If the settings in the controller are to be protected by a numerical code, you can set a
numerical value between 0 and 100. If not, you can cancel the function with setting
OFF.
Special settings
Outputs DO9 and DO10 are normally used for the ”AKD start/stop” function and for the alarm
function, but they may be redened in special cases.
DO9 function:
o75DO9 function
0: AKD Start/stop
1: Inject-on function (see drawing below)
2: Boost ready function (see drawing below)
3: Not used
DO10 function:
o76DO10 function
0: Alarm relay
1: Not used
Status on the digital inputs
The signal on the DI inputs can be read in the following menus:
Status on DI 1u10
Status on DI 2u37
Status on DI 3u87
Status on DI 4u88
Status on DI 5u89
(50=0, 60=1)
Following installation of a data communication module, the controller can
be operated on a par with the other
controllers in ADAP-KOOL® refrigeration controls.