Fact sheet
Capacity Controller
Type AK-PC 351
C:\Users\U250480\Pictures\IMG122426688432(AK_PC 351 Pack
Digital inputs
max. 8 pcs signal from
automatic safety control,
day/night signal
Analogue inputs
• Po suction pressure or S4 media
temperature
• Pc condensing pressure or S7
media temperature
• Sc3 outdoor temperature
• Sd digital scroll/stream media
temperature
Analogue outputs
max. 2 pcs for speed control
of lead compressor and
condenser fan
Controller).tif
Solid state relay
output 1 pcs control of
bypass on a digital scroll or
for controlling unloader on
a stream compressor. If the
output is not used for the
function, it can be used as
ordinary relay output
Relay outputs
max. 5 pcs connection
of compressors,
condenser fans
Compact and powerful
Suction control
Up to 4 compressors in a variety of
combinations:
• Single step
• Variable speed
• Digital scroll
• Stream (4 cylinder)
• Multi step with unloader valves
Condenser control
• Step control of up to 4 fans
• Speed control
Optimised control algorithms and factory settings
• Low and high suction pressure safety
• High condensing pressure safety
• Automatic compressor and fan control override functions to avoid high
pressure cut out
• Smart settings and gain scheduling based on Danfoss refrigeration know-how
• Pump down on last compressor to reduce start/stops at low load
Energy saving features
• Night setback via Digital input or network
• Floating condensing pressure control
• Suction pressure optimisation
Graphical user interface with
• Multi language support
• Overview screens
• Wizard programming
• Celsius or Fahrenheit / Bar or Psi
Application Description
Single step
Single step compressors of
same size
Speed on lead
Speed compressor of one size
single step compressors of
another size
Digital scroll on lead
Digital scroll of one size single step
compressors of another size
Stream 4 cyl. on lead
Stream 4 cyl. of on size single step
compressors of another size
Multistep compressors
Multistep compressors with same
no. of unloader valves and of
same size
Technical data
Features Description
Supply voltage
4 analog Input
8 digital input
Relay output to
capacity control
2 Voltage output 0-10 V d.c. Ri = 1kohm
Display output For type MMIGRS2
Data
communication
Environments
Enclosure IP 40
Weight 0.2 kg
Mounting DIN-rail
Connection
terminals
Approvals
24 V a.c. ± 15 % 50/60 Hz, 17 VA
24 V d.c. (20-60 V ), 17 VA
Pressure measuring:
Ratiometric pressure transmitter type AKS 32R
1-5 volt pressure transmitter type AKS 32
0-20 (4-20) mA pressure transmitter type AKS 33
Temperature measurement
Pt 1000 ohm/0 °C
NTC - 86 K from digital scroll/stream
From contact function
E.g. to:
Start/stop of regulation
Monitoring of safety circuits
General alarm function
5 pcs. SPST (5 A): AC-1: 5 A (ohmic)
5 pcs. SPST (5 A): AC-15: 2 (inductive)
1 pc. Solid State
PWM for scroll -unload
Modbus for AK-SM 850
-20 – 60 °C, During operations
-40 – 70 °C, During transport
20 – 80 % Rh, not condensed
No shock influence/vibrations
max. 2.5 mm2 multi core
EU Low Voltage Directive and EMC demands re
CE-marking complied with
LVD tested acc. EN 60730-1 and EN 60730-2-9
EMC-tested acc. EN61000-6-2 and 3
Imax. = 0.5 A
Imin. = 50 mA
Leak<1.5 mA
Ordering
Typ e Description Code no.
AK-PC 351
24 V AC/20-60 V DC, LCD, RS485, 1SSR S
080G0289
Approvals EU Low Voltage Directive and EMC demands CE-marking complied with
LVD tested acc. EN 60730-1 and EN 60730-2-9
EMC-tested acc. EN61000-6-2 and 3.
Samples and related products For samples and related products, please contact your local Danfoss representative.
RD8CF122 / 520H9033
© Copyright Danfoss | RJA | 10 2014